Just as with any other vented device, vertical vent rise creates draft (negative pressure) in the firebox as the 
exhaust gases heat up.  If this draft becomes excessive, it can affect the performance or appearance of the 
fire.  The Solas Nua Freestanding Stove includes air and exhaust restrictors that are used to balance the 
draft in the fireplace to the optimal level for installations where excessive draft might occur.  The venting 
charts on pages 9 and 10 provide an easy means for determining whether your specific installation requires 
inlet air or exhaust restrictors or both.  To make the determination about whether air or exhaust restrictors 
are needed, a venting chart worksheet is provided on page 11.  Follow the instructions and fill in the work-
sheet for your particular installation.  This will allow you to determine the recommended restrictor settings 
for your exact installation.  Although this might appear to be a complicated process at first glance, it is 
really quite straight-forward and the result will be a fire that looks and performs as intended.  Several ex-
amples of worksheet calculations are shown on page 12 to help guide you.   
Please be sure to note that: 
1.  There are separate venting charts for Natural Gas and LP Gas.  Refer to the appropriate chart for your 

fuel type to determine your specific restrictor requirements.  The settings in the charts have been deter-
mined based on extensive testing. 

2.  Determine the total vertical vent rise and total horizontal vent run for your installation.  All measure-

ments are made from the center of the vent opening in the back of the fireplace. 

3.  If your stove will not be venting directly though an outside wall to a horizontal termination or if more 

than 30” of horizontal vent run is required, some vertical vent rise will be required for the fireplace to 
function and vent properly.  Elbows will also be required for those installations.  However, installations 
are limited to a maximum of four 90° elbows (or 45° elbow equivalents).   

4.  Note: Two 45° elbows equal one 90° elbow. 
5.  The recommended restrictor settings in the venting charts allow up to two 90° elbows (or 45° elbow 

equivalents) to be used without affecting the restrictor settings.  Additional elbows will require that you 
calculate a new equivalent horizontal run for your installation to account for the additional flow resis-
tance caused by the extra elbows.  For the purposes of calculating the equivalent horizontal vent run, 
each additional 90° elbow is equivalent to three feet of horizontal vent run.  The total horizontal vent 
run including elbow equivalents can not exceed 10 feet. 

6.  The maximum vertical vent rise can not exceed 20 feet. 
7.  There are two exhaust restrictors that are provided with your Solas Nua Stove  .  They are labeled “A” 

and “B”.  The A restrictor provides less exhaust restriction than B. 

8.  An air restrictor plate is also provided with your stove.  It is a ring with bendable tabs that can be set to 

adjust the amount of restriction in the air supply system.  Once the appropriate number tabs are bent 
open (in accordance with the requirements for your installation), the plate is inserted between the stove 
and the vent starter pipe. 

 

USING THE VENTING CHARTS 

 

The location of the vent termination must meet the requirements of the current edition of ANSI Z223.1/
NFPA 54, National Fuel Gas Code or CAN B419.1, Natural Gas and Propane Installation Code and the 
requirements shown on page 15 of this manual. 

Содержание FS-16N RV

Страница 1: ...lowed exactly a fire or explosion may result causing property dam age personal injury or loss of life WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch d...

Страница 2: ...NSTALLATION RECORD FORM 38 WARRANTY INFORMATION 39 TABLE OF CONTENTS WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BE GININNG THE INSTALLATION OF THE SOLAS NUA FREESTANDING DIRECT VE...

Страница 3: ...of the appliance A commercially available hearth pad meets this requirement The appliance area must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids Th...

Страница 4: ...r use with the fuel type indicated on the rating plate This appliance has been certified by OMNI Test Laboratories Inc to ANSI Z21 88a 2007 CSA 2 33a 2007 Vented Gas Fireplace Heaters and CAN CGA 2 17...

Страница 5: ...ruction are listed below In addition access to the gas supply must be considered The location of the stove will also affect the venting requirements and you must be certain the location will allow com...

Страница 6: ...d on each additional level of the dwelling building or structure served by the appliance It shall be the responsibility of the property owner to secure the services of qualified licensed professionals...

Страница 7: ...installation will include at least one 90 elbow Up to three additional 90 elbows or equivalent 45 elbows may also be used The total venting may not exceed 20 feet of vertical rise and or 10 feet hori...

Страница 8: ...r stove will not be venting directly though an outside wall to a horizontal termination or if more than 30 of horizontal vent run is required some vertical vent rise will be required for the fireplace...

Страница 9: ...B NU B NU B NU 11 10 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU 10 9 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU 9 8 B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU B NU...

Страница 10: ...B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 10 9 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 B 3 9 8 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 8 7 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 B 4 7 6 B 4 B 4...

Страница 11: ...A VERTI CAL RISE AND HORIZONTAL RUN SNORKEL CAPS HAVE BUILT IN VERTICAL RISE THAT MUST BE COUNTED D TOTAL NUMBER OF 90 ELBOWS _______ NOTE SNORKELS COUNT AS 2 90 ELBOWS E TOTAL NUMBER OF 45 ELBOWS __...

Страница 12: ...zontal Run Exhaust Restrictor Required B Air Restrictor Tabs Open 3 A Fuel LP Gas B Total Vertical Vent Rise 2 feet C Total Horizontal Vent Run Actual 10 feet D 90 Elbows Needed 2 E 45 Elbows Needed 0...

Страница 13: ...13 VENT TERMINAL CLEARANCES Venting terminals shall not be recessed into a wall or siding...

Страница 14: ...items 1 Installation and operation Manual 2 A C Adapter 3 Vent Restrictor Kit 4 Glass Media burner 5 Remote Control 6 Battery Pack 7 Levelling bolts 4 8 Blow Off Relief Door The stove has been bolted...

Страница 15: ...page 7 to make that determination If your installation does require an air restrictor or exhaust restrictor or both these must be installed be fore you connect your vent system to the stove Again refe...

Страница 16: ...ove body 6 Place the vent starter pipe gasket on the back of the stove aligning the holes in the gasket with the pilot holes on the rear of the fireplace 7 Align the inner pipe of the vent starter pip...

Страница 17: ...lly clip one corner of the poly bag to form a pouring spout The opening should be large enough to allow the glass media to flow but not so large that you can t control the flow 3 You will notice that...

Страница 18: ...f door enough to allow the rear line up tab to engage the rear retainer slot Refer to the sec ond illustration below 5 Rotate the front edge of each relief door so they line up over front retainers 6...

Страница 19: ...Replace the battery pack on the bracket and secure with the hook and eye strap 6 Reconnect the battery connector to the Electronic Module Note An optional A C adapter is also supplied with the unit a...

Страница 20: ...tom front of the fire box Take care to center the frame from left to right 3 Once the bottom edge is in place move your fingers out of the way and press the top of the frame against the firebox while...

Страница 21: ...system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5kPa 6 The fireplace must be isolated from the gas supply piping system by closing the gas shut off valve dur...

Страница 22: ...the pilot Do not try to light the pilot by hand 3 If using the Remote Handset push the button until you hear an audible signal to insure the appliance is off 4 Wait five 5 minutes to clear out any ga...

Страница 23: ...burner has been in operation for a few minutes the flames should look like those in the illustration below Note The flame height will vary depending on the firing rate setting but flames should be eve...

Страница 24: ...te that the system has accepted the order and the flame will light on the High setting To decrease the flame level press the DOWN button A beep and a flash of the LED indicate that the sys tem has acc...

Страница 25: ...me C Signal strength D Selected working mode E Selected setting F Current flame status G Current fan status Not Applicable on this appliance H Current room temperature I Child lock status J Button lab...

Страница 26: ...ible that the remote is locked in the OFF screen to unlock it just press the button below Unlock and then OK 2 3 Switching on Once the remote is unlocked press ON left button and OK middle button A be...

Страница 27: ...27 COPRECI R emotion CONTROL SYSTEM...

Страница 28: ...et in the configuration menu This specified the maximum permitted room temperature This temperature can never be set higher than 104 F 40 C It is recommended you set to 95 F 35 C Auto Thermostatic Mod...

Страница 29: ...ppliance will heat until this temperature is reached Comfort Temp The comfort temperature is set as the desired temperature and the appliance will heat until this temperature is reached Finally to lau...

Страница 30: ...ou get to main screen PS If pairing has been attempted previously and has not been achieved try the follow ing Press and hold the OFF button for 40 seconds Set the channel on channel A Select On in th...

Страница 31: ...possible range of values is 77 104 F 25 40 C Suggested setting is 95 F 35 C Channel There are three different channels available A Band C These different channels make it possible to have more than o...

Страница 32: ...32 TROUBLESHOOTING...

Страница 33: ...e in the frame so it is very important to support both the glass and the frame when handling Place your thumbs on the outside of the glass frame and wrap your fingers around the frame and onto the gla...

Страница 34: ...Burner and Firebox During the annual inspection and maintenance appointment the service person should clean the burner and firebox To gain access to the firebox and burner follow the instructions begi...

Страница 35: ...Gas Connections Other __________________________ MAINTENANCE LOG Date of Service ____________________ Serviced By ______________________ Service Performed Inspect Venting Clean Burner Firebox Clean C...

Страница 36: ...36...

Страница 37: ...ls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing A B C D E F G H Caution Label all wires prior to disconnection when servicing the controls Wiring er...

Страница 38: ...ow that describes the details of the installation Having this writ ten record of installation information available will greatly expedite trouble shooting should any problem arise with your stove The...

Страница 39: ...39 4 Technology Drive Suite 5 West Lebanon NH 03784 Telephone 603 298 5169 Fax 603 298 9246 Sales hearthinnovations com...

Страница 40: ...40 V1 01 2013 Manufactured by Progressive Manufacturing Inc 4 Technology Drive Suite 5 West Lebanon NH 03784 USA www hearthinnovations com...