Installation instructions
• The heater must only be installed using suitable fastenings (e.g. use M6x60
bolts with steel anchors in a stone or concrete substrate) on a firm, load-bea
-
ring, standard, flame-resistant or non-combustible substrate.
• If heater and socket are not installed on the same surface, it must be ensured
that the field of radiation cannot be directed towards the socket. Failing this,
it must be ensured that the socket cannot heat up to more than 70°C during
heater operation.
• When mounted on a sloping ceiling, IR radiant heaters must be fitted with a
„bottom“ power cord arrangement.
• The safety distances given in Appendixes 1 and 2 must be observed.
• The area in which the heat acts can be estimated from the radiation diagram
(Appendix 3). The diagram shows the sizes of the irradiated areas at various
distances from the radiant heater and in each case the maximum radiation
intensity.
• Installation height: at least 1.80 m above the ground
GB