HYD 5-20KTL-3PH
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
。
- 60 -
versions
upgrades.
ID157
BMSCommunica
tonFault
Communication failure
of lithium battery
Make sure your battery is compatible with
the inverter.
CAN communication is recommended.
Check the communication line or port of the
battery and inverter for faults.
ID161
ForceShutdown
Force shutdown
The inverter is performed a forced
shutdown
ID162
RemoteShutdown
Remote shutdown
The inverter is performed a remote
shutdown.
ID163
Drms0Shutdown
Drms0 shutdown
The inverter is performed with a Drms0
shutdown.
ID165
RemoteDerating
Remote derating
The inverter is performed for remote load
reduction.
ID166
LogicInterfaceDe
rating
Logic interface derating
The inverter is loaded by the execution
logic interface.
ID167
AlarmAntiReflux
ing
Anti reflux derating
The inverter is implemented to prevent
countercurrent load drop.
ID169
FanFault1
Fan 1 fault
Please check whether the fan 1 of inverter is
running normally.
ID170
FanFault2
Fan 2fault
Please check whether the fan 2 of inverter is
running normally.
ID171
FanFault3
Fan 3 fault
Please check whether the fan 3 of inverter is
running normally.
ID172
FanFault4
Fan 4 fault
Please check whether the fan 4 of inverter is
running normally.
ID173
FanFault5
Fan 5 fault
Please check whether the fan 5 of inverter is
running normally.
ID174
FanFault6
Fan 6 fault
Please check whether the fan 6 of inverter is
running normally.
ID177
BMS OVP
BMS
over-voltage Internal failure of lithium battery, close