UPS for 400 Vac Grid, User Guide, doc. rev. 4
54
Figure 35: Auto correction
Auto Correction is enabled by default. This is the recommended setting for most
situations.
After performing any calibrations or adjustments the Auto Correction feature should
be re-enabled, for optimal system performance.
8.2.2.11.
Power walk-in
At system startup, this parameter give you control of the time it takes to bring the system’s DC
voltage up to its nominal level. The UPS gently raises the DC voltage, suppressing inrush current
that would otherwise be experienced by the power input source.