sunlight  and  therefore  boost  current  and 
power.  In  addition,  colder  temperatures  can 
substantially increase voltage and power.   

Solartec  modules  are  constructed  with 

tempered glass, but still must be handled with 
care.  If  the  front  glass  is  broken  or  if  the 
polymer  backskin  is  torn,  contact  with  any 
module  surface  or  the  frame  can  produce 
electrical shock, particularly when the module 
is  wet.  Broken  or  damaged  modules  must  be 
disposed of properly.   

Refer  to  Section  690-8  of  the  National 

Electric  Code  for  an  additional  multiplying 
factor of 1.25 which may be applicable. 

The  modules  have  been  evaluated  by  UL 

for  a  maximum  positive  or  negative  design 
loading of 30 lbs/ft2. 

 

Installation Condition 

Installation  shall  be  in  accordance  with 

CSA  C22.1,  Safety  Standard  for  Electrical 
Installations, Canadian Electrical Code, Part 1.

 

 

Sit Selection 
 

PV modules should be installed in a location 

where there is no shading throughout the year. 
In  the  northern  hemisphere,  PV  modules 
should  typically  face  south,  and  in  the 
southern  hemisphere,  PV  modules  should 
typically  face  north.  Please  make  sure  that 
there  are  no  obstructions  in  the  surroundings 
of  the  site  of  installation.  Artificially 
concentrated sunlight shall not be directed on 
the  module.  Take  proper  steps  in  order  to 
maintain  reliability  and  safety  in  case  the  PV 
modules are installed in areas that have heavy 
snow  /  extreme  cold  /  strong  winds  / 
installations  over,  or  near,  water  and  areas 
where  installations  are  prone  to  salt  water 
exposure  or  on  small  islands  or  in  desert 
areas.. 

 

 

Operating Conditions   
 

A.

 

Modules  are  intended  for  use  in 
terrestrial  applications  only—no  outer 
space use.   

B.

 

Modules  must  not  be  installed  nor 
operated  in  areas  where,  salt,  hail, 
snow,  sand,  dust,  air  pollution, 
chemically active vapors, acid rain, soot, 
etc., are excessive.   

C.

 

The recommended standoff height is 20 
cm.   If  other  mounting  means  are 
employed this may affect the UL Listing. 

D.

 

The  ambient  temperature  should  be 
within –20°C (-4°F) to 46°C (115°F). The 
temperature  limits  are  defined  as  the 
monthly  average  high  and  low  of  the 
installation site.   

E.

 

The  wind  pressure  load  of  the 
installation  site  should  be  less  than 
2,880N/m

(60PSF).   

 

Mechanical Installation 

Modules may be mounted at any angle from 

a  vertical  orientation  to  a  horizontal  one.  The 
appropriate  fixed  tilt  angle  and  azimuth 
orientation  should  be  used  in  order  to 
maximize  the  exposure  to  sunlight.  They  may 
be  mounted  in  either  orientation,  in 
“landscape” or “portrait.”   

There  are  several  approved  ways  to  mount 

these Solartec Modules to a support structure. 
They  may  be  mounted  either  using  the  bolt 
holes  provided  or  using  frame  clamps  (not 
provided).  For  roof  mounting  applications  the 
assembly is to be mounted over a fire resistant 
roof covering rated for the application 

 

 

Mounting Using Frame Bolt Holes

 

      The modules may be fastener to a support 
using the bolt holes in the bottom of the frame, 