STATYS
Jbus / Modbus serial link
14 OPMSTAJB0810-GB_01
IT
ALIANOENGLISH
8. 6.
p
ermISSIonS
tableS
:
StartIng
addreSS
0
x
0150, 1
wordS
CODE
DESCRIPTION
BIT
ADDRESS
Remarks
P00
Close SSP
0
0x0150
P01
Close SSA
1
0x0150
P02
Close SS1
2
0x0150
P03
Close SS2
3
0x0150
P04
S1 is preferred source
4
0x0150
P05
S2 is preferred source
5
0x0150
P06
6
0x0150
P07
Lock transfer ext.
7
0x0150
P08
Unlock transfer ext.
8
0x0150
P09
9
0x0150
P10
Allows remote controls
10
0x0150
P11
Forbid remote controls
11
0x0150
P12
Trsf Asynchro Forced
12
0x0150
P13
Trsf OnFly Abort
13
0x0150
P14
14
0x0150
P15
Load off
15
0x0150
8. 7.
c
ommandS
tableS
:
StartIng
addreSS
0
x
0190, w
rIte
1
wordS
To modify a parameter, write 1 in the corresponding bit.
CODE
DESCRIPTION
BIT to write ADDRESS
Remarks
C00
Close SSP
0
0x0190
C01
Close SSA
1
0x0190
C02
Close SS1
2
0x0190
C03
Close SS2
3
0x0190
C04
S1 is preferred source
4
0x0190
C05
S2 is preferred source
5
0x0190
C06
6
0x0190
C07
Lock transfer ext.
7
0x0190
C08
Unlock transfer ext.
8
0x0190
C09
9
0x0190
C10
Allows remote controls
10
0x0190
C11
Forbid remote controls
11
0x0190
C12
Force Asynchro Trsf
12
0x0190
C13
Abort OnFly Trsf
13
0x0190
C14
14
0x0190
C15
Load off
15
0x0190
It is advised to modify only one parameter per request.