TROUBLESHOOTING 

Calibration Sequence Troubleshooting 

Should any of the following scenarios occur, please check the 
following: 

Concern: 

Calibration sequence begins as normal but 

concludes with “Calibration sequence LED” turning from blue 
to red. 

Cause:

 Restrictor opened fully without the pressure switch 

closing. 

Check:  

1.

 

Is the pressure switch plugged in?  

2.

 

Has pressure tube been installed on wrong port on 
pressure switch? (Should be connected to light 
colored port). 

 

 

3.

 

Actuate pressure switch manually (suck on pressure 
line), does “pressure” LED light up? If not, replace 
pressure switch. 

 

 

4.

 

Is the fireplace fully assembled, glass installed on the 
fireplace?  

5.

 

Is the vent system within approved configurations for 
this appliance?  

6.

 

Is the vent system free of leaks, compromised or poor 
joints? 

7.

 

Is Termination wire harness securely plugged into 
both the control and the termination? 

Concern: “

Calibration Status LED” turns red when “Calibration” 

button is pressed. 

 

 

Cause:

 Pressure switch is closed while power vent is off. 

Check:  

1.

 

Actuate pressure switch manually (suck on pressure 
line), try again. “Pressure LED” should illuminate as the 
switch is actuated. 

2.

 

Replace pressure switch. 

 

Concern:

 Calibration sequence does not start. 

Cause:

 Powervent control is turned off, does not have power, or 

is currently performing a purge cycle. 

Check: 

1.

 

Power vent control is currently in its purge cycle, the 
“Operation Status LED” will be blue during the purge 
cycle. Once the purge cycle ends after 60 seconds, the 
LED will turn off and a calibration cycle can be initiated. 

 

 

2.

 

Check that “Power LED” is illuminated, if not, turn on 
the power vent control. 

3.

 

Connect power to Power vent control. 

 

OPERATION STATUS LED 

CALIBRATION STATUS LED 

PRESSURE LED 

CALIBRATE BUTTON 

PRESSURE LED 

ON/OFF SWITCH 

POWER LED 

TERMINATION 

HARNESS 

PLUG 

INSTALL PRESSURE TUBE ON THE GREY PORT 

Содержание SCPV-12218-100

Страница 1: ...CONTROL CONTROL AND AND AND AND TERMINATION TERMINATION TERMINATION TERMINATION KIT KIT KIT KIT Ce manual est disponsible en Francais sur demande SCPV 900C SHOWN S LAS STRONGLY SUGGESTS THAT YOU READ...

Страница 2: ......

Страница 3: ...ibration and Operation 17 Troubleshooting 20 Replacement Parts List 22 Warranty Information 23 WARNING This installation manual covers the functional requirements for optimal performance of your firep...

Страница 4: ...Powervent control kit SCPV 914GS Self Calibrating Power Vent Gas Solenoid required for all power vent installations Only gas solenoids certified for use by S LAS are to be used with the S LAS Self Ca...

Страница 5: ...s termination requires the use of SCPV 946DVA Self Calibrating Power Vent Pressure Port Vent Adapter SCPV 459SM Self Calibrating Power Vent Surface Mount Termination for use with vent runs over 10 fee...

Страница 6: ...0 SSL BI 60 SSR BI 60 ST BI 72 SSL BI 72 SSR BI 72 ST This kit uses either M G Duravent direct vent pipe Secure Vent direct vent pipe or Selkirk Direct temp vent pipe with a 4 inner pipe and a 6 5 8 o...

Страница 7: ...6 FLUSH MOUNT TERMINATION SPECIFICATIONS SCPV 160FM Self Calibrating Flush Mount Power Vent Dimensions SCPV 160FM Self Calibrating Flush Mount Power Vent Cavity Dimensions NAILING FLANGE FLUE OUTLET...

Страница 8: ...9SM Self Calibrating Surface Mount Power Vent Dimensions SCPV 459SM Self Calibrating Surface Mount Power Vent Cavity Dimensions These dimensions apply to SCPV 459SM and SCPV 459SM 10 see page 12 for S...

Страница 9: ...rom the center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8 m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any oth...

Страница 10: ...minimum clearance to combustibles and electrical wiring of 1 5 38mm is required around the vent pipe at all times Failure to maintain this clearance may result in property damage injury or death NOTE...

Страница 11: ...heathing is 14 50 368mm wide by 14 50 368mm tall as shown in the image right 2 The power vent termination is secured to the sidewall by the left right top and bottom nailing flanges shown on page 6 3...

Страница 12: ...ening required in the framing and exterior sheathing is 14 50 368mm wide by 10 00 254mm tall as shown in the image right 2 The power vent termination is secured to the sidewall by the left and right n...

Страница 13: ...nsional requirements for the site fabricated chase WARNING This installation manual covers the functional requirements for optimal performance of your fireplace with power vent installation consult wi...

Страница 14: ...outlet is on the 12 9 328mm long side of the chase 2 Exterior dimensions of the site fabricated chase should be 18 9 480mm long by 455mm wide The exhaust outlet is on the 18 9 480mm long side of the c...

Страница 15: ...e top edge of the Self Calibrating Power Vent Control The lower Termination Harness Plug is for the Termination Wire Harness which carries power to the power vent and restrictor position signals back...

Страница 16: ...ent control SCPV 900C Only use the length of tubing that is necessary for your installation trim to length Tape all seams in the venting system using Aluminum Foil HVAC Tape For vent runs that are und...

Страница 17: ...ace is enclosed within the wall WARNING All electrical shall be completed by a licensed Electrician and must conform with local building code Improper installation may result in property damage injury...

Страница 18: ...N THE POWER VENT CONTROL THE CONTROL WILL BEGIN A 60 SECOND PURGE CYCLE DURING THIS PURGE CYCLE THE CALIBRATION SEQUENCE CANNOT BE INITIATED DURING THE PURGE CYCLE THE OPERATION STATUS LED WILL BE BLU...

Страница 19: ...quence at any time in the product s life this is ok 3 Without any user intervention the calibration sequence is as follows The restrictor contained within the power vent termination will close Once th...

Страница 20: ...PRESSED ON THE POWER VENT CONTROL THE CONTROL WILL BEGIN A 60 SECOND PURGE CYCLE DURING THIS PURGE CYCLE THE CALIBRATION SEQUENCE CANNOT BE INITIATED DURING THE PURGE CYCLE THE OPERATION STATUS LED WI...

Страница 21: ...securely plugged into both the control and the termination Concern Calibration Status LED turns red when Calibration button is pressed Cause Pressure switch is closed while power vent is off Check 1...

Страница 22: ...status LED turns red after the pilot lights but before the main burner ignites Cause Power vent control did not get signal pressure switch has closed Check 1 Is the pressure switch plugged in 2 Actuat...

Страница 23: ...wer Vent Flush Mount Termination requires SCPV 946DVA 10 SCPV 459SM Self Calibrating Power Vent Surface Mount Termination for use with vent runs over 10 feet in length requires SCPV 946DVA 11 SCPV 459...

Страница 24: ...and will nullify this warranty This warranty is void if a The unit has been operated in atmospheres contaminated by chlorine fluorine or other damaging chemicals b The unit is subject to submersion i...

Страница 25: ...24 V1 5 5 20...

Отзывы: