Testing the RM-DCM-2

34

Self-Test Mode

The RM-4E has a built-in self-test mode. Perform the steps in this section 

to run the self-test. 

1. Remove power to the RM-4E.
2. Set Rotary Switch SW4 to position 0. 
3. To test the reader LEDs, connect three LEDs to the Reader LED port as 

shown in Figure 19. Connect the anode (long lead) of each LED to Pin 1 

(+5v). Cover the LED wires with heat shrink to prevent short circuits. 

NOTE

If you are using an older LED that does not have a built-in current-limiting 
resistor, add a 1K-ohm resistor in series. 

FIGURE 19.  Connecting LEDs for Self-Test Mode

4. Power up the RM-4E. When you power up the RM-4E:

Relays 1 and 2 toggle every second.

Reader LED lines Red, Green, and Yellow flash on and off.

The LCD displays the information shown in Figure 20. 

Содержание RM-DCM-2

Страница 1: ...harged by the RM 4E battery charging circuit The RM 4E board provides the hardware interface between Magnetic signaling read heads or Wiegand signaling read heads and the apC 8X iSTAR and iSTAR Pro ha...

Страница 2: ...STAR Pro hardware TABLE 1 RM DCM 2 Product Offering Product Description Enclosure RM DCM 2 RM 4E module with connectors LEDs on board relays and battery charger Factory mounted in metal junction box w...

Страница 3: ...display RS 485 inputs outputs and power status Maglock component for use with door objects Bypass component connects to a release switch on a door secured by a magnetic lock On board battery charger...

Страница 4: ...the Off Open position for Magnetic read heads NOTE The RM DCM 2 has been evaluated by Underwriters Laboratories Inc UL for compatibility with HID Model 30387 and HID 5355 readers only RM DCM 2 with R...

Страница 5: ...igure 2 2 Verify or set DIP switch SW5 4 Tamper Override to Off Closed on the RM 4E See Figure 5 3 To configure the tamper C CURE 800 use the Reader Configuration Advanced dialog box C CURE 9000 use t...

Страница 6: ...upply Wiegand signaling or magnetic ABA signaling to the apC 8X iSTAR and iSTAR Pro using RM 4E boards Figure 3 indicates how an RM 4E board interfaces with Wiegand and Magnetic signaling read heads F...

Страница 7: ...RM 4E Reader Interface 7 RM 4E Layout Figure 4 shows the photograph of an RM 4E board with LCD FIGURE 4 Photograph of RM 4E Board...

Страница 8: ...on the RM 4E board RM 4E Board Layout FIGURE 5 RM 4E Board Layout This section lists the RM 4E components starting from the upper right corner of Figure 5 and moving in a clockwise direction Tamper Th...

Страница 9: ...pable of four hours standby must be used when the unit is powered from a source other than the apC or iSTAR FIGURE 6 RM 4E Power Wiring Method A Method A via Power In Connect 12 or 24 VDC to Pin 2 of...

Страница 10: ...he Power In connector LED Connector Table 2 lists LED Connector Signals and Functions on the RM 4E board NOTE UL has not evaluated using Pin 5 to drive an external beeper Typical LED Scenarios One wir...

Страница 11: ...ad heads to the Read Head connector Connect either a Wiegand signaling device or a magnetic ABA signaling device Wiegand signaling uses Data 1 and Data 0 lines and magnetic signaling uses Clock and Da...

Страница 12: ...ong with the MagLock and Bypass connectors have internal etch connections for wiring magnetic and electric strike locks Tie Point TP1 TP2 connector pins are not connected to the circuitry They are use...

Страница 13: ...e examples are shown as Fail Secure Magnetic Locks The normal state of a magnetic lock has current flowing through an electromagnet on the lock that pulls a strike plate with a force of 500 2000 lbs S...

Страница 14: ...Lock Wiring Configurations 14 FIGURE 8 Magnetic Lock Wiring with Jumper Options...

Страница 15: ...e lock to earth ground The connection from the minus side of the power supply must go to Maglock pin 3 Bypass Switch Connect a normally closed NC emergency Bypass switch as shown Remove the J15 Bypass...

Страница 16: ...and unlock when powered You must decide if you want to wire for fail secure or fail safe Fail secure means that if there is a power failure the door goes to a secure or locked state Fail safe fail op...

Страница 17: ...Lock Wiring Configurations 17 FIGURE 9 Relay 2 Fail Secure Wiring...

Страница 18: ...de jumper closed If the electric strike has a suppression diode built in disconnect the J13 Diode jumper open Using Relay 1 for an Electric Strike Relay 1 is a standard Form C dry contact relay Wiring...

Страница 19: ...l Secure Wiring INPUTS Input 1 and Input 2 Connect inputs using the standard Software House supervision for either NO or NC Figure 11 shows an example of wiring Normally Open NO and Normally Closed NC...

Страница 20: ...inal 500 ohms or 2K ohms Green LED indicates secure hardware state nominal 1k ohms Yellow LED indicates supervision error open circuit shorted or line fault The RM 4E input status LEDs show flashing s...

Страница 21: ...on RM 4 SW 5 1 Reader Type Off Magnetic ABA signaling On Wiegand signaling SW 3 1 SW 5 2 LED Control Off Normal On One Wire A B C SW 3 6 SW 5 3 LED Control Off Normal On External Bi color SW 3 3 SW 5...

Страница 22: ...TABLE 9 SW5 LED Control Three Wire LED Control When both SW5 3 and SW5 2 are Off it specifies Three wire LED control In this case the Red Green and Yellow LED drives are wired to the associated LED of...

Страница 23: ...2 sec Off Off Access denied Software Flag Enabled Off Off On Access granted or door unlocked Software Flag Enabled Off Off Fast flash Access granted Off Off Slow flash Door unlocked Off Slow flash Off...

Страница 24: ...and Green in the reader The LEDs will appear as Yellow when both Red and Green are on making the function essentially a Tri color Red Green Yellow Two Wire Red and Green There are two cases of Extern...

Страница 25: ...man eye that the LED is Yellow The RM 4E will oscillate the Yellow drive at 1 KHz when a Yellow LED display is required FIGURE 14 External Bi color 1 wire Special RM 4E 1 Wire LED Control Setting both...

Страница 26: ...s One Wire A B C mode In this case a single LED drive Red or Green or Yellow is wired with varying results as shown in Figure 15 One wire mode is typically used for older read heads with a single LED...

Страница 27: ...nd includes a tamper switch and key lock This section describes the dimensions and installation requirements for the RM DCM 2 enclosure and modules Installing the Enclosure Make sure the installation...

Страница 28: ...Hole Dimensions Enclosures UL has approved the RM DCM 2 enclosure for use with R 8 and I 8 boards Mounting the RM 4E R 8 and I 8 Boards To mount the RM 4E R 8 and I 8 boards in an RM DCM 2 enclosure...

Страница 29: ...e voltage drop due to wiring length NOTE A UL Listed power limited access control or burglar alarm power supply capable of four hours standby must be used when the unit is powered from a source other...

Страница 30: ...ations of the RM 4E board in the RM DCM 2 enclosure TABLE 11 RM 4E Power Requirements and Operating Specifications Requirement Specification RM 4E Power requirements 12 24 VDC 280 mA without reader an...

Страница 31: ...Requirements and Operating Specifications Requirement Specification Contact Ratings R 8 module power requirements 125mA at 12 VDC plus 25mA for each Active Relay R 8 relay contact rating 2A at 30 VDC...

Страница 32: ...C Part 15B class A CE EN50081 1 EN50130 4 Requirement Specification Enclosure dimensions 14 x 12 x 3 5 in 35 6 x 30 5 x 8 9 cm Weight without battery 10 lbs 4 53 kg TABLE 14 RM DCM 2 Parts List Descri...

Страница 33: ...required Two 1K resistors An LCD display module 2 line x 16 character Software House part number RM LCD Three LEDs A multi meter to measure voltage and resistance Configuration Requirements You must c...

Страница 34: ...gure 19 Connect the anode long lead of each LED to Pin 1 5v Cover the LED wires with heat shrink to prevent short circuits NOTE If you are using an older LED that does not have a built in current limi...

Страница 35: ...a 1 in the appropriate reader line position to indicate that the data line is low for example W 010 when you short the D1 line After removing the short from the data line the display should revert to...

Страница 36: ...oltage must be 12 Volts 5 or 24 Volts 10 2 Check the RM 4E address setting The RM 4E must be set to an unused address when connected to the apC or ISTAR The LCD will display the switch setting upon po...

Страница 37: ...sted with the reader chosen for the installation Reading a card will cause the display to show Access Granted or Access Denied depending upon the clearance of the card CE NOTICE This product is in com...

Страница 38: ...f these products or for an infringement of rights of the other companies that may result from their use RM DCM 2 Quick Start Installation Guide Document Number UM 215 Revision H0 Print Date March 2018...