10
I
NSTALLATION
This UPS is designed for data processing equipment. Maximum load
must not exceed that shown on the UPS rating label. Do not connect
equipment that could overload the UPS or draw half-wave current
from the UPS, for example: electric drills, vacuum cleaners, laser
printers or hair dryers. Your total load earth leakage current must not
exceed 3.5 mA. Most data processing equipment meets this require-
ment if you use no more than two pieces of equipment. If uncertain
about your load, consult your local distributor, Sola/Hevi-Duty repre-
sentative, or Sola/Hevi-Duty Technical Services.
1. Visually inspect the UPS for freight damage. Report damage to the
carrier and your local distributor, Sola/Hevi-Duty representative, or
Sola/Hevi-Duty Technical Services.
2. Decide where to place the S2K unit. Find a location that is near an
easily accessible mains outlet. Install the UPS indoors in a con-
trolled environment, where it cannot be accidentally turned off.
Place it in an area of unrestricted airflow around the unit, away
from water, flammable liquids, gases, corrosives, and conductive
contaminants. Maintain a minimum clearance of 100mm (4 inches)
on each side of the UPS. Maintain an ambient temperature range of
0°C to 40°C (32°F to 104°F).
3. The Sola S2K 230 VAC models are not supplied with an input power
lead for connection to the mains supply. Additional input/output
leads can be obtained from your dealer. The input power cord must
have a minimal cross-sectional area of 1mm
2
.
NOTE
UPS operation in temperatures above 25°C (77°F) reduces
battery life.
Plug this type of equipment into black
receptacles ONLY
Plug computers, monitors & network hubs
into orange receptacles
Inkjet
printer
Scanner
Fax
machine
Содержание S2K
Страница 1: ...S2K UPS USER MANUAL Line Interactive 350 1000 VA 230V...
Страница 2: ......
Страница 30: ...26...
Страница 31: ......