Front Panel (320VA-1200VA and 1500VA)

1)  “ REPLACE BATTERY “ indicator (RED LED): 

The LED illuminates when the UPS’s battery is 

no longer useful and must be replaced.  

 

Caution: Do not attempt to open the UPS or 

replace the battery. Call technical support 

(800-377-4384) when battery replacement 

 

is required. 

2)  “ BACK UP” indicator (YELLOW LED): 

 

The LED illuminates when the UPS is 

 

supplying battery power to the loads.

3)  “ LINE NORMAL” indicator (GREEN LED):  

 

The LED illuminates when the line input 

 

voltage is normal.

4)  “ ON/OFF/TEST” button: 

 

Press the button more  
than 1 second to turn the UPS on or off, press 
the button less than 1 second to activate the  

UPS’s self-testing. Press for more than 

 

2 seconds to turn off.

Alarms

1.  

“BACK UP” (slow beeping)

  

   

  When in BACK UP mode, the YELLOW LED illuminates and the UPS sounds 

an audible alarm. The alarm stops when the UPS returns to LINE 

 

NORMAL operation.

2.   

“LOW BATTERY”  (rapid beeping)

       In BACK UP mode when the battery energy runs low, the UPS beeps rapidly 

until the UPS shuts down from battery exhaustion or returns to LINE 

 

NORMAL operation.

3.  

“OVERLOAD”  (continuous alarm)

       When the UPS is overloaded (the connected loads exceed the maximum rated 

capacity), the UPS sounds a continuous alarm and LED to warn of an overload 
condition.  Remove non-critical loads from the battery power outlets to 

 

eliminate the overload.

320VA - 1200VA

1500VA

Rear Panel (320VA-1200VA)

5)  TEL/SURGE PROTECTION

6)   INPUT CIRCUIT BREAKER: Protection from 

AC overload and Short-circuit.

7)  AC INPUT POWER CORD

8)  UPS OUTPUT OUTLETS (Black) 

9)  SURGE PROTECTED OUTLET (White)

5)  “ LED indicator: 

 

The LED indicator indicates the UPS’s status.  The indicator is illuminated 

steady when the UPS is supplying utility power to the loads.  The indicator 

flashes slowly (about once every 2 second) when the UPS is supplying 

 

battery power to the loads.  The indicator flashes rapidly (about once every 

 

0.5 second) when loads connected to the UPS exceed the UPS’s capacity.

* 650 VA and above models

Содержание S1K320

Страница 1: ...mages resulting from use of this information or for any errors or omissions 2007 Sola Hevi Duty All rights reserved throughout the world Specifications are subject to change without notice Sola Hevi D...

Страница 2: ......

Страница 3: ...uct with Sola Hevi Duty Warranty Information Please see enclosed Terms Conditions and Sales Policies Procedures 1 12 Table of Contents Important Safety Instructions 2 Storage 3 Introduction System Des...

Страница 4: ...105 of nominal at 20 seconds 120 at 10 seconds 130 at 3 seconds UPS automatic shutdown if overload exceeds 110 of nominal at 60 seconds 130 at 3 seconds Short Circuit UPS output cut off immediately or...

Страница 5: ...has been designed and manufactured to assure personal safety improper use can result in electrical shock or fire To ensure safety please observe the following rules Turn off UPS and disconnect the AC...

Страница 6: ...ORT at computer side can be either COM 1 or COM 2 The other installation instructions and powerful features please refer to READ ME file Characteristics of Computer Interface Port The computer interfa...

Страница 7: ...LOW BATTERY rapid beeping In BACK UP mode when the battery energy runs low the UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to LINE NORMAL operation 3 OVERLOAD contin...

Страница 8: ...ing and hold the on off test button more than 2 seconds until the LINE NORMAL or BACK UP LED off to switch the UPS off 5 Self test Use the self test to verify both the operation of the UPS and the con...

Отзывы: