CONNECTIONS – ELECTRICAL 

 

The  power  supply  to  the  water  heater  must  not  be  switched  on  until  the  water  heater  is  filled  with 
water

 and a satisfactory megger reading is obtained. 

 

MEGGER READING 

When a megger test is conducted on this water heater, then the following should be noted. 
 

 

Warning:

  This  water  heater  contains  electronic  equipment  and  500 V  insulation  tests  must  only  be 

conducted between active and earth and between neutral and earth. An active to neutral test WILL damage 
the electronics. 
 

An insulation test result of between 100 

KΩ and 660 KΩ for this water heater is normal. 

 
Typically  the  insulation  resistance  between  live  and  earthed  parts  of  an  electrical  installation  should  not  be 
less than 1 

MΩ. However AS/NZS 3000:2000 clause 6.3.3.3.2 „Results‟ states: 

 
“The value of 1 MΩ may be reduced to: 

 

0.01 

MΩ for sheathed heating elements or appliances; or 

 

a value permitted in the Standard applicable to electrical equipment.” 

This  model  water  heater  is  categorised  as  a  „stationary  class 1  motor  operated  appliance‟  and  has  been 
tested  to  AS/NZS 3350.1:2002  clause 

16  „Leakage  current  and  electric  strength‟  and  has  passed  the 

requirements  of  this  Standard.  Therefore,  this  model  water  heater  complies  with  the  condition  stated  in 
AS/NZS 3000:2000 clause 6.3.3.3.2 (b). 
 

ELECTRICAL CONNECTION 

All electrical work and permanent wiring must be carried out by a qualified person and in accordance with the 
Wiring Rules AS/NZS 3000 and all local codes and regulatory authority requirements. 
 
The  water  heater  must  be  directly  connected  to  a  240 V AC 50 Hz  mains  power  supply.  The  water  heater 
must be on its own circuit with an isolating switch installed at the switchboard. A secondary isolating switch 
may be installed within reach of the water heater. 
 
The  325 HAV model  water  heater  is  recommended  for  connection  to  a  minimum  16 hour  per  day  power 
supply. 
 
A  flexible  20 mm  conduit  is  required  for  the  electrical  cable  to  the  water  heater.  The  conduit  is  to  be 
connected to the unit with a 20 mm terminator. Connect the power supply wires directly to the terminal block 
and earth tab connection, ensuring there are no excess wire loops inside the front cover. 
 
The  water  heater  will  only  operate  on  a  sine  wave  at  50 Hz.  Devices  generating  a  square  wave  cannot be 
used to supply power to the water heater. 
 

BOOSTER HEATING UNIT AND THERMOSTAT SETTING 

The water  heater has a  booster heating  unit  and thermostat. The booster heating unit  will be automatically 
activated during periods when the ambient air temperature is 

outside the heat pump‟s operating temperature 

range  of  between  a  minimum  of  3°C  to  5°C  and  maximum  of  45°C  to  55°C  and  heating  of  the  water  is 
required. The thermostat is not adjustable. 
 

TIMER 

A  timer  can  be  installed  in  the  electrical  circuit  to  the  water  heater.  The  timer  must  be  weatherproof  if  it  is 
installed outdoors. 
 
It  may  be  desirable  for  the  water  heater  not  to  operate  between  certain  hours,  such  as  during  the  peak 
period  when  connected  to  a  Time  of  Use  electricity  supply  due  to  a  more  expensive  tariff  rate  applying.  A 
timer will affect the operating times of both the heat pump circuit and the booster heating unit. 
 

Note:

  The  325 HAV model  water  heater  is  recommended  for  connection  to  a  minimum  16 hour  per  day 

power supply. 

Содержание 325 HAV

Страница 1: ...lled and serviced by a qualified person Please leave this guide with the householder 325 HAV Electric Boosted HEAT PUMP WATER HEATER OWNER S MANUAL AND WARRANTY INSTALLATION INSTRUCTIONS Solahart Industries Pty Ltd ABN 45 064 945 848 ...

Страница 2: ...a Pty Ltd TRADE MARKS Registered trademark of Solahart Industries Pty Ltd or Rheem Australia Pty Ltd Trademark of Solahart Industries Pty Ltd or Rheem Australia Pty Ltd Note Every care has been taken to ensure accuracy in preparation of this publication No liability can be accepted for any consequences which may arise as a result of its application ...

Страница 3: ...ended for the installer but may be of interest About Your Water Heater 4 Regular Care 10 Water Supplies 12 Save A Service Call 14 Installation 19 Heat Pump And Tank Assembly 26 Connections Plumbing 37 Connections Electrical 39 Commissioning 41 Draining The Water Heater 43 Warranty 45 ...

Страница 4: ...he storage tank This process continues while heating is required until the water in the storage tank reaches a temperature of 60 C Even on cloudy or cold days heat is drawn from the surrounding air The heat pump will operate when the ambient air temperature is between a minimum of 3 C to 5 C and maximum of 45 C to 55 C The booster heating unit will operate when the ambient air temperature is outsi...

Страница 5: ...ot water pipe work to the bathroom and ensuite when this water heater is installed This will keep the water temperature below 50 C at the bathroom and ensuite The risk of scald injury will be reduced and still allow hotter water to the kitchen and laundry TEMPERATURE ADJUSTMENT The thermostats controlling the heat pump and the booster heating unit are factory set and not adjustable WARNING This wa...

Страница 6: ...tion is not in accordance with these instructions OPERATING MODE MONITOR An operating mode monitor is located on the front of the heat pump module and houses a green and a red LED The green LED marked SOLAR BOOST indicates the current operating mode of the heat pump water heater and the red LED marked ATTENTION indicates a fault mode The green LED will emit either a constant glow or a series of fl...

Страница 7: ... in the top of the water heater drops to below 62 C and the thermostat closes circuit reinstating power to the heat pump when the red LED will emit a solid glow for three 3 seconds and then extinguish The green LED will then recommence to glow or flash The green LED will glow standby mode water is hot if the water temperature in the lower part of the water heater is 50 C or more The green LED will...

Страница 8: ... will only operate when power is available at the water heater the water in the storage tank requires heating the heat pump compressor is cool and the ambient air temperature is within the heat pump s operating temperature range of between a minimum of 3 C to 5 C and a maximum of 45 C to 55 C If the ambient temperature is outside of this range the water heater will commence heating with the booste...

Страница 9: ...RS Notice to Victorian Customers from the Victorian Plumbing Industry Commission This water heater must be installed by a licensed person as required by the Victorian Building Act 1993 Only a licensed person will give you a Compliance Certificate showing that the work complies with all the relevant Standards Only a licensed person will have insurance protecting their workmanship for 6 years Make s...

Страница 10: ... included in the Solahart warranty A charge will be made for this work Only genuine replacement parts should be used on this water heater The major service includes Replace the temperature pressure relief valve Inspect and flush the expansion control valve if fitted If required replace the valve Inspect and if required replace the anode If the anode is not replaced it should be replaced within thr...

Страница 11: ...ge when operating the valve s lever If water does not flow freely from the drain line when the lever is lifted then the water heater must be checked Phone your nearest Solahart Dealer to arrange for an inspection The temperature pressure relief valve should be replaced at intervals not exceeding 5 years or more frequently in areas where there is a high incidence of water deposits refer to Water Su...

Страница 12: ...S content in the water is less than 2500 mg L and when the correct colour coded anode is used If an incorrect colour coded anode is used in the water heater any resultant faults will not be covered by the Solahart warranty In addition the use of an incorrect colour coded anode may shorten the life of the storage tank The correct colour coded anode is as shown in the following table Total Dissolved...

Страница 13: ... In a corrosive water supply the water can attack copper parts and cause them to fail Where the saturation index exceeds 0 40 the water is very scaling and the Solahart warranty does not apply to the water heater Water which is scaling may be treated with a water softening device to reduce the saturation index of the water CHLORIDE AND PH Where the chloride level exceeds 250 mg L the Solahart warr...

Страница 14: ...heating mode using the booster heating unit Refer to Heat Pump Is Not Operating on page 15 Temperature pressure relief valve running Is the relief valve discharging too much water Refer to Temperature Pressure Relief Valve Running on page 17 Water heater size Do you have the correct size water heater for your requirements WATER NOT HOT ENOUGH You may find that due to heavy hot water usage the wate...

Страница 15: ...ower part of the water heater is 50 C or more The green LED will flash if the water temperature in the lower part of the water heater is less than 50 C If at least 45 minutes has elapsed after power is reinstated to the heat pump i e 45 minutes after the red LED emitted a solid glow for three 3 seconds and then extinguished heating of the water by the heat pump will recommence 3 x green flashes if...

Страница 16: ...art of the water heater and the green LED will commence to flash Close the hot tap when the green LED commences to flash The heat pump will commence to operate when the green LED is flashing and at least 45 minutes has elapsed after power is reinstated to the heat pump i e 45 minutes after the red LED flashed the fault mode for thirty 30 seconds and then extinguished If the heat pump stops operati...

Страница 17: ...may indicate the mains water pressure sometimes rises above the designed pressure of the water heater Ask your installing plumber to fit a pressure limiting valve Warning Never replace the relief valve with one of a higher pressure rating Heavy flows of hot water until the water heater is cold then stops until water reheats The water heater must be switched off at the isolating switch or switchboa...

Страница 18: ...t Enough Hot Water on page 14 Is there a leaking hot water pipe dripping hot water tap etc Even a small leak will waste a surprising quantity of hot water and energy Replace faulty tap washers and have your plumber rectify any leaking pipe work Has there been an increase in hot water usage An increase in hot water usage will result in an increase in heat pump operation Has your water heating tarif...

Страница 19: ...n the event that this water heater was to become inoperable for any reason We recommend you provide advice to the system owner about their needs and building backup redundancy into the hot water supply system The 325 HAV model water heater is recommended for connection to a minimum 16 hour per day power supply A Solahart heat pump water heater consumes less energy than an electric water heater The...

Страница 20: ...aced in direct contact with a concrete surface that is less than two months old and not fully cured as this may attack the metal coating of the water heater base A moisture barrier should be used between the two surfaces in this instance The water heater must be installed with a clearance of at least 100 mm from a wall A clearance of at least 300 mm is required perpendicular from both the front ai...

Страница 21: ...eratures are not delivered to a bathroom ensuite or other ablution area The temperature limiting device used with a heat pump water heater should have a specified minimum temperature differential between the hot water inlet and the tempered water outlet of no greater than 10 C Refer to the specifications of the temperature limiting device Where a temperature limiting device is installed adjacent t...

Страница 22: ...lding a temperature limiting device can only be installed on a dead leg branching off the circulated hot water flow and return pipe If circulated tempered water were to be returned back to the water heater depending on the location of the return line connection on the water supply line to the water heater then either water will be supplied to the cold water inlet of the temperature limiting device...

Страница 23: ...e storage tank The black anode is typically fitted as standard refer to Anode on page 12 If an incorrect anode is used there is also the possibility the anode may become overactive and hydrogen gas could accumulate in the top of the water heater during long periods of no use In areas where this is likely to occur the installer should instruct the householder on how to dissipate the gas safely refe...

Страница 24: ...INSTALLATION 24 TYPICAL INSTALLATON OUTDOOR LOCATION TYPICAL INSTALLATION HEAT PUMP WATER HEATER 325HAV ...

Страница 25: ...del number T325 HAV Maximum rated power input 3600 watts Storage capacity litres 325 Rated heat pump power input 800 watts Boost capacity 1 8 kW litres 100 Booster heating unit rating 1800 2400 3600 watts 2 4 kW 3 6 kW litres 180 Refrigerant type R134a Weight tank empty kg 88 Refrigerant circuit pressure 3000 kPa Weight heat pump kg 42 Weight heat pump module 42 kg Weight system empty kg 130 Weigh...

Страница 26: ...ckaging Good lifting practice should be followed There are two flexible hoses provided inside the heat pump module The flexible hoses are to be withdrawn from the module and fixed to the two water fittings on the heat pump storage tank during the assembly procedure There are two connection points located on the underside of the control box in the heat pump module to which the power cable and tank ...

Страница 27: ...allation Heat Pump Module Integrated 126573 Installation instructions heat pump module integrated 1 052158 Saddle clamp 20 mm Clipsal 261 20 1 080021 Screw phillips pan head No 8 x 13 zinc plated black 2 080156 Screw pack of 3 M6 x 12 HD bolts 2 080203 Stud M6 x 25 zinc plate 3 080204 Nut hex whizzlock M6 3 104767 Cover fan shroud 1 080191 Screw hilo 13 16 x 20 pan head combination zinc plated 1 1...

Страница 28: ... perpendicular from both the front air inlet louvres and the outlet grille to any wall or obstruction 638 574 300 MIN 300 MIN 32 613 894 281 AIR OUTLET AIR INLET VENTILATION CLEARANCE CONDENSATE DRAIN AIR INLET TPR VALVE 1631 1317 119 162 544 872 1018 ELECTRICAL CONNECTION AIR OUTLET AIR INLET 300 M IN COLD INLET HOT OUTLET VENTILATION CLEARANCE 100 Step 1 position storage tank at least 100 mm fro...

Страница 29: ...ly wiring to the terminal block and earth connection inside of the lower front cover Secure the conduit to the side of the storage tank with the saddle clamp and screws provided The saddle clamp must be positioned over the pilot holes otherwise the conduit will interfere with the heat pump module installation Refer to Connections Electrical on page 39 Note The power supply to the water heater must...

Страница 30: ...e the hand holes provided in the sides of the packaging Good lifting practice should be followed 9 Protective Film Peel away and completely remove the protective film cover from the heat pump module and its front cover Ensure there are no remnants of the protective film left around or under the module top or hand grips The function of the protective film is to protect the jacket of the heat pump m...

Страница 31: ...he 20 mm screw provided Insert the black plug provided into the recess to cover the head of the screw FAN COVER SHROUD SCREW PLUG REMOVE AND DISCARD EXISTING SCREW Step 10 Steps 11 and 13 fit the fan cover shroud to the heat pump module remove front cover from heat pump module and feed through cables 11 Heat Pump Module Cover Remove the two screws securing the front cover to the heat pump module R...

Страница 32: ... is not required Position the hose such that when the heat pump module is moved and secured to the tank it does not kink Step 15 attach flexible hose with blue collar to inlet 16 Hot Hose Connection Attach the flexible braided hose marked with a red collar from the top of the circulator to the fitting in the top connection on the storage tank and marked OUTLET in red Tighten the swivel nut on the ...

Страница 33: ... required to remove the tab Step 18 remove the tab on the side of the electrical entry to the heat pump module 19 Studs Retrieve the three 3 studs from the kit and screw into the three 3 threaded inserts on the side of the tank closest to the wall These studs will assist in aligning the heat pump module for connection to the storage tank Step 19 screw in studs into threaded inserts ...

Страница 34: ...Nuts Screw the three flange nuts onto the studs to connect the wall side of the heat pump module to the storage tank Steps 20 and 21 align heat pump module over studs and screw on flange nuts 22 Tab Engage the tab at the bottom of the heat pump module on the front side of the module into the slot in the tank 23 Fixing Bolts Screw in the three fixing bolts to connect the front side of the heat pump...

Страница 35: ...e Connection Insert the four pin power cable plug to the connector on the underside of the control box The plug is polarised and can only be inserted one way SK6502 AD A4 5 08 CONTROL BOARD HEAT PUMP 325L WITH SENSOR CABLE POWER CABLE TANK SENSOR CABLE PLUG POWER CABLE PLUG Steps 24 and 25 connect power cable and tank sensor cable 26 Positioning of Water Heater Complete final positioning of the wa...

Страница 36: ...y Turn on the cold water supply and fill the water heater Check the pipe work and the connection points for the flexible braided hoses for leaks Refer to To Fill And Turn On The Water Heater on page 41 however the electrical supply should not be turned on at this stage 29 Heat Pump Module Cover Replace the heat pump module cover and re fit the two screws Step 29 replace heat pump module front cove...

Страница 37: ...heat nearby They will be pushed into the correct position as the fitting is screwed in PIPE SIZES To achieve true mains pressure operation the cold water line to the water heater should be the same size or bigger than the hot water line from the water heater The pipe sizing for hot water supply systems should be carried out by persons competent to do so choosing the most suitable pipe size for eac...

Страница 38: ...e can discharge into a tundish Subject to local regulatory authority approval the drain lines from the temperature pressure relief valve and expansion control valve from an individual water heater may be interconnected The outlet of a drain line must be in such a position that flow out of the pipe can be easily seen but arranged so discharge will not cause injury damage or nuisance The termination...

Страница 39: ...nnected to a 240 V AC 50 Hz mains power supply The water heater must be on its own circuit with an isolating switch installed at the switchboard A secondary isolating switch may be installed within reach of the water heater The 325 HAV model water heater is recommended for connection to a minimum 16 hour per day power supply A flexible 20 mm conduit is required for the electrical cable to the wate...

Страница 40: ...GREEN YELLOW RED BLUE BLACK GREEN YELLOW GREEN YELLOW CONTROL BOARD A E N POWER PLUG FROM TANK T0 THERMISTOR PLUG FROM TANK COMPRESSOR CAPACITOR FAN CAPACITOR TANK THERMISTOR T0 COMPRESSOR THERMISTOR T2 EVAPORATOR THERMISTOR T1 CABLING INSIDE TANK JACKET SK6501 A4 REV AD 5 08 T0 Tank Thermistor T1 Evaporator Thermistor T2 Compressor Thermistor COM NC NO COMP A COMP N FAN N FAN A PUMP N PUMP A NEUT...

Страница 41: ...witch to the booster heating unit if the detected ambient air temperature is outside the operating temperature range of between a minimum of 3 C to 5 C and a maximum of 45 C to 55 C The system will not switch back to heat pump operation from the booster heating unit if the detected ambient air temperature has moved back within the heat pump s operating temperature range The heating cycle will be c...

Страница 42: ...sor over temperature possible circulator fault 2 x red Heating unit off compressor fault condition 3 x red Heating unit on compressor cooling fault condition 4 x red Heating unit on tank thermistor fault condition 5 x red Heating unit on evaporator thermistor fault condition 6 x red Heating unit on compressor thermistor fault condition 9 x red Heating unit on compressor fault condition Notes Power...

Страница 43: ...t code for thirty 30 seconds and then extinguish If the red LED then recommences to flash or recommences to flash after the heat pump next operates a service call may be required Before phoning to arrange a service inspection due to the red LED flashing refer to Heat Pump Is Not Operating on page 15 in the Save A Service Call section of this Owner s Guide DRAINING THE WATER HEATER Warning Exercise...

Страница 44: ...44 This page is intentionally blank ...

Страница 45: ... the water heater is installed in a position that does not allow safe or ready access the cost of that access including the cost of additional materials handling and or safety equipment shall be the owner s responsibility In other words the cost of dismantling or removing cupboards doors or walls and the cost of any special equipment to bring the water heater to floor or ground level or to a servi...

Страница 46: ...ll 1300 769 475 for details 4 ENTITLEMENT TO MAKE A CLAIM UNDER THIS WARRANTY 4 1 To be entitled to make a claim under this warranty you need to a Be the owner of the water heater or have consent of the owner to act on their behalf b Contact Solahart without undue delay after detection of the defect and in any event within the applicable warranty period 4 2 You are not entitled to make a claim und...

Страница 47: ... Installation please circle New Solar to Solar Tank Replacement Other Work Delivery Details System Model No System Type Tank Model No Tank Serial No Collector Model No No of Collectors Collector Serial No s 1 2 3 4 Booster Type please circle Electric continuous Off Peak 1 night Off Peak 2 night day In Tank Gas Booster In Line Booster Solar Preheat only Booster Control please circle None Timer Manu...

Страница 48: ...mail solahart solahart com au Web www solahart com Postal Address PO Box 95 Welshpool WA 6986 Australia International Offices Registered Office 1 Alan Street PO Box 6 Rydalmere New South Wales 2116 Australia www solahart com au Europe Phone International 31 492 579 696 Facsimile International 31 492 579 694 USA Australia Phone International 1 334 260 1586 For SERVICE Telephone 1800 638 011 or your...

Отзывы: