background image

 

 

 

2

 

MAN-01-00028-1.1 

 

Configuring the SolarEdge device using the user buttons: 

1

 

Verify that the SolarEdge device’s ON/OFF switch is OFF.  

2

 

Press the LCD Light button once to turn ON the backlight. 

3

 

WARNING! 

If the SolarEdge device worked properly before this action, the adjacent message is 

displayed. 

This message is displayed until the DC is below the safety voltage threshold. The 

default safety voltage is 50 V. Do not open the cover or open DC connectors until 

the voltage is indicated as safe or until at least five minutes have passed. 

Short press the LCD button to scroll through the informative screens to show the ID status window and verify the CPU 
firmware version. Verify if it is below or above version 2.250. 

I D    :    #  #  #  #  #  #  #  #    #  #         
D S  P  1  /  2  :  1  .  0  2  1  0  /  1  .  0  0  3 4 

C P  U  :  0  0  0  2  .  0  2  5  0   

           

C o  u  n  t  r  y  :  U  S  A                   

The following configuration procedures are performed with the SolarEdge device cover open. 

 

 

WARNING! 

Refer to the SolarEdge device manual for instructions about how to open the SolarEdge device cover.  

Four buttons for controlling the LCD panel menus are then accessible, as shown below: 

 

Esc:

 Goes to the beginning of the currently entered 

parameter or to the previous menu. 

 

Up (1):

 Goes up one option in a menu. 

 

Down (2): 

Goes down one option in a menu. 

 

Enter (3):

 Confirms the entry or selection of a parameter. 

 

 

 

 

Figure 4: LCD Panel Menu Buttons 

5

  Press the 

Enter

 button for at least five seconds. The following message is displayed:  

      P  l  e  a  s  e    e  n  t  e  r           
      P  a  s  s  w  o  r  d                   
          *  *  *  *  *  *  *  *               
                                       

The SolarEdge device is now in Setup mode and all its LEDs are lit. The SolarEdge device automatically exits Setup mode 
if no buttons are pressed for more than two minutes. 

6

  Use the three right-most buttons inside the SolarEdge device (the 

UP-1

Down-2

 and 

Enter-3

 buttons), shown above, to 

type in the following default password: 

12312312

 

7

  Scroll down to the 

Communication

 submenu and select it. 

For firmware versions above 2.250, continue to step 

14

. For earlier versions, complete steps 

8

 through 

13

 below. 

Select the 

Server

 submenu, scroll down to the 

RS232

 option and select it. The SolarEdge device performs a reset 

immediately after the selection is made. 

9

  Repeat steps 

5

 through 

7

 

to enter Setup mode. 

 

Enter (3) 

Esc 

Up (1) 

Down (2) 

Содержание GenPro 20e SQB

Страница 1: ...the AC power off and wait five minutes 5 Open the SolarEdge device cover as instructed in the device manual 6 Open gland 1 located on the bottom of the SolarEdge device as shown in Figure 2 Figure 2 shows the SMI as an example The procedure is similar for the inverter Figure 2 Cable Gland Location on SMI The smallest hole is for RS232 cable insertion The SolarEdge device glands come presealed from...

Страница 2: ...ce cover Four buttons for controlling the LCD panel menus are then accessible as shown below Esc Goes to the beginning of the currently entered parameter or to the previous menu Up 1 Goes up one option in a menu Down 2 Goes down one option in a menu Enter 3 Confirms the entry or selection of a parameter Figure 4 LCD Panel Menu Buttons 5 Press the Enter button for at least five seconds The followin...

Страница 3: ... Conf submenu select Set Password and then enter the password if required by the GSM service provider Press the Enter button for a long press to apply or press the ESC button for a long press to abort Verifying the Connection To verify the connection 1 Wait for the SolarEdge device to connect to the SolarEdge Monitoring Server This may take up to two minutes 2 Verify that the LCD panel displays a ...

Страница 4: ...the remaining steps in this procedure Figure 6 RS485 Termination Switch 2 Verify that the SolarEdge device s ON OFF switch is OFF 3 Press the LCD Light button once to turn ON the backlight WARNING If the SolarEdge device worked properly before this action the adjacent message is displayed This message is displayed until the DC is safe The default safety voltage is 50 V Do not open the cover or ope...

Страница 5: ...SolarEdge RS485 X Submenu D e v i c e T y p e S E P r o t o c o l M D e v i c e I D 1 S l a v e D e t e c t 15 Select the Protocol submenu and set it to Slave 16 Press the ESC button repeatedly to exit the Setup menu or wait for the device to automatically exit Setup mode if no buttons are pressed for more than two minutes This concludes the slave device configuration using the LCD button for firm...

Страница 6: ... Yes A Detecting Slaves message is shown during the detection process The master should report the correct number of slaves on the LCD screen If it does not verify the connections and terminations 11 Press the ESC button repeatedly to exit the Setup menu This concludes the multi SolarEdge device setup using the user buttons Support and Contact Information If you have technical questions concerning...

Отзывы: