5. Commissioning

5. Commissioning

28

29

Note!

When powering on the BMS, the system will start self-testing. If the 
buzzer bips, it means DIP configuration fault or communication failure 
occurs. If the buzzer bips, please check if the number of battery 
modules is corresponding to the DIP configuration, and also check if 
the RS485 communication calbes are correctly connected. After these 
two situation checked OK, press the POWER button to power on, and 
press the POWER button again 10s later. In addition: The buzzer will only 
alarm on the corresponding fault during the power-on self-test. After 
the self-test is completed, it won't bip again even if the same fault 
occurs.

5.2 

 Commissioning

Verify the model number of each battery module to make sure that they are all 
the same model. 
If all the battery modules are installed, follow these steps to put it in operation.
1. Configure the DIP (

) to corresponding number accroding to the number of 

battery module(s) that has(have) been installed;
2. Remove the cover board of BMS;
3. Move the circuit breaker switch 

(Ⅴ

) to the ON position;

4. Press the POWER button (

) to turn on the T-BAT system;

5. Reinstall the cover board to BMS;
6. Turn on Inverter AC switch.

Note!

Frequently press the POWER button may cause the system error. Please 
make sure at least 10 seconds is needed when you are going to press 
the POWER button from the last pressing operation.

3

4

2

Содержание HV10045

Страница 1: ...X Power Co Ltd Any corporation or individual should not plagiarize partitially or fully copy including software etc and no reproduction or distribution of it in any form or by any means All rights res...

Страница 2: ...5 2 3 QUALIFIED INSTALLER 6 3 PRODUCT INTRODUCTION 7 3 1 PRODUCT OVERVIEW 7 3 1 1 DIMENSION AND WEIGHT 7 3 1 2 APPEARANCE 8 3 2 BASIC FEATURES 10 3 2 1 FEATURES 10 3 2 2 CERTIFICATIONS 10 3 3 SPECIFI...

Страница 3: ...on indicates a hazardous situation which if not avoided could result in minor or moderate injury Note Note provides tips that are valuable for the optimal operation of your product 4 5 CABLE CONNECTIO...

Страница 4: ...he medical equipment and automotive application Warning Please don t crush or impact the battery and always dispose it according to the safety regulation 2 1 2 Explanation of Symbols This section give...

Страница 5: ...ith flowing water for 15 minutes and seek medical attention immediately Dermal contact Wash the affected area thoroughly with soap and water and seek medical attention immediately Ingestion Induce vom...

Страница 6: ...ual and all safety precautions and best practices 6 7 3 Product Introduction 3 1 Product Overview For safety reasons installers are responsible for familiarizing themselves with the contents of this m...

Страница 7: ...r Button CAN Connector Charge Discharge Connectors Object Mark Description XPLUG RS485 I GND RS485 II YPLUG S1 S2 SOC 25 50 75 100 Status 3 1 2 Appearance Section view of MC0500 Status Capacity Power...

Страница 8: ...V Configuration List 3 3 2 Performance Model BMS Battery Module Energy kWh Voltage V No 1 2 3 4 5 6 7 8 T BAT H4 5 T BAT H9 0 T BAT H13 5 T BAT H18 0 T BAT H6 3 T BAT H12 6 T BAT H18 9 T BAT H25 2 MC0...

Страница 9: ...he optimal temperature range for the battery module to operate is 15 C to 30 C Frequent exposure to harsh temperatures may deteriorate the performance and lifetime of the battery module 4 2 Safety Gea...

Страница 10: ...m CAN communication cable 2m RS485 communication cable 120mm Short circuit plug M5 screw Ground wire Rotation wrench L type wrench Quantity 1 1 1 1 1 1 4 1 1 1 E J A1 B1 E1 F1 C1 D1 Battery Module T45...

Страница 11: ...nd the appropriate expansion scree sleeves if you want to change the mounting mode Floor mounting or wall mounting is a mandatory requirement for installation Wrong cable connection might occur if the...

Страница 12: ...he following figure is the back view of wall mounting 1m 300 mm Note Keep the distance from installation point to the floor less than 1m 4 5 Cable Connection 4 5 1 Connecting Power Cables For one batt...

Страница 13: ...e power cable Notes for Unplugging Power Cables Caution 4 Installation 4 Installation 20 21 For 2 4 battery modules The power cable between battery modules A1 is different from the one that between BM...

Страница 14: ...battery module The communication ports are marked at the following figure For 2 4 battery modules 1 There s a protect cover for the RS485 connector unscrew the cover and plug one end of the RS485 comm...

Страница 15: ...cting Ground Wire Unscrew the ground terminal with hexagon wrench on BMS and battery module at either side of the ground port as marked at the following figure Connect the ground wire from BMS to batt...

Страница 16: ...DIP switch is used to configure the number of battery modules which are communicating to Inverter The detailed configuration information is shown as follows 0 1 2 3 4 5 6 7 Configuration activated by...

Страница 17: ...he self test is completed it won t bip again even if the same fault occurs 5 2 Commissioning Verify the model number of each battery module to make sure that they are all the same model If all the bat...

Страница 18: ...ash once every 5s Take SOC 60 for instance in discharging state 1 The last three blue LED indicators flash once every 5s The following table shows the status of BMS Capacity Status Capacity Status Cha...

Страница 19: ...on Please contact SolaX after sales service or your distributor directly BMS_DishargeOCP Battery discharge over current protection Please contact SolaX after sales service or your distributor directly...

Страница 20: ...nect the series wiring terminal on the ended battery Disconnect the other cables 7 2 Packing Please pack the BMS and battery modules with the original packaging If it is no longer available you can al...

Отзывы: