13
EN
SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01
• the maximum power required from the load (at 40 °C ambient temperature).
Distance from the rear wall
Space above the top panel
Power
30 cm
45 cm
100%
25 cm
90%
20 cm
45 cm
90%
25 cm
80%
10 cm
45 cm
75%
25 cm
75%
SPACING-AIR FLOW
Typical air extraction structure
SUNSYS
PCS
2
hood
air
air extractor
external
environment
internal
environment
≥
10 cm
Minimum air extractor flow
(1)
Models
Minimum extraction
fl
ow
33 TR
600 m
3
/h
66 TR
1200 m
3
/h
100 TR
1800 m
3
/h
66 TL
900 m
3
/h
100 TL
1350 m
3
/h
132 TL
1780 m
3
/h
200 TL
2700 m
3
/h
1. SUNSYS PCS
2
at a distance of 10 cm from the rear wall (40 °C ambient temperature and full load).
NOTE: the hood must prevent air losses and enable the removal of the SUNSYS PCS
2
’s top panel
for maintenance.