- 20 -
1. M5 screw
2. OT Terminal
3. Tapped hole
③
4.3. Battery Connection & PV Connection
The connection mode of Battery connection and PV connection is the same,
only the terminal specifications are different. Please correctly correspond when
inserting the terminal into the machine end.
Procedure
:
Step 1
Select the appropriate cable type and specifications according to the
table4-3.Remove cable glands from the positive and negative connectors.( It is
recommended that the positive and negative be distinguished by different colors).
Step 2
Remove the insulation layer with an appropriate length from the
positive and negative power cables by using a wire stripper as show in Fig.4-2
①
.
Step 3
Insert the stripped positive and negative power cables into the positive
and negative metal terminals respectively and crimp them using a clamping tool.
Ensure that the cables are crimped until they cannot be pulled out by force less than
400 N, as shown in Fig.4-2
②③
.
Step 4
Insert crimped power cables into corresponding housings until you
hear a "click" sound. The power cables snap into place.
Step 5
Reinstall cable glands on positive and negative connectors and rotate
them against the insulation covers.
Step 6
Insert the positive and negative connectors into corresponding
Battery&PV terminals of the inverter until you hear a "click" sound, as shown in
Fig.4-2
⑥
.
To remove the positive and negative connectors from the inverter, insert a