Three Phase Inverters
Three Phase Inverters for the
Medium Voltage Grid
SE50K
1
SE55K
SE82.8K
SE66.6K
2
SE100K
2
Unit
Additional Features
Supported
communication
interfaces
RS485, Ethernet,Cellular GSM (optional)
RS485 Surge Protection
Built-in
DC Safety Unit
DS Disconnect
1000V / 2 x 40A
1000V /3 x 40A
1000V / 2 x 40A
1000V /3 x 40A
DC Surge Protection
Optional, Type II field replaceable
DC Fuses on Plus &
Minus
Optional, 30A
Standard Compliance
Safety
IEC-62109, AS3100
Grid connection
standards
3
VDE -AR-N-4105, G59/3, AS-4777,EN50438, CE-1, VDE 0126-1-1, CEI-016,BDEW
Emissions
IEC61000-6-2, IEC61000-6-3, IEC61000-3-11, IEC61000-3-12,
FCC part15 class B
RoHS
Yes
Installation Specifications
Number of units
2
3
2
3
mm
AC Output Cable
Cable range AC - diameter 20-38; Cable range PE - diameter 10-16
mm
1
Available
in
the
UK
and
Israel
only
2
The
SE66.6K
and
SE100K
models
require
a
medium
voltage
transformer
3For
all
standards
refer
to
the
Certifications
category
in
http://www.solaredge.com/groups/support/downloads
Three Phase Inverter with synergy technology
-
Technical
Specifications
4
Three Phase Inverter with synergy technology
MAN-01-00457-1.0