14
Transfer Voltage Selectors (DIP Switches)
The two-position DIP switch control on the rear panel, shown above,
allows the operator to select the mains transfer voltage at which the
UPS will switch to battery power. DIP switch positions for each volt-
age setting are as follows:
DIP switch settings
Left
Right
Nominal Mains
Input Range Setting
↑
Up
↑
Up
230VAC
163 - 282VAC (default)
↑
Up
↓
Down
220VAC
155 - 270VAC
↓
Down
↑
Up
240VAC
171 - 291VAC
↓
Down
↓
Down
230VAC
163 - 282VAC
!
CAUTION
Never change the voltage settings while the UPS is ON and
powering connected loads. Change DIP switches only when
the UPS is OFF.
!
CAUTION
To ensure protection of the connected equipment, the DIP
switch settings should match the nominal mains input
voltage. DIP switch settings not matching the nominal
mains could potentially damage connected equipment.
Rear of UPS
DIP Switches
Содержание S2K
Страница 1: ...S2K UPS USER MANUAL Line Interactive 350 1000 VA 230V...
Страница 2: ......
Страница 30: ...26...
Страница 31: ......