32
L20, L30
Table 10 Batteries Quantity
Model
Rating SolarEdge P/N
Description
L20
20 kVA L20-IB60, L20-IB00
UPS 30kVA, IEC standard, pf 1.0, 3-level
inverter, ±120V, L20-IB60: Build-in 60x9Ah,
L20-IB00: Long run for external batteries.
L30
30 kVA L30-IB60, L30-IB00
UPS 30kVA, IEC standard, pf 1.0, 3-level
inverter, ±120V, L20-IB60: Build-in 60x9Ah,
L20-IB00: Long run for external batteries.
5.10.5.
External battery connections for long-run units
L20: totally 20pcs (optional 16/18/22/24/26) in series. A neutral cable is retrieved from the
joint between the cathode of the 8th (9th/10th/11th/12th/13th), and the anode of the 9th
(10th/11th/12th/13th/14th) of the batteries.
L30: totally 30pcs (optional 32/34/36/38/40/42/44/46/48/50) in series. A neutral cable is
retrieved from the joint between the cathode of the 15th
(16th/17th/18th/19th/20th/21st/22nd/23rd/24th/25th), and the anode of the 16th
(17th/18th/19th/20th/21st/22nd/23rd/24th/25th/26th) of the batteries.
Then the neutral cable, the battery Positive and the battery Negative are connected with the
UPS, respectively. The battery sets between the Battery anode and the neutral are called
positive batteries and that between neutral and cathode are called negative ones. The user
can choose the capacity and the numbers of the batteries according to their desire.
External battery connections for long-run units.
Содержание L20-IB60, L20-IB00
Страница 2: ......
Страница 17: ...9 L20 L30 Figure 5 Install covers...
Страница 27: ...19 L20 L30 5 5 Cabinet view Figure 15 Front view Side view of L20 and L30...
Страница 31: ...23 L20 L30 5 7 Electrical Diagrams Figure 19 Remote EPO NO and NC port...
Страница 32: ...24 L20 L30 Figure 20 External maintenance bypass auxiliary contacts...