SS202-05 INSTALLATION MANUAL v1.2
Connecting Inverters/chargers/UPS to the battery unit while it is ON can cause big sparks
due to capacitors inside the connected device. This could cause serious injuries.
Use the appropriately sized cable for connected devices.
Based on the rated current of the battery and inverter as well as cable length.
Figure 3 connection Busbar
Step 2
. Connect the negative cable to the negative battery busbar and the positive cable to
the positive battery busbar as shown is figure 3.
All used connection points should be a suitably tightened, ensuring good electrical
connection between the lug and busbar. A bad connection could cause serious damage to
the battery, inverter and connected electrical components.