![Solas ONE6 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/solas/one6/one6_installation-and-operation-manual_1314167008.webp)
SÓLAS
CONTEMPORARY FIRE
8
The gas fireplace is shipped with a 3/8" tube OD (male
flare) connection. The gas supply piping should have a
separate gas shutoff valve and a 1/8" NPT plugged tapping
upstream of the valve. The stove and its main control
valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test
pressures in excess of 1/2 psi (3.5 kPa). The stove must be
isolated from the gas supply piping system by closing the
main control valve during any pressure testing of the gas
supply system at test pressures equal to or greater than
1/2 psi (3.5 kPa). After the gas supply has been connected,
use a commercial gas leak detector or apply a soapy water
solution to all the fittings to check for gas leaks. Never use
a flame to test for leaks.
A COPY OF THESE INSTRUCTIONS PLUS ALL
VENTING INSTRUCTIONS WHICH INCLUDE
PARTS LISTS, AND/OR ALL VENTING DESIGN
INSTRUCTIONS MUST REMAIN WITH THE STOVE AT
THE COMPLETION OF THE INSTALLATION.
ATTENTION INSTALLERS: Mark below which venting
system was used in the installation. These instructions
must remain with the SÓLAS Gas Fireplace Installation
& Operation Manual.
O Simpson DuraVent GS/PRO®
O Selkirk Direct-Temp®
O Security Secure Vent™
O AmeriVent Direct™
O Metal Fab Direct Vent
O ICC Direct Vent
NOTICE
Failure to follow these instructions will void the
warranty.
INSTALLATION REQUIREMENTS / GAS CONNECTION
STATE OF MASSACHUSETTS
The installation must be completed by a licensed
plumber or gas fitter in the Commonwealth of
Massachusetts.
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
This product must be installed by a licensed plumber
or gas fitter when installed within the Commonwealth
of Massachusetts. If this appliance is installed in a
dwelling, building or structure used in whole or in part
for residential purposes and the installation includes a
horizontal vent termination that is less than seven (7)
feet above the finished grade in the area of the venting,
including but not limited to decks and porches, a hard-
wired carbon monoxide detector with an alarm and
battery back-up must be installed on the floor level of the
dwelling, building or structure where the appliance is to
be installed.
Additionally, a hard-wired or battery operated carbon
monoxide detector with an alarm must be installed
on each additional level of the dwelling, building
or structure served by the appliance. It shall be the
responsibility of the property owner to secure the
services of qualified licensed professionals for the
installation of hard-wired carbon monoxide detectors.
In the event that the horizontally vented appliance is
installed in a crawl space or attic, the hardwired carbon
monoxide detector with alarm and battery back-up may
be installed on the next adjacent floor level.
In the event that this requirement cannot be met at the
time of completion of the installation of the appliance,
the owner shall have a period of thirty (30) days to
comply with the requirement. However, during said thirty
(30) day period, a battery operated carbon monoxide
detector with alarm must be installed.
Each carbon monoxide detector as required in
accordance with the above provisions must comply with
NFPA 720 and be ANSI/UL 2034 and IAS certified.
In addition, when the vent termination is less than
seven (7) feet above finished grade a metal or plastic
identification plate must be permanently mounted to the
exterior of the building at a minimum height of eight (8)
feet above grade directly in line with the exhaust vent
terminal. The sign shall read, in print size no less than
one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS".