Operator and Maintenance Manual for PRO-Verter RMK LAN
2. Connect RMK to the PRO-Verter: Two RJ11
crossover
wires are included with the RMK: one
connects the “Inverter” ports, and the other connects the “Remote” ports (Figure 2). The red or
black 3’ Cat5 straight-through cable connects the “Ethernet” ports. The power cable plugs into
the “Power” port on the back side of the RMK, and the other end of this wire is connected to the
24 V, 5 A DC terminals on the front left-hand corner of the Faceplate.
Note:
Red to red, black to
black.
RJ11 Crossover Cable
To Inverter Port
RJ11 Crossover Cable
To Remote Port
24VDC Power Port
CAT5 straight-
through cable
connects
ETHERNET
ports
Figure 3. The RMK Ports
NOTICE
The cables connecting the RMK to the PRO-Verter must be bundled together and secured
to the Faceplate to prevent them from slipping between the lid and the body of the PRO-
Verter and causing damage to the cables and/or the PRO-Verter case hinges. If the cables
are not already secure as shown (Figure 4), a zip tie with ring on the end may be used to
bundle the cables, which should then be secured to the Faceplate using one of the nearby
Faceplate screws.
Case Lid
Case Lid
PRO-Verter Faceplate
PRO-Verter Faceplate
RMK
RMK
Figure 4. Correct (left) and incorrect (right) routing and securing of cables