Solaronics SSTG Скачать руководство пользователя страница 10

10

ROOF VENTING CAP USED FOR INLET AIR MUST BE 

6 IN. (15 CM) HIGHER THAN SHOW DEPTH.

COMBUSTION AIR SUPPLY PIPING

4 IN. (10 CM) I.D. (BY OTHERS)

SUPPORT AS NEEDED

ROOF VENTING

CAP 4 IN. 

(10 CM) I.D.

INLET AIR 

SLEEVE 

ACCESSORY

(SEAM TO BE 

AT TOP)

COMBUSTION AIR SUPPLY 
PIPING 4 IN. (10 CM) I.D.
(BY OTHERS) SUPPORT

AS NECESSARY

FLEX DUCT ACCESSORY

4 IN. (10 CM) I.D. 

18 IN. (46 CM) LONG

INLET AIR WALL CAP

ACCESSORY REQUIRES

4" B-VENT ADAPTOR

(BY OTHERS)

INLET AIR SLEEVE ACCESSORY
(SEAM TO BE AT TOP)

INLET AIR 

COLLAR

TWO HOSE CLAMPS

COMBUSTION AIR SUPPLY

GENERAL NOTES

MAXIMUM LENGTH OF AIR SUPPLY PIPE

 

Uncontaminated atmospheric air for
combustion may come from either outdoors or
indoors (from within the building).

 

Installation of combustion air supply must
comply with the instructions, drawings, and
installation notes provided in this section.

OUTDOOR AIR SUPPLY

40 to 125 MBTUH (12 – 37 kW)           

35

 linear ft. (10.7 m)*

130 to 200 MBTUH (38 – 59 kW)         

40

 linear ft. (12.2 m)*

*Each 90 degree elbow inserted in the venting system

is equivalent to 10 linear ft. (3.0 m).

*Each 45 degree elbow inserted in the venting system

is equivalent to 5 linear ft. (1.5 m).

A maximum of 

two

 90 degree elbows or their equivalent are allowed (e.g. one 90

degree elbow plus two 45 degree elbows; or four 45 degree elbows, etc.)

OUTDOOR AIR SUPPLY THRU-THE-ROOF

OUTDOOR AIR SUPPLY THRU-THE-WALL

 

Uncontaminated atmospheric air for
combustion may come from either outdoors or
indoors (from within the building).

 

Installation of combustion air supply must
comply with the instructions, drawings, and
installation notes provided in this section.

 

In buildings contaminated with excessive dust
or dirt, or containing substances which when
combined with flame and exhaust products
result in corrosive gasses or those under a
negative pressure, or high humidity areas,
combustion air must come from outdoors.

 

Outdoor air supply may be accomplished by
bringing in air through piping from either the
roof or wall as the drawings illustrate.

 

When combustion air is supplied from outdoors,
the heater must also be vented to the outdoors
(

EXCEPT

 high humidity environments consult

factory).

 

The roof venting cap used for inlet air cap
(roof), inlet air wall cap or inlet air box (wall)
must be located at least three (3) feet (.91 m)
away from any vent termination and in a
manner to prevent blockage by snow.

 

Components supplied by others must be
identical to those specified in this manual and
be Metalbestos brand, or equal, for the roof
vent cap; and Simpson Dura-Vent, or equal, for
the wall vent cap.  

NO SUBSTITUTIONS

.

 

Single wall 4” (10.2 cm) I.D., 26-gauge (.044
cm) minimum stainless or galvanized sheet
metal pipe or schedule 40 PVC is
recommended for combustion air supply piping.

 

It may be desirable to insulate piping with 1
inch (2.54 cm) of pipe insulation to eliminate
condensation from warm inside air.

 

DO NOT use collapsible material for
combustion air supply, as it will restrict the
proper amount of combustion air from being
supplied to the burner.

 

An optional blower enclosure extends the
burner housing to enclose the blower.  The
outdoor air piping is then attached to the
enclosure, isolating the outside of the blower
and motor from contaminants.

INDOOR AIR SUPPLY

 

When combustion air is to be taken from inside
a tightly closed building, an opening to the
outdoors must be installed to supply the burner
with sufficient air for combustion.

 

For every 4,000 BTUH (1.17 kW) input of the
total input of 

ALL

 gas-fired equipment, one (1)

square inch (6.45 cm

2

) or more of free area

opening must be provided.

 

The openings should be located above the
heaters to reduce the effect of drafts.

 

Do not draw combustion air into the heater from
attic space or another tightly closed room.
There is no guarantee adequate air will be
supplied

Содержание SSTG

Страница 1: ...damage personal injury and or death A gas fired appliance could expose you to substances in fuel or from fuel combustion which have been determined by the State of California to cause cancer birth de...

Страница 2: ...ached This will cause damage to the controls within the burner requiring them to be replaced If heater is being operated in an atmosphere with a negative pressure or an atmosphere containing contamina...

Страница 3: ...gth of air supply pipe air supply cap specifications and indoor air supply 10 EXHAUST VENTING outdoor exhaust venting maximum length of exhaust vent pipe vent cap specifications and unvented indoor ve...

Страница 4: ...installation must meet the requirements of the Occupational Safety and Health Act OSHA which requires OSHA approved service and safety access to the systems after they are installed AIRCRAFT HANGARS...

Страница 5: ...Burning Equipment CAN CSA C22 2 No 3 Vent terminal clearances shall be in accordance with the current Canadian Natural Gas and Propane Installation Code CAN CSA B149 1 A horizontal vent shall not term...

Страница 6: ...ch may be damaged by temperatures 90 F above 50 C above ambient room temperature These clearances to combustibles are specified on each heater s serial plate In locations used for the storage of combu...

Страница 7: ...9 8 2 4 1 0 3 13 5 4 1 11 5 3 5 6 1 8 1 0 3 90 27 4 90 95 26 28 12 0 3 7 10 0 3 0 8 2 4 1 0 3 14 0 4 3 12 0 3 7 6 1 8 1 0 3 95 29 0 100 105 29 31 12 5 3 8 10 5 3 2 8 2 4 1 0 3 14 5 4 4 12 5 3 8 6 1 8...

Страница 8: ...EAR FT 10 7 M FOR 40 TO 125 MBTUH 12 37 KW OR 40 LINEAR FT 12 2 M FOR 130 TO 200 MBTUH 38 59KW NO MORE THAN TWO 90 ELBOWS MAY BE USED A 90 ELBOW IS EQUIVALENT TO 10 LINEAR FT 3 0 M INLET AIR SLEEVE SE...

Страница 9: ...NGTH OF PIPING FOR ALL INDOOR JOINTS USE RTV SEALANT TO PREVENT HOT FLUE GAS LEAKAGE INTO THE BUILDING USE A SHEET METAL PIPE AND CRIMPER FOR JOINING IDENTICAL SIZE SHEET METAL PIPES USE THREE 3 6 SHE...

Страница 10: ...igh humidity areas combustion air must come from outdoors Outdoor air supply may be accomplished by bringing in air through piping from either the roof or wall as the drawings illustrate When combusti...

Страница 11: ...s limited to appliances with neutral or negative pressures Local authorities may waive this provision since the heaters are approved for indoor venting with proper exhaust and leakage due to condensat...

Страница 12: ...ired correctly Electrical power takeoff must be connected to a separately fused circuit with a disconnect and must be properly polarized and grounded to the heaters power cord Do not run wiring over t...

Страница 13: ...s valve steps up to its operating position DC electrical current flows from sensing electrode through flame to ground IDC senses flame presence turns OFF spark gas continues flowing through valve Vali...

Страница 14: ...15 2 m 2 1 in 53 mm 25 30 ft 7 6 9 1 m 1 5 in 38 mm 55 60 ft 16 8 18 3 m 2 4 in 61 mm 35 40 ft 10 7 12 2 m 1 8 in 46 mm 65 70 ft 19 9 21 3 2 7 in 67 mm When inlet gas pressure is greater than 14 in WC...

Страница 15: ...nd the manifold gas pressure For proper sequence of operation see the OPERATION AND SHUTDOWN section If heater does not operate normally see the TROUBLESHOOTING section Once startup testing is complet...

Страница 16: ...speed Remove the cover by removing the 4 sheet metal screws on top of the cover Remove the ignitor by removing ONLY the end where the vinyl tubing is attached to the ignitor bracket the fitting to wh...

Страница 17: ...serial plate Gas inlet piping not sized correctly 4 Replace inlet gas piping with correct size pipe 5 Gas inlet pressure not correct See serial plate Gas supply regulator not set correctly 5 Adjust g...

Страница 18: ...sembly with snubber and fittings 14 Strain relief bushing 4 Burner core 15 System validation light 5 Ignitor gasket 16 Ignition detection control IDC 6 Ignitor 17 Burner tube holding bracket with scre...

Страница 19: ...ING DOCK AIRPLANE HANGAR DOORS OR OTHER WINDY AREAS FASTEN THE REFLECTORS TO THE REFLECTOR SUPPORT BRACKETS WITH TEK SCREWS OR OTHER POSITIVE MEANS BRACKET TEK SCREW REFLECTOR BRACKET REFLECTOR BURNER...

Страница 20: ...with its radiant tubes horizontal or with the heat exchanger angled above the combustion chamber as illustrated by the drawing below When radiant tubes are horizontal reflectors may be individually r...

Страница 21: ...m Each system can use a maximum of two 2 16 gauge 17 cm stainless steel or aluminized steel 90 elbows OR one 1 16 gauge 17 cm stainless steel or aluminized steel 180 U bend Elbows and U bends can not...

Страница 22: ...22 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 23: ...H5 130 150 38 44 45 13 7 C N L 4 C2 H2 H2 H6 H5 100 29 50 15 2 B N L 4 C2 C3 H2 H2 H2 H5 105 120 31 35 50 15 2 B N L 4 C2 H2 H2 H6 H5 125 37 50 15 2 B N only 4 C2 H2 H2 H6 H5 125 37 50 15 2 C L only 4...

Страница 24: ...ed on tube EXHAUST END stenciled on tube white tape at exhaust end 2 two stainless steel 304 tube clamps 10 ft 3m stainless steel 304 reflector 2 stainless steel 304 reflector brackets 10 ft 3m 16 ga...

Страница 25: ...d 9 1 10 7 m MC 10 ft 3m 16 ga 1 7mm 304L stainless steel tube painted black Stainless steel 304 tube clamp 10 ft 3m stainless steel 304 reflector 2 stainless steel 304 reflector brackets 10 ft 3m 16...

Страница 26: ...he S hook into the loop in the sliding hanger at the top of the tube clamp crimping it closed and then inserting the other end of the S hook into the last chain link and crimping it closed NOTE Make s...

Страница 27: ...edge of the reflector under the reflector bracket tab Be certain the spring steel clamp is in place to hold the reflector securely as shown If the reflectors are to be at an angle loosen the two 2 nu...

Страница 28: ..._____ THIRD Contact the Nearest Distributor Name _________________________________________________________ Address _______________________________________________________ _____________________________...

Отзывы: