December 2020
|
Solar Stik
®
, Inc.
50
|
Operator and Maintenance Manual for the PRO-Verter S 3000
PRELIMINARY
GROUP 3: INPUT LOW LIMIT
Parameter
Setting Value
Description
Reset Voltage
105.0 V
This is the reset voltage at which the PRO-Verter will revert to Charge mode
after it has switched over to Invert mode due to input voltage falling to Cut
Off Volt 1/Cut Off Volt 2/Cut Off Volt 3.
Cut Off Volt 1
100.0 V
If during Charge mode, the AC input voltage falls below Cut Off Volt 1 for
period > Detect Time 1, the PRO-Verter will transfer to Invert mode from
Charge mode.
Detect Time 1
300 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off Volt
1 is allowed.
Cut Off Volt 2
95.0 V
If during Charge mode the AC input voltage falls below Cut Off Volt 2 for
period > Detect Time 2, the PRO-Verter will transfer to Invert mode.
Detect Time 2
60 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off 2 is
allowed.
Cut Off Volt 3
90.0 V
If during Charge mode, the AC input voltage falls below Cut Off Volt 3 for
period > Detect Time 3, the PRO-Verter will transfer to Invert mode.
Detect Time 3
1 Cycle
This is the time limit in cycles up to which the low AC input voltage Cut Off
3 is allowed.
Input Low Limit Programmable Settings
Table 7. Parameters for Grid/Generator Input Low Voltage Level
GROUP 4: INPUT HIGH LIMIT
Parameter
Setting Value
Description
Reset Voltage
125.0 V
This is the reset voltage at which the PRO-Verter will revert to Charge
mode after it has switched over to Invert mode due to input voltage falling
to Cut Off Volt 1/Cut Off Volt 2/Cut Off Volt 3.
Cut Off Volt 1
135.0 V
If during Charge mode the AC input voltage falls below Cut Off Volt 1 for
period > Detect Time 1, the PRO-Verter will transfer to Invert mode from
Charge mode.
Detect Time 1
60 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off
Volt 1 is allowed.
Cut Off Volt 2
140.0 V
If during Charge mode the AC input voltage falls below Cut Off Volt 2 for
period > Detect Time 2, the PRO-Verter will transfer to Invert mode.
Detect Time 2
15 Cycles
This is the time limit in cycles up to which low AC input voltage Cut Off
Volt 2 is allowed.
Cut Off Volt 3
145.0 V
If during Charge mode the AC input voltage falls below Cut Off Volt 3 for
period > Detect Time 3, the PRO-Verter will transfer to Invert mode.
Detect Time 3
1 Cycle
This is the time limit in cycles up to which the low AC input voltage Cut
Off Volt 3 is allowed.
Input High Limit Programmable Settings
Table 8. Parameters for Grid/Generator Input High Voltage Level