M a l f u n c t i o n s / t r o u b l e s h o o t i n g
Please refer to the control unit manual for troubleshooting malfunctions shown on the control
unit display.
Fault
Possible cause
Troubleshooting
Pump noise
Air in the system
Bleed
Insufficient tapping quantity Insufficient water pressure
Check pressure, increase if
necessary
Calcification in heat
exchanger
Decalcify/replace
Insufficient tapping
temperature
Incorrect adjustment on the
control unit
Check settings
Excessive pressure loss in
the piping on the heating
side
Check the piping, change if
necessary
Drinking water does not
heat up
Control unit not in operation.
Check control unit
Air in the system.
Bleed
HW flow sensor not
connected correctly, or
defective.
Check, replace if applicable
Heating flow temperature
sensor not connected
correctly or faulty.
Check, replace if applicable
Pump faulty
Check, replace if applicable
Volume flow sensor faulty or
incorrect type (VFS instead
of VFD or vice versa)
Check and replace if
applicable