5. ENVIRONMENTAL REQUIREMENTS AND HANDLING
5.1 ENVIRONMENTAL REQUIREMENTS
Install the unit in an equipment room.
The room must be:
• of a suitable size;
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability. The unit is designed for indoor rooms only.
For information regarding ambient temperature, dimensions and weights refer to 'Technical specifications' chapter.
To position the unit correctly see the diagrams below.
ROOM POSITIONING
Top view
Free area
SUNSYS
PCS
2
SUNSYS
PCS
2
SUNSYS
PCS
2
30 cm
1.5 m
SPACING-AIR FREE
To ensure the full unit power up to 40°C ambient temperature, observe the following minimum distances:
- rear space: 30 cm.
- above space: 45 cm.
This distance can be reduced depending on:
• the maximum ambient temperature accepted (Full load conditions).
Distance from the rear wall
Space above the top panel
Ambient temperature
30 cm
45 cm
40 °C
25 cm
35 °C
20 cm
45 cm
35 °C
25 cm
30 °C
10 cm
45 cm
25 °C
25 cm