Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on a
single Point of Common Connection. The default settings are in compliance with IEEE1547. Utility authorization is required
to change these set-points.
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
V < 50%
0.16
50 % < V < 88%
2.00
110% < V < 120
1.00
V > 120 %
0.16
Frequency Range (Hz)
Max. Clearing Time (Sec)
> 60.5
0.16
< 59.3 (Hawaii – 57)
0.16