SAB12-0669_02_Installation and Maintenance Manual SFxxx-S
11
Grounding Image:
Connect to earth ground from where the grounding sign
is indicated.
Grounding (IEC) Grounding with washer (UL)
Use M4 bolt or standard gauge size #6 bolt. Tighten the bolts or screw with an adequate torque value. Please refer to further
instructions provided by the screw or bolt manufacturer.
UL: Recommended tightening torque is 1.5 N-m and 1.0 N-m minimum for M4 and standard size #6 bolt respectively.
7.3 Electrical Wiring
A set of cables with a plastic connector for each polarity is supplied with SF PV modules. Use these to connect
modules.
Do not open the junction box on the back side of the module
Fasten the module cable to the frame or to the mounting system in order to avoid any stress to the connector.
Cables drooping from the terminal box are hazardous and must be avoided.
Cables should be secured so they are not exposed to direct sunlight (such as behind the module).
The sum of Voc of modules in series must not exceed the maximum system voltage rating of the module under any
condition, even at low temperature.
Reverse current applied to the modules should not exceed 7 A under any condition.
Minimum cable diameter: 2.5 mm sq
Carry out installation and wiring work in compliance with all relevant health, safety and environment laws and regulations.
Series connection
Junction
box
Parallel connection
stainless-steel bolt
stainless-steel cupped washer
stainless-steel star washer
stainless-steel nut