5.5 Connection of the Inverter

PV String Connection

Ø

X1series inverter have a couple of PV connectors which can be connected in 
series  into 2-strings PV modules. Please select PV modules with excellent function 
and reliable quality. Open circuit voltage of module array connected should be 

Max.DC (table as follow) input voltage, and operating voltage should be within 
the MPPT voltage range. 

Table 3   Max. DC  Voltage Limitation

Max.DC Voltage

Warning!

PV module voltage is very high which belongs to dangerous 
voltage range, please comply with the electric safety rules when 
connecting.

Warning!

Please do not make PV positive or negative ground!

Note!

Please follow the requirements of PV modules as below:
Same type; Same quantity; Identical alignment; Identical tilt.
In order to save cable and reduce the DC loss, we suggest 
installing the inverter near PV modules.

5.5.1  The Main Steps to Connect to the Inverter

Connection Steps

a)  Turn off the DC switch.
b)  Choose 12 AWG wire to connect the PV module.
c)  Trip 7mm of insulation from the wire end.
d)  Separate the DC connector as below.

d)  Separate the DC connector as below.

e)  Insert striped cable into pin contact and ensure all conductor strand are 
captured in the pin contact.
f )  Crimp pin contact by using a crimping pliers. Put the pin contact with 
striped cable into the corresponding crimping pliers and crimp the 
contact.(torque:1.2

±

0

.

1Nm)

g)  Insert pin contact through the cable nut to assemble into back of the male 
or female plug. When you feel or heard a “click” the pin contact assembly is 
seated correctly.(torque:1.2

±

0

.

1Nm)

7.0 mm

12AWG

trip length

plug

pin contact

cable nut

18

19

Installation 

Installation 

Model

Note!

Please choose a suitable external DC switch if the model (X1

-

6

.

0

-

T

-

N

,

X1

-

7.0-T

-

N

,

X1

-

8.0

-

T

-

N) is purchased.

Note!

PV connection mode below is not allowed!

Inverter

PV array

PV1

PV2

+

-

+

-

+

-

+

-

+

-

x

Danger!

Danger to life due to high voltages on DC conductors.
when exposed to sunlight,the PV array generates dangerous DC 
voltage which is present in the DC conductors.Touching the DC 
conductors can lead to lethal electric shocks.
Cover the PV modules.        
Do not touch the DC conductors.

550V

X1-6.0-T-N

X1-6.0-T-D/

X1-7.0-T-N

X1-7.0-T-D/

X1-8.0-T-N

X1-8.0-T-D/

Содержание X1-6.0-T-D

Страница 1: ...nual belongs to SolaX Power Network Technology Zhe jiang Co Ltd Any corporation or individual should not plagiarize partially or fully copy including software etc and no reproduction or distribution of it in any form or by any means All rights reserved SolaX Power Network Technology Zhe jiang Co Ltd reserves the right of final interpretation ...

Страница 2: ...rter 3 3 Dimension 4 Technical Data 4 1 DC Input 4 2 AC Output 4 3 Efficiency Safety and Protection 4 4 General Data 5 Installation 5 1 Check for Transport Damage 5 2 Packing List 5 3 Installation Precaution 5 4 Installation Steps 5 5 Connection of the Inverter 5 6 Run the Inverter 6 Operation Method 6 1 Control Panel 6 2 LCD Function 6 3 LCD Operation Contents 01 03 03 03 03 04 04 06 09 10 11 11 ...

Страница 3: ...Symbols Used The following types of safety instructions and general information appear in this document as described below Danger Danger indicates a hazardous situation which if not avoided will result in death or serious injury Warning Warning indicates a hazardous situation which if not avoided could result in death or serious injury Caution Caution indicates a hazardous situation which if not a...

Страница 4: ...ween the inverter and the PV generator if the voltage protection level VP of the surge arresters is greater than 1100V an additional SPD type 3 required for surge protection for electrical devices To protect the AC system surge suppression devices SPD type2 should be fitted at the main incoming point of AC supply at the consumer s cutout located between the inverter and the meter distribution syst...

Страница 5: ...ing wiring is in good condition and that wire is not undersized Do not disassemble any parts of inverter which are not mentioned in installation guide It contains no user serviceable parts See Warranty for instructions on obtaining service Attempting to service the X1 Series inverter yourself may result in a risk of electric shock or fire and will void your warranty Keep away from flammable explos...

Страница 6: ...el Symbols on the Inverter Symbol Explanation Operating Display Communication is active An error has occurred please inform your installer immediately Symbols on the Type Label Symbol Explanation CE mark The inverter complies with the requirements of the applicable CE guildlines RCM remark SAA certification Beware of hot surface The inverter can become hot during operation Avoid contact during ope...

Страница 7: ... upon installing and configuring system correctly including using the specified wires The system must be installed only by professional assemblers who are familiar with requirements for safety and EMC The assembler is responsible for ensuring that the end system complies with all the relevant laws in the country where it is to be used The individual subassembly of the system shall be interconnecte...

Страница 8: ...al AC Connector B C D E F G Description Waterproof Valve 12 13 Introduction Technical Data Model Model 45 0 37 3 1 0 8 leading 0 8 lagging single phase Max output overcurrent protection A Max inverter backfeed current to the array mA optional 401mm 450mm 213mm RS 485 NFI DRM optional 3000 4000 550 360 100 500 11 22 12 24 120 2 X1 6 0 T N X1 6 0 T D 550 X1 7 0 T N 3000 5000 360 100 500 11 22 12 24 ...

Страница 9: ...100 non condensing 2000 IP65 Transformerless Ⅰ 1w Ⅲ MAINS Ⅱ PV Ⅱ External natural wind Internal intelligent fan 40dB Non isolated RS485 NFI optional DRM WIFI GPRS LAN USB Standard 5 years 10 years optional 5 Installation 5 1 Check for Transport Damage 5 2 Packing List Make sure the inverter is intact during transportation If there are some visible damages such as cracks please contact your dealer ...

Страница 10: ... Step 2 Match the inverter with wall bracket Ø Ø Ø Below tools are needed before installation Installation tools crimping pliers for binding post and RJ 45 screwdriver manual wrench and Φ10 driller a Use the wall bracket as a template to mark the position of the 4 holes on the wall b Drill holes with driller make sure the holes are deep enough at least 50mm for installation and then tighten the ex...

Страница 11: ...Trip 7mm of insulation from the wire end d Separate the DC connector as below d Separate the DC connector as below e Insert striped cable into pin contact and ensure all conductor strand are captured in the pin contact f Crimp pin contact by using a crimping pliers Put the pin contact with striped cable into the corresponding crimping pliers and crimp the contact torque 1 2 0 1Nm g Insert pin cont...

Страница 12: ... Connection between Load and Inverter Cable Micro breaker d Separate the AC plug into three parts as below Hold the middle part of the female insert rotate the back shell to loose it and detach it from female inset Remove the cable nut with rubber insert from the back shell e Slide the cable nut and then back shell onto the cable f Insert the tripped end of each three wires into the appropriate ho...

Страница 13: ...not provided galvanic isolation from the mains to the PV array feedback current to the array is 0A 250VAC for 6 0KW 7 0KW 8 0KW based on the fuse provided in the mains Also in the worst case the reverse current comprises the sum of the short circuit currents of all intact lines Therefore the current carrying capacity of the components and sub assemblies provided in the end use system connectors ca...

Страница 14: ...he waterproof connector with RJ45 then insert it into the RJ45 connector following the PIN definition rule 4 Crimp the RJ45 connector with the crimping plier 5 Insert the cable into the RS 485 NFI port of the inverter and tighten the waterproof connector DRM is provided to support several demand response modes by giving control signals as below 1 8 c DRM 24 25 Installation Installation PIN Definit...

Страница 15: ...h fault alarm is the additional detection as required by AS 4777 2 and AS NZS 5033 it will give an alarm once the earth impedance of the PV arrays is less than 30KΩ Earth Fault Alarm Optional 26 27 Installation Installation 5 After the upgrade is complete please remember to turn off the DC switch or disconnect the PV connector then pull off the U disk screw the waterproof lid Note Vx xx is version...

Страница 16: ... which means inverter starting Waiting Inverter is waiting to checking when DC input voltage from panels is greater than 100V lowest start up voltage but less than 150V lowest operating voltage Checking Inverter will check DC input environment automatically when DC input voltage from the PV panels exceeds 150V and PV panels have enough energy to start inverter Normal Inverter begins to operate nor...

Страница 17: ...s the power generated within the day Normal shows the status of the inverter Menu interface The menu interface is a transfer interface for user to get into other interface to finish the setting or getting the information User can get into this interface by pressing OK button when LCD displays the main interface User can select interface by moving the cursor with function button and press OK to con...

Страница 18: ... 0 0 Safety country AS4777 Setting Safety Date Time New Password a Safety The user can set the safety standard here According to different countries and grid tied standards There is 2 standards for choice May change without notice b Solar This status shows the real time PV condition of the system such as input voltage current and power situation of each PV input Press up and down button to review ...

Страница 19: ...Excited PF p Q u Fixed Q Power Mode Comment Off Under Excited PF value Over Excited PF value PF p Upper limit Lower limit Power Upper Power Lower Q u QuVupRate QuVlowRate Reactive power control Reactive standard curve cos φ f P For VDE ARN 4105 curve cos φ p should refer to curve A default values of setting are as shown in curve A For E 8001 curve cos φ f P should refer to curve B default values o...

Страница 20: ...quency low protect Fac upper slow Frequency high slow protect Fac lower slow Frequency low slow protect Vac 10m avg 10 min voltage high protect 36 Operation Method Operation Method P u Function Enable Disable e P u Function The device is suitable for Australia if the Enable is chosen Enable h DRM Function User can choose whether using the DRM function or not DRM Function Mode Select Disable 37 j R...

Страница 21: ...e items About This interface shows information of the inverter include product SN register SN machine type master DSP1 slave DSP2 and manager Error log No error About Product SN 0123456 7 Troubleshooting 7 1 Trouble shooting This section contains information and procedures for solving possible problems with X1 series inverters and provides you with troubleshooting tips to identify and solve most p...

Страница 22: ...er located in a clean dry adequately ventilated place Have the DC input breakers been opened Are the cables adequately sized and short enough Are the input and output connections and wiring in good condition Are the configurations settings correct for your particular installation Are the display panel and the communications cable properly connected and undamaged Contact Solax Customer Service for ...

Страница 23: ...ter are in normal state check if the keys of the inverter are in normal state check if the display of the inverter is normal This check should be performed at least every 6 months 3 Check that if the input and output wires are damaged or aged This check should be performed at least every 6 months 4 You should get the inverter panels cleaned and their security checked at least every 6 months 8 Deco...

Страница 24: ......

Отзывы: