Connection Steps
Grid Connection
Ø
X1 series inverter are designed for single phase grid. Voltage range is
220/230/240V, frequency is 50/60Hz. Other technical requests should comply
with the requirement of the local public grid.
Micro-breaker should be installed between inverter and grid, any loads should
not be connected with inverter directly.
a) Check the grid voltage and compare with the permissive voltage range (refer
to technical data).
b) Disconnect the circuit-breaker from all the phases and secure against re-
connection.
c) Trip the wires(Choose 8 AWG wire):
- Trip all the wires to 45mm and the PE wire to 47mm.
- Use the crimping pliers to trip 9mm of insulation from Al wire ends as below.
Table 4 Cable and Micro-breaker recommended
Incorrect Connection between Load and Inverter
Cable
Micro-breaker
d) Separate the AC plug into three parts as below.
- Hold the middle part of the female insert, rotate the back shell to
loose it, and detach it from female inset.
- Remove the cable nut (with rubber insert) from the back shell.
e) Slide the cable nut and then back shell onto the cable.
f ) Insert the tripped end of each three wires into the appropriate hole in
the female insert, and then tight each screw (to tight each wire in
place).(2hexagon wrench .torque:0.8
±
0
.
1Nm))
g) Tighten the threaded sleeve
.
h) Screw down the pressure screw.(torque:3
±
0
.
3Nm)
I) Connect the AC plug to the inverter.
20
21
Installation
Installation
Model
12mm
²
50A
*The parameters have some differences because of different environment and material. Please
according to the local conditions to choose appropriate cable and micro-breaker.
9mm
X1-6.0-T-N
X1-6.0-T-D/
X1-7.0-T-N
X1-7.0-T-D/
X1-8.0-T-N
X1-8.0-T-D/
12mm
²
50A
12mm
²
50A
45mm
47mm