Installation Requirements for the Commonwealth of Massachusetts

In the Commonwealth of Massachusetts, the installer or service agent shall be a plumber or gas fitter licensed by the
Commonwealth.

When installed in the Commonwealth of Massachusetts or where applicable codes; the unit shall be installed with a CO detector
per the requirements listed below.

1

.

For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the
vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:

A If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm shall be placed in the

living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).

B. A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall:

a. Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the appliance and

the carbon monoxide detector;

b. Have battery back-up power;

c. Meet ANSI./UL 2034 Standards and comply with NFPA 720 (2005 Edition); and

d. Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR.

C. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict

compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the
completion of the installation.

D. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The

plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.

2.

For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air
intake is installed above four feet above grade the following requirements must be satisfied:

A If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm shall be placed in the

living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).

B. A carbon monoxide detector shall:

a. Be located in the room that houses the appliance or equipment;

b. Be either hard-wired or battery powered or both; and

c. Shall comply with NFPA 720 (2005 Edition).

C. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict

compliance with the manufacturer instructions. A copy of the installation instructions shall remain with the appliance or equipment at the com-
pletion of the installation.

Содержание Zero Clearance MQZDV3318

Страница 1: ...vice or maintenance can cause property damage personal injury or loss of life Refer to this manual Installation and service must be performed by a qualified installer service agency or the gas supplie...

Страница 2: ...wn between each Be aware during log and firebox paint curing that a white deposit may be developing on the inside of the glass doors It is important to remove this white deposit from the glass doors w...

Страница 3: ...es Specifications 16 Dimensions Installation of Wall Mount Surrounds 17 Fan Installation 18 Brick Installation 19 Porcelain Panel Installation Guide 20 General Glass Information 21 Gas Line Installati...

Страница 4: ...LED IN MANUFACTURED MOBILE HOMES Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrical Code in Canada An appliance must be grounded...

Страница 5: ...iately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water 12 WARNING Do not operate appliance with t...

Страница 6: ...terminal must be used and if applicable a Product approved air intake must be used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructi...

Страница 7: ...d installation with a top vent is possible as long as the hori zontal portion of the vent system does not exceed 20 feet 6 1 m A Flat on a wall D As a room divider B Across the corner E Flat on wall c...

Страница 8: ...ust be raised a minimum of 2 7 8 above the finished floors to accommodate the wall surround The fireplace may be raised higher but the 60 clearance measured from the bottom of the fireplace to the cei...

Страница 9: ...9 Z33CVCK Framing and Facing Requirements MQZDV3318 WITH Z33CVCK CLEAN VIEW CIRCULATING KIT Z33CVCK with Wall Surround...

Страница 10: ...nd installation with a top vent is possible as long as the hori zontal portion of the vent system does not exceed 20 feet 6 1 m A Flat on a wall D As a room divider B Across the corner E Flat on wall...

Страница 11: ...the fireplace must be raised a minimum of 2 1 2 above the finished floors to accommodate the wall surround The fireplace may be raised higher but the 60 clearance measured from the bottom of the firep...

Страница 12: ...12 Z36CVCK Framing and Facing Requirements MQZDV3622 WITH Z36CVCK CLEAN VIEW CIRCULATING KIT Z36CVCK with Wall Surround...

Страница 13: ...hers skip to Step 4 Using screws provided fasten the non combustible header onto the top of CVCK assembly 4 Hang CVCK onto top of fireplace retainer tabs and rotate into position Fig 2 5 Using 4 suppl...

Страница 14: ...MQZDV3318 3622 Mantels Surrounds Warning Combustible objects must not be placed on a non combustible mantel unless the non combustible mantel meets the minimum height and width requirements for a comb...

Страница 15: ...o or over the front face of the fireplace NO PORTION OF GRILL AREA OR DOOR AREAS CAN BE COVERED except where designer clean view kit is used Combustible material can extend flush to unit up to the top...

Страница 16: ...ance For units with CVCK Clear View Circulating Kit see framing with CVCK to establish floor heights MQZDV3622 Clearance to Combustibles Clearance to Combustibles Back from Standoffs 0 inches 0 mm Sid...

Страница 17: ...G 8 3 4 8 3 4 H 1 1 I 1 3 16 1 3 16 1 Set Surround Lip on CVCK Ledge and ensure that it is securely in place 2 Swing the upper portion of the Surround so that the Surround Ledge is resting on top of t...

Страница 18: ...o 120v Install a duplex outlet to junction box and plug fan into outlet 4 Turn the wall switch on clockwise Turn fireplace on Once the sensor in the unit reaches operating temperature approximately 10...

Страница 19: ...firebox When placing Panel tilt panel towards you and lift panel over the burner assembly Fig 2 5 To place side Liner Panels rotate panel towards you and place bottom edge of panel over the front ledg...

Страница 20: ...e panel tilt it towards you while lifting it over the burner assembly 5 To place the side liner panels rotate it towards you while placing the bottom edge over the front ledge of the firebox Then rota...

Страница 21: ...ed fittings Always pro vide a union so that gas line can be easily disconnected for burner or fan servic ing See gas specification for pressure details and ratings 4 When a vertical section of gas pip...

Страница 22: ...oval Instructions 2 Disconnect gas line connection at burner system through access cover opening 3 Remove extension knobs and wiring from face of gas valve 4 Remove screws from perimeter of burner sys...

Страница 23: ...pilot screw to provide proper sized flame Caution Do Not Wire 120 Volt PowerTo Millivolt Switches Or Thermostats Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire...

Страница 24: ...etting Loosen screw on the side of air mixing tube and rotate to the correct opening using a dirll bit or tape measure Tighten screw 7 After converting parts to the new type of gas reverse all step s...

Страница 25: ...amped on the side of the injector near the top LPG injectors have a groove machined around their circumference near the top while NG injectors do not have a groove 5 Refer to the Appliance Manufacture...

Страница 26: ...rminals at wall switch If burner comes on replace Switch ON defective wall switch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connec tions are bad Gen...

Страница 27: ...glowing rock wool on burner as shown in step 1 being sure to leave the multiple porting areas open For Lp only the multiple porting areas can be completely covered Do not cover the Rear Porting areas...

Страница 28: ...ectly over top of the multiple porting area on the left side Step 5 Fill in the rest of the burner pan and ember plates with lava rock and vermiculite Do not place lava rock or vermiculite on any of t...

Страница 29: ...ove the 2 ember plates once the grate bar is removed The 2 screws removed must be re installed once the grate bar is removed Step 3 Using the left ember plate mounting bracket slide the left ember pla...

Страница 30: ...ure that they are crossing over the single line porting MQRSP5 finished setup and burn Step 8 Place rock 3 and rock 1 into position as shown to complete the setup Lava rock and vermiculite are optiona...

Страница 31: ...fami ly dwellings and serves both dwellings 4 Permitted only if veranda porch deck or balcony is fully open on a minimum of two sides beneath the floor 5 Clearance in accordance with local installati...

Страница 32: ...e Venting Kingsman Flex pipe is shipped in unexpanded length When installing pipe expand the lengths Pipe can be expanded to twice their lengths e g 4ft to 8ft Fully expand pipe and cut off excess Do...

Страница 33: ...ght of the system and the number of bends required 2 Having determined the vertical distance determine the maxi mum horizontal section allowed 3 Vent table has been established for 90 horizontal verti...

Страница 34: ...assing through a ceiling or floor If an attic insulation shield is to be used a fire stop is not required Roof Flashing Ensure that you have the proper roof flashing by checking your roof pitch using...

Страница 35: ...IR INTAKE ADJUSTMENT PLATE NOTE Unit comes preset for short horizontal or vertical venting under a 15 feet run Follow these instructions when venting exceeds 15 foot run 1 Locate the 3 x 1 4 hex screw...

Страница 36: ...Surround Slim Line Antique Brass Z33SLCR Surround Slim Line Chrome Z33SLPB Surround Slim Line Polish Brass Z33SLBL Surround Slim Line Gun Metal Black Designer Doors for 33 Fireplaces Operative Z33DDA...

Страница 37: ...AB Surround Slim Line Antique Brass Z36SLCR Surround Slim Line Chrome Z36SLPB Surround Slim Line Polish Brass Z36SLBL Surround Slim Line Gun Metal Black Designer Doors for 36 Fireplaces Operative Z36D...

Страница 38: ...iece Kit Catalog Number Description ZDVHSK Horizontal Vent Starter Kit 3 FT Length Horizontal Vent Termination Wall Thimble 36 Flex Pipe Mill Pac ZDVHSK5 Horizontal Vent Starter Kit 5 FT Length Horizo...

Страница 39: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: