7/19/1999 

 
 
IF NO VOLTAGE IS SEEN AT TERMINALS 6 LD- AND 7 LD, THEN:

 

 
 
1  Make sure the switch is turned on. (In the up position)  
 
2. Check to see if the water level is above the top electrode when the low water 
cut-off circuit is being used, or below the bottom electrode when the high water 
cut-off circuit is being used. (To bypass all remote switching circuits, 
disconnect wires from terminals 3 and 4 and turn switch #5 and #6 off).  
 
3. Check the controller for proper adjustment. If the voltage setting on the 
controller is higher than the incoming voltage, the controller will not turn on. 
(See controller adjustment section.)  
 
4. Check to see if the float switch, if used, is functioning properly. 
(Disconnect wires from terminals 3 & 4 to bypass float circuit.)  
 
5. Make sure the yellow light is not on. (Over-current turn-off)  
 
EXCESSIVE CURRENT DRAW (More than the rating of the pump but less than the 
rating of the controller).  
 

1. Check wiring diagrams for proper connections.  
 
2. Check for skinned wires or faulty underwater splice. (See section 2.3d in 
your pump manual.)  
 
3. Check for a locked motor armature. (With the pump out of the well, bypass the 
controller and connect power directly to the motor leads. If the pump still does 
not run and the current is over 1.5 amps, the pump is in a locked rotor 
condition and must be repaired.)  

Содержание PCA 8-60B

Страница 1: ...PCA 8 60B SDS SUBMERISIBLE PUMP CONTROLLER USER S MANUAL...

Страница 2: ...you how to make the connections for your particular system configuration Additional options are also explained and the wiring diagrams are given PCA 8 60B SPECIFICATIONS Input Voltage 24 80V Open Circ...

Страница 3: ...DIP SWITCH 6 ON Low water cut off 1 LO LOW WATER LEVEL SENSOR turns the pump off Mount an E 1s electrode 2 above the ground sensor 2 HI HIGH WATER LEVEL SENSOR turns the pump on Mount an E 1s brass el...

Страница 4: ...oints available on this controller are as follows Switch No Used For Voltage Set Point 1 30 Volt Panel Direct 26 0 2 45 Volt Panel Direct 41 O 3 60 Volt Panel Direct 54 0 4 For Factory Use Only 5 Remo...

Страница 5: ...cross terminals 5 PV and 6 LD this will bypass the controller and will allow the pump to run panel direct Note You must have full or almost full sun for this test to be valid 3 Make sure the proper vo...

Страница 6: ...controller will not turn on See controller adjustment section 4 Check to see if the float switch if used is functioning properly Disconnect wires from terminals 3 4 to bypass float circuit 5 Make sure...

Страница 7: ...7 19 1999 7...

Страница 8: ...S POS SOLAR MODULE PRESET VOLTAGE SETTINGS 1 ON FOR 2 MODULES WIRED IN SERIES 30 VOLTS 2 ON FOR 3 MODULES WIRED IN SERIES 45 VOLTS 3 ON FOR 4 MODULES WIRED IN SERIES 60 VOLTS 4 FOR FACTORY USE ONLY RE...

Страница 9: ...7 19 1999 9 WELL ELECTRODE INSTALLATION...

Страница 10: ...7 19 1999 10...

Страница 11: ...7 19 1999 11...

Страница 12: ...7 19 1999 12...

Страница 13: ...r of the product voids all warranty Warranty limitations There are no express warranties except as listed above SOLARJACK shall have no responsibility for damage to property persons animals or other l...

Отзывы: