SOFTLINK WB169-SI2 Скачать руководство пользователя страница 43

visually check an external antenna and antenna cable (if used), possibly replace these elements for the spare
ones with proven functionality;

check correctness of module settings, especially setting of radio parameters as described in paragraph

3.1.11

and perform the check of module overall functionality as described in paragraph

4.8

;

replace the module according to the paragraph

4.6

and perform the setting and check of overall functionality

off the new module after that;

if the module is not properly working even after its replacement for proven device and equipment, the trouble
can be caused by local interference (jamming) from external source. Another possible reason could be an
unsuitable setting of some configuration parameter that has not been discovered. In this case ask for your
supplier, producer, or other experienced person for some form of assistance.

Appropriate level of transmitting power can be checked by comparing of its signal strength with the reference
signal from another module (modules) under comparable circumstances, for example with using of signal analyzer
or testing receiver placed to the suitable spot. If the signal strength is similar to the signal of reference transmitter,
then the module’s transmitting power is adequate, and the reason of troubles could be in insufficient signal strength
on the receiving side. Attenuation of the signal can be caused by making of some change in module installation
site (e.g. turning of antenna or placing of some object nearby, installation of iron bars, rack or shelfs...) or similar
changes in the installation site of receiver (GateWay). This kind of troubles can be solved by redesign of the radio
network in order to secure sufficient signal reception (that means changing of antenna for better type, moving of
antenna or whole device etc.).

5.1.4

Failures of communication with meters

Failures of pulse signal transfer from the consumption meters to the correspond module inputs typically appear as

zero consumption” of the meter even though the consumption of the meter is evident, or generally, meter status

from remote reading is different than meter status shown in meter’s mechanical counter. In this case try to proceed
with troubleshooting of the connection with meters in following steps:

1. Visually check the meter and connecting cable between meter and radio-module, especially whether the meter’s

pulse generator is correctly mounted on the meter (if it is removable) and whether the meter or cable are not
damaged;

2. in case of any doubt check the functionality of cable connection by ohm-meter. If there is a problem with

reliability of the connection, or the cable is evidently damaged, replace the cable immediately;

3. check whether the cable is correctly associated with the module input (correct port number, correctness of

polarity - if required by meter producer);

4. Visually check if there are not placed any objects or devices radiating a magnetic field (for example a device for

water treatment with magnet, electrical installation. . . ) around the consumption meter. The pulse generators
of some types of the consumption meters are very sensitive to the magnetic field presence. If such devise
is detected, it must be removed or there must be taken necessary measures to eliminate the magnetic field
influence on the pulse generator of the consumption meter. To find more about the influence of the magnetic
field on a particular consumption meter, you must follow its manufacturer instructions;

5. if there is some possibility of measuring metering pulses, make sure that the meter generates the pulses

properly and that these pulses lead up entirely to the radio module input;

6. correctness of generating and transfer of metering pulses can be alternatively checked by short-circuiting of

the cable on the meter side. If after each short-circuit the status value of the module’s counter goes up, the
module and cable are probably correct, and the trouble is probable caused by meter or by its pulse generator;

7. if the module doesn’t read the data even the metering pulses are provably brought to the correct radio module

input, check the pulse counter parameter settings (counter mode, trigger edge) according to the paragraph

3.1.6

Internal Counter Setting Commands”. In case the setting is correct, the problem is the most probably in the

malfunction of the radio module. Replace the module following the instructions in the paragraph

4.6

.

If the module register

false” pulses (consumption registered by remote reading is significantly higher than con-

sumption registered by mechanical counter) and setting of the counter to

slow” mode has not solved the problem,

the failure could be caused either by too long or poor-quality cable or strong local disturbance (or combining of these
two circumstances). In this case replace the cable for high-quality shielded one or make changes in the installation
to shorten the cable.

In case of unstable data transfer from connected sensors the signs of failure are very similar to the troubles with
pulse meters - the wrong indication of measured data from sensors. Troubleshooting of this failure is similar with
troubleshooting of pulse meters:

1. visually check the sensor and connecting cable between sensor and radio-module for any damage;

WB169-SI2

40

Содержание WB169-SI2

Страница 1: ...WIRELESS COMMUNICATION SYSTEM Wireless M BUS WB169 SI2 Revision 1 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Страница 2: ...for RF subsystem diagnostics 20 3 1 12 Commands of Utils group for setting of module common functions 20 3 1 13 Overview of module configuration parameters 22 3 2 Setting of parameters by using of opt...

Страница 3: ...le 24 10 Basic forms of WB169 SI2 module in SOFTLINK Configurator application 27 11 Input output setting form and form for setting of encryption 28 12 View of WB169 SI2 module information message rece...

Страница 4: ...appointed element of the radio network repeater or slave with such functionality Each repeated message is marked as repeated message so as not to be repeated again 1 2 Module usage The WB169 SI2 modul...

Страница 5: ...g of opening closing of overhead doors of halls where the module can provide information about current status of each door and measure number of open close cycles of the doors Another example is monit...

Страница 6: ...red remote control with using of optical converter The module is equipped with the circular crater shaped pit that supports magnetic fixing of optical converter with holding on magnet in right positio...

Страница 7: ...ce Transmission speed 115 200 Baud Optical I F specification complies with IrPHY 1 4 standard Pulse sensor inputs Resistance of released contact more than 10 M Resistance of short circuited contact le...

Страница 8: ...acoSystem product family devices The description and meaning of the parameters that can be changed by optical converter can be found in the section 3 2 Setting of parameters by using of optical conver...

Страница 9: ...S version 0 255 medium Show or set MBUS medium 0 255 periode Change periode of send 0 disable 0 periode in minutes 0 from input mode Set WMBUS mode 1 N1 2 N2 chan Set WMBUS channel type for help ekey...

Страница 10: ...s configuration parameters it does so only in operating configuration If the current operating configuration was not stored to FLASH memory the module returns to the saved configura tion after reset I...

Страница 11: ...mmunication mode 1 N1 mode 2 N2 mode chan setting of frequency channel choice from 7 options ekey setting of encryption key encryption disabled Variable M BUS ID is a serial number of the device in M...

Страница 12: ...info XYZ cfg Maximum length of the string is 29 characters The only basic set of characters can be used without diacritics It is not recommended to change this parameter Periode command serves for set...

Страница 13: ...for transmitting power 27 dBm 500 mW An example of checking setting and re checking of transmitting power cfg power MBUS power 3 20 dBm cfg power 5 MBUS power changed from 3 to 5 27 dbm cfg power MBU...

Страница 14: ...is set to the module s configuration an information Data will be encrypted by AES displays in the list of configuration parameters see chapter 3 1 1 Encryption can be switched off by setting of dot p...

Страница 15: ...coming pulse Actual counter value can be displayed by using of val index command without parameter Counter status can be set to required value by using of val index command followed by required whole...

Страница 16: ...0 If it is needed to get volume in other units than litres e g in m3 or other quantity than volume is measured e g electrical work in kWh it is necessary to adjust values of multiplier and divisor to...

Страница 17: ...t 1000 x Wh unit is presented as 1000 000 Wh By using of det index command a trigger edge of the counter could be chosen If it is preset to 0 option default setting the value of counter will increase...

Страница 18: ...ume If there are any leaks time intervals with zero consumption practically either do not occur or there are only short intervals caused by discontinuity of measuring system e g if one metering pulse...

Страница 19: ...in the consumption of gas water or other liquids when the burst consumption caused by broken pipe or similar fatal failure of distribution system occurs If the consumption of liquid gas is abnormally...

Страница 20: ...es in normal operation e g during filling a tank with water but in the same time it will prolong the response time between the breakdown and sending of alarm Setting of Burst alarm function parameters...

Страница 21: ...atus after transition value is 0 or 1 and a relevant port identifi cation coded into DIF code as follows status of 0 input DIF 31 status of 1 input DIF 71 VIF code is alway set to FD 3A value that in...

Страница 22: ...ching function activated all input pulses are carried only to the first input The second physical input is connected to the tariff switching control voltage see figure 7 Input pulses from the first po...

Страница 23: ...eration Using of these commands can cause inoperability of the device 3 1 12 Commands of Utils group for setting of module common functions This group of commands is intended for control and setting o...

Страница 24: ...follows cfg time 0x182555 RTC time 18 25 55 2019 01 30 systime 1548869155 2019 01 30 18 25 55 01 cfg date 0x190128 RTC time 18 26 58 2019 01 28 systime 1548696418 2019 01 28 18 26 58 01 cfg As it is...

Страница 25: ...command can be used during installation and testing of the module An example of the command for sending of series of 5 messages mon sendp 5 send 5 msgs mon The command reset performs the module reset...

Страница 26: ...t 0 65535 Alarm limit value Burst function 0 17 Burst periode 0 1090 Burst check time Burst function 0 18 Radio Power 1 5 Transmitting power 5 19 Comm mode 1 2 Communication mode 1 N1 20 Channel 1 7 F...

Страница 27: ...the module s cover This is the significant advantage especially if the module is used in humid environment and has been sealed by additional silicon filling additional adaptation for IP 68 proofing An...

Страница 28: ...ditable for the WB169 SI2 it is an editable part of full meter sensor M Bus identification the default value of the Medium parameter is 07 Water More detailed description of the variable and possibili...

Страница 29: ...for setting of counter trigger edge Falling option means that the counter value will increase with falling edge of measuring pulse i e short circuiting of mechanical contact or 1 to 0 transition of el...

Страница 30: ...details in section 3 1 11 Modem group commands The WMBUS Mode parameter can be used for selection of the module s WMBUS communication mode Factory setting is N1 mode variable is entered by choosing f...

Страница 31: ...d information message with status of all variables broadcasted periodically short alarm message sent immediately when alarm status has been detected 3 3 1 Iinformation message Information message of t...

Страница 32: ...e AES 128 data encryption is switched on there are two additional Figure 12 View of WB169 SI2 module information message received by WMBUSAN4 analyzer control segments inserted before data segments of...

Страница 33: ...s Positive events of NO LEAK NO BURST type are generated in that case when after one or several alarm periods a period without alarm status came around Each alarm message has Wireless M BUS header WMB...

Страница 34: ...information about the current status of sensor input counter i e number of transitions since last counter reset The DIF and VIF values correspond with setting of given input transferred data value Val...

Страница 35: ...ischarging current increases in low temperature the battery capacity reduces frequency of radio transmitting Modules are delivered with preset period of regular transmitting of info messages as stated...

Страница 36: ...30 C To prevent the unwanted discharging of internal battery it is recommended storing the modules with batteries disconnected and activate the battery during mounting with exception of modules with a...

Страница 37: ...the module to a suitable firm object wall pipe by two screws or by a clamping tape There are mounts by the box sides for the attachment The recommended position of the mounted module is in the way th...

Страница 38: ...rea of installation as well as protection of the device against possible mechanical damage The radio signal conditions can be estimated empirically on the base of previous experience or examined by me...

Страница 39: ...meter 4 7 Module dismantling When dismantling open the module disconnect cables and dismantle the cap from the wall pad or pipe Switch the battery off and put the module parts back together put the ca...

Страница 40: ...is necessary to carry out the installation carefully with using of high quality cables and mounting components To prevent an unexpected breakdown it is recommended to perform regular monitoring of al...

Страница 41: ...t segment In this case the primary cause of alarm status should be opening of security loop that causes detachment of contact head from magnet and releasing of reed contact inside the head Releasing o...

Страница 42: ...k functionality of the new module If the new device works properly label the original module as defective and fill in the appropriate documentation prescribed by internal rules for this case 5 1 3 Tra...

Страница 43: ...ctionality of cable connection by ohm meter If there is a problem with reliability of the connection or the cable is evidently damaged replace the cable immediately 3 check whether the cable is correc...

Страница 44: ...h meters 2 No data are available from only one meter sensor connected to the WB169 SI2 module In this case it is recommended to check functionality of the module subsystems in following order check fu...

Отзывы: