SOFTLINK WB169-SI2 Скачать руководство пользователя страница 4

1

Introduction

This document describes features, parameters and setting possibilities of the WB169-SI2 module, which is used for
reading of either consumption meters with pulse output (water meters, electrometers, gas-meters. . . ), or two-state
sensors (e.g. door contacts, flood detectors, fire detectors, electronic seals...etc.) and for radio-broadcasting of the
data from connected meters/sensors to the superior remote reading system in form of Wireless M-BUS standard
messages. The WB169-SI2 module works either in unidirectional communication mode N1, or in the bidirectional
N2 mode. In both modes the module regularly broadcasts information messages of

User Data” type intended for

superior

master” device. In bidirectional N2 mode it is possible to use a back channel from master device, that

can be used for transfer of

Request” type of messages with remote configuration demands. In

alarm mode” the

module sends

Alarm from meter” type of messages based on the sensor status changes. These messages are sent

immediately, out of regular broadcasting interval.

1.1

Wireless M-BUS Communication Protocol

Wireless M-BUS is the communications protocol described by international standards EN 13757-4 (physical and
link layer) and EN 13757-3 (application layer), which is intended primarily for radio transmission of remote reading
values from consumption meters and sensors. Protocol Wireless M-BUS (hereinafter

WMBUS”) is based on a

standard M-BUS definition (uses the same application layer as M-BUS standard), but is adapted for data transfer
via radio signals.

Communications via WMBUS protocol works in Master-Slave mode, where

Master” is a collecting data device,

Slave“ is a providing data device. Slave device could be integrated or external radio module transmitting data

from the meter/sensor. The communications protocol WMBUS defines several communication modes (simplex or
duplex). If working in simplex mode a

Slave” device only transmits messages to

Master” that these messages

receives. If working in

bidirectional” mode, it is possible to use a back channel from

Master” device to

Slave”

device for

Request” type of messages, that can contain e.g. request for the change of slave’s configuration.

Wireless M-BUS communications protocol partially supports repeating of the messages. If receiving from some

Slave” device is not possible because of the low level of radio signal, the messages can be re-transmitted (repeated)

by appointed element of the radio network (repeater or slave with such functionality). Each repeated message is
marked as

repeated message” so as not to be repeated again.

1.2

Module usage

The WB169-SI2 module can be used either for remote reading of two consumption meters with pulse output, or for
transfer of alarm messages from two two-state sensors. It is possible to combine both type of usage.

When using for

remote reading of consumption meters

(water meters, gas-meters, electro-meters...), up to

two meters with standard pulse (”SI”) output can be connected to the module. The meters can be of different kind,
with different quantities and units and with different conversion rates. The module continuously registers incoming
pulses (generated by meters) into its internal counters, with using of preconfigured multipliers/divisors converts
current status of each counter into the required output units (m3, kWh, MJ...) and broadcasts info-messages with
current statuses of all connected meters as Wireless M-BUS

User Data” messages.

When using for

remote monitoring of sensor statuses

(door contacts, flood detectors, fire detectors, electronic

seals..), up to two two-state sensors with ”off/on” (”0/1”) outputs can be connected to the module. The sensors
can be of different kind, with different type of output and different logic of signaling. The module continuously
monitors status of each sensor and records all its changes. If the counter is switched into alarm mode, the module
immediately transmits alarm messages according to preselected rule. The module regularly broadcasts in each
info-message the number of

0-to-1” transitions, as well as current sensor status (”0” or ”1”). If the counter is

switched into the alarm mode, the module sends

Alarm from meter” message immediately at the change of sensor

status.

Each regular

information message

contains module identification, values of both counters, actual statuses of

all connected sensors in alarm mode and operational entries from embedded sensors (battery voltage, processor
temperature). Each

alarm message

contains only module identification and information about the actual status

of that port, on which the status was changed. Detailed information about the content and format of information
and alarm messages can be found in paragraph

3.3

.

Information and alarm messages are transmitted either in open mode (without encryption), or encrypted by AES-
128 encryption key. The messages are transmitted on the 169.4 MHz frequency with data rate from 2.4 kbps to
19.2 kbps (according to used frequency channel). Messages can be received either by WB169-RFE communication

WB169-SI2

1

Содержание WB169-SI2

Страница 1: ...WIRELESS COMMUNICATION SYSTEM Wireless M BUS WB169 SI2 Revision 1 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Страница 2: ...for RF subsystem diagnostics 20 3 1 12 Commands of Utils group for setting of module common functions 20 3 1 13 Overview of module configuration parameters 22 3 2 Setting of parameters by using of opt...

Страница 3: ...le 24 10 Basic forms of WB169 SI2 module in SOFTLINK Configurator application 27 11 Input output setting form and form for setting of encryption 28 12 View of WB169 SI2 module information message rece...

Страница 4: ...appointed element of the radio network repeater or slave with such functionality Each repeated message is marked as repeated message so as not to be repeated again 1 2 Module usage The WB169 SI2 modul...

Страница 5: ...g of opening closing of overhead doors of halls where the module can provide information about current status of each door and measure number of open close cycles of the doors Another example is monit...

Страница 6: ...red remote control with using of optical converter The module is equipped with the circular crater shaped pit that supports magnetic fixing of optical converter with holding on magnet in right positio...

Страница 7: ...ce Transmission speed 115 200 Baud Optical I F specification complies with IrPHY 1 4 standard Pulse sensor inputs Resistance of released contact more than 10 M Resistance of short circuited contact le...

Страница 8: ...acoSystem product family devices The description and meaning of the parameters that can be changed by optical converter can be found in the section 3 2 Setting of parameters by using of optical conver...

Страница 9: ...S version 0 255 medium Show or set MBUS medium 0 255 periode Change periode of send 0 disable 0 periode in minutes 0 from input mode Set WMBUS mode 1 N1 2 N2 chan Set WMBUS channel type for help ekey...

Страница 10: ...s configuration parameters it does so only in operating configuration If the current operating configuration was not stored to FLASH memory the module returns to the saved configura tion after reset I...

Страница 11: ...mmunication mode 1 N1 mode 2 N2 mode chan setting of frequency channel choice from 7 options ekey setting of encryption key encryption disabled Variable M BUS ID is a serial number of the device in M...

Страница 12: ...info XYZ cfg Maximum length of the string is 29 characters The only basic set of characters can be used without diacritics It is not recommended to change this parameter Periode command serves for set...

Страница 13: ...for transmitting power 27 dBm 500 mW An example of checking setting and re checking of transmitting power cfg power MBUS power 3 20 dBm cfg power 5 MBUS power changed from 3 to 5 27 dbm cfg power MBU...

Страница 14: ...is set to the module s configuration an information Data will be encrypted by AES displays in the list of configuration parameters see chapter 3 1 1 Encryption can be switched off by setting of dot p...

Страница 15: ...coming pulse Actual counter value can be displayed by using of val index command without parameter Counter status can be set to required value by using of val index command followed by required whole...

Страница 16: ...0 If it is needed to get volume in other units than litres e g in m3 or other quantity than volume is measured e g electrical work in kWh it is necessary to adjust values of multiplier and divisor to...

Страница 17: ...t 1000 x Wh unit is presented as 1000 000 Wh By using of det index command a trigger edge of the counter could be chosen If it is preset to 0 option default setting the value of counter will increase...

Страница 18: ...ume If there are any leaks time intervals with zero consumption practically either do not occur or there are only short intervals caused by discontinuity of measuring system e g if one metering pulse...

Страница 19: ...in the consumption of gas water or other liquids when the burst consumption caused by broken pipe or similar fatal failure of distribution system occurs If the consumption of liquid gas is abnormally...

Страница 20: ...es in normal operation e g during filling a tank with water but in the same time it will prolong the response time between the breakdown and sending of alarm Setting of Burst alarm function parameters...

Страница 21: ...atus after transition value is 0 or 1 and a relevant port identifi cation coded into DIF code as follows status of 0 input DIF 31 status of 1 input DIF 71 VIF code is alway set to FD 3A value that in...

Страница 22: ...ching function activated all input pulses are carried only to the first input The second physical input is connected to the tariff switching control voltage see figure 7 Input pulses from the first po...

Страница 23: ...eration Using of these commands can cause inoperability of the device 3 1 12 Commands of Utils group for setting of module common functions This group of commands is intended for control and setting o...

Страница 24: ...follows cfg time 0x182555 RTC time 18 25 55 2019 01 30 systime 1548869155 2019 01 30 18 25 55 01 cfg date 0x190128 RTC time 18 26 58 2019 01 28 systime 1548696418 2019 01 28 18 26 58 01 cfg As it is...

Страница 25: ...command can be used during installation and testing of the module An example of the command for sending of series of 5 messages mon sendp 5 send 5 msgs mon The command reset performs the module reset...

Страница 26: ...t 0 65535 Alarm limit value Burst function 0 17 Burst periode 0 1090 Burst check time Burst function 0 18 Radio Power 1 5 Transmitting power 5 19 Comm mode 1 2 Communication mode 1 N1 20 Channel 1 7 F...

Страница 27: ...the module s cover This is the significant advantage especially if the module is used in humid environment and has been sealed by additional silicon filling additional adaptation for IP 68 proofing An...

Страница 28: ...ditable for the WB169 SI2 it is an editable part of full meter sensor M Bus identification the default value of the Medium parameter is 07 Water More detailed description of the variable and possibili...

Страница 29: ...for setting of counter trigger edge Falling option means that the counter value will increase with falling edge of measuring pulse i e short circuiting of mechanical contact or 1 to 0 transition of el...

Страница 30: ...details in section 3 1 11 Modem group commands The WMBUS Mode parameter can be used for selection of the module s WMBUS communication mode Factory setting is N1 mode variable is entered by choosing f...

Страница 31: ...d information message with status of all variables broadcasted periodically short alarm message sent immediately when alarm status has been detected 3 3 1 Iinformation message Information message of t...

Страница 32: ...e AES 128 data encryption is switched on there are two additional Figure 12 View of WB169 SI2 module information message received by WMBUSAN4 analyzer control segments inserted before data segments of...

Страница 33: ...s Positive events of NO LEAK NO BURST type are generated in that case when after one or several alarm periods a period without alarm status came around Each alarm message has Wireless M BUS header WMB...

Страница 34: ...information about the current status of sensor input counter i e number of transitions since last counter reset The DIF and VIF values correspond with setting of given input transferred data value Val...

Страница 35: ...ischarging current increases in low temperature the battery capacity reduces frequency of radio transmitting Modules are delivered with preset period of regular transmitting of info messages as stated...

Страница 36: ...30 C To prevent the unwanted discharging of internal battery it is recommended storing the modules with batteries disconnected and activate the battery during mounting with exception of modules with a...

Страница 37: ...the module to a suitable firm object wall pipe by two screws or by a clamping tape There are mounts by the box sides for the attachment The recommended position of the mounted module is in the way th...

Страница 38: ...rea of installation as well as protection of the device against possible mechanical damage The radio signal conditions can be estimated empirically on the base of previous experience or examined by me...

Страница 39: ...meter 4 7 Module dismantling When dismantling open the module disconnect cables and dismantle the cap from the wall pad or pipe Switch the battery off and put the module parts back together put the ca...

Страница 40: ...is necessary to carry out the installation carefully with using of high quality cables and mounting components To prevent an unexpected breakdown it is recommended to perform regular monitoring of al...

Страница 41: ...t segment In this case the primary cause of alarm status should be opening of security loop that causes detachment of contact head from magnet and releasing of reed contact inside the head Releasing o...

Страница 42: ...k functionality of the new module If the new device works properly label the original module as defective and fill in the appropriate documentation prescribed by internal rules for this case 5 1 3 Tra...

Страница 43: ...ctionality of cable connection by ohm meter If there is a problem with reliability of the connection or the cable is evidently damaged replace the cable immediately 3 check whether the cable is correc...

Страница 44: ...h meters 2 No data are available from only one meter sensor connected to the WB169 SI2 module In this case it is recommended to check functionality of the module subsystems in following order check fu...

Отзывы: