NETYS RT 

1.1-3.3 kVA - Ref.: IOMNETRTXX0B-EN  01

10.6.3 Customized con

fi

 guration for relay and/or input contacts

Connect 

Tx

 to pin 2, 

Rx

 to pin 3 and 

GND-C

 to pin 5 of the computer’s RS232 port.

In Windows, start the Hyper-Terminal application and proceed to open the specified COM port.

Set the following properties: Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.

10. COMMUNICATION

• Configuration.

Press <Enter> to display the main menu of the relay card.

1. Press ‘1’ to configure the alarms relative to contacts 

R1~R6 

(Customize Output Relay)

.

  This menu can be used to assign a customized alarm indica-

tion to contacts 

R1~R6

.

  Having completed the configuration, shift 

SW2

 to the ON 

position to activate the settings.  The default settings can be 
restored by setting 

SW2

 to OFF.

2. Press ‘2’ to configure the 

input

 signal.

  The input signal can be used either to shut down the UPS or to 

test the batteries. The delay preceding shutdown of the UPS 
can be set up to 9999 seconds maximum. 

3. Press ‘3’ to configure NO or NC operation of each relay.

 Shift 

SW2

 to the ON position to activate the settings.

  If SW2 is returned to the OFF position, SW1 can be used to 

check the NO or NC position of all the relays.

4. Press ‘0’ to end the configuration session. The system will 

prompt you to save the new settings.  

  Press ‘Y’ to save, ‘N’ to cancel.

UPS Relay Card 

Firmware Version: Relay Card V1.4 
[1] . Customize Output Relay
[2] . Con

fi

 gure Input Signal

[3] . Customize Normal Open or Normal Close
[0] . Quit

Please Enter Your Choice  

>

Con

fi

 gure Input Signal 

[1] . Act as Shutdown or Test: Shutdown
[2] . Input Signal Con

fi

 rm 3 Seconds

[3] . Delay Before Shutdown 30 Seconds
[0] . Back to Previous Menu

Please Enter Your Choice  >

Customize Output Relay 

 Relay Selected Event
[1] . Relay 1:  Summary Alarm
[2] . Relay 2:  Power Fail
[3] . Relay 3:  Battery Low
[4] . Relay 4:  On by-pass
[5] . Relay 5:  Overload
[6] . Relay 6:  Overtemperature
[0] . Back to Previous Menu

Please Enter Your Choice  >

Customize Output Relay 

 

Relay Selected Event
[1] . Relay 1:  Normal Close
[2] . Relay 2:  Normal Open
[3] . Relay 3:  Normal Close
[4] . Relay 4:  Normal Open
[5] . Relay 5:  Normal Close
[6] . Relay 6:  Normal Open
[0] . Back to Previous Menu

Please Enter Your Choice  >

Содержание NRT2-U1100

Страница 1: ...al de instalaci n y uso ES Asennus ja k ytt ohje FI Manuel d installation et d utilisation FR Manuale di installazione e uso IT MK Installatie en bedieningshandleiding NL Dokumentacja Techniczno Rucho...

Страница 2: ...ve humidity temperature poor ventilation etc tampering or any unauthorised repair work During the warranty period SOCOMEC reserves the right to decide whether the product should be repaired or whether...

Страница 3: ...ERY EXTENSION 14 5 1 SAFETY WARNINGS 14 5 2 CONNECTION OF BATTERY EXTENSION 14 6 MIMIC PANEL 16 7 OPERATING MODES 17 7 1 BATTERY RECHARGE 17 7 2 SWITCHING THE NETYS RT ON AND OFF 17 7 3 BATTERY TEST 1...

Страница 4: ...ocket with protective earth connection It is manda tory the use of the provided cable ref CONNECTIONS This earth connection will assure also the safety bonding for the appliances powered by the UPS Th...

Страница 5: ...egulations in the country of purchase CAUTION IF DAMAGED NON SPILLABLE BATTERIES Torn crushed or damaged packaging which exposes the contents should be set aside in an isolated area and inspected by a...

Страница 6: ...equency settings are correct for the mains power supply at the installation site Details for the UPS will be found on the data plate affixed to the rear panel The mains supply socket must be protected...

Страница 7: ...RWNETRT2 XX 2 INSTALLATION 2 3 VERTICAL INSTALLATION 4 4 2 1 3 031 DRWNETRT XX 059 DRWNETRT XX 208DRWNETRT2 XX 207DRWNETRT2 XX 026 DRWNETRT2 XX 027 DRWNETRT2 XX UPS Installation with 1 battery extensi...

Страница 8: ...8 NETYS RT 1 1 3 3 kVA Ref IOMNETRTXX0B EN 01 2 3 1 UPS Installation with multiple battery extensions 2 INSTALLATION 4 2 1 3 036 DRWNETRT XX 033 DRWNETRT XX 059 DRWNETRT XX 028 DRWNETRT XX...

Страница 9: ...1 1 3 3 kVA Ref IOMNETRTXX0B EN 01 ENGLISH 2 INSTALLATION 2 4 HORIZONTAL INSTALLATION ON RACK 2 4 1 Rotation of mimic pannel 038 DRWNETRT XX 043 DRWNETRT XX 042 DRWNETRT XX 041 DRWNETRT XX 039 DRWNETR...

Страница 10: ...10 NETYS RT 1 1 3 3 kVA Ref IOMNETRTXX0B EN 01 2 4 2 Fitting rack brackets 2 INSTALLATION 044 DRWNETRT XX 046 DRWNETRT XX 1 2 3 045 DRWNETRT XX...

Страница 11: ...ON MAX 100 kg MAX 100 kg MAX 100 kg MAX 100 kg 3 3 4 060 DRWNETRT XX 047 DRWNETRT XX 061 DRWNETRT XX 2 1 2 4 3 Fixing to rack 1 Adapt the length of the tracks to fit the rack 2 Secure the wing nuts 3...

Страница 12: ...EPO Emergency Power Off E RS232 serial connector JBUS protocol F USB socket G Input thermal protection H Slot for optional communication cards I Output socket full power L Power output sockets LS1 pr...

Страница 13: ...ENGLISH Connection to the mains power supply and to the load s must be made using cables of suitable cross section in accordance with current standards 4 CONNECTIONS 1100 VA 3300 VA 1700 VA 2200 VA 0...

Страница 14: ...the battery storage unit 5 2 CONNECTION OF BATTERY EXTENSION WARNING Before commencing any operation make certain that the voltages of the UPS battery and of the battery extension are the same 1 1 kVA...

Страница 15: ...BATTERY EXTENSION 1100 VA 1700 VA 2200 VA 3300 VA Connection of multiple batteries Max EBM with additional charger NRT2 U1100 2 NRT2 U1700 2 up to 10 NRT2 U2200 2 up to 10 NRT2 U3300 2 up to 10 Switc...

Страница 16: ...PANEL E A B Legend A LED Green Normal operation Yellow Alarm Red Load not supplied B LCD display C Scroll button D On button E Off button D C Output present Load Level 5 step Battery status Overload...

Страница 17: ...ormal operation 7 2 SWITCHING THE UPS ON AND OFF 7 2 1 Switching on with mains present 7 2 2 Switching on with no mains power Cold Start Power up all loads one at a time Power up all loads one at a ti...

Страница 18: ...Battery mode the buzzer 7 OPERATING MODES UPS is off but battery remains on charge Shut down all loads one at a time Switch off mains power to shut down completely 10 sec 7 2 3 2 UPS off 7 2 4 2 1 sho...

Страница 19: ...second 1 Short every seconds 8 2 Overload with Bypass 1 Short every seconds 8 3 Overload without Bypass 021 DRWNETRT2 XX 011 DRWNETRT2 XX 014 DRWNETRT2 XX 204 DRWNETRT2 XX 023 DRWNETRT2 XX 019 DRWNETR...

Страница 20: ...t frequency Hz 50 60 50 Bypass voltage tolerance window on nominal output 0 5 10 15 20 HI as input mains 10 9 2 1 9 2 2 Press 0 1 sec to set the value Press 0 1 sec to change the value 9 2 3 Press 0 1...

Страница 21: ...load value Allow to set the overload alarm level of nominal power 5 10 15 105 105 Enable frequency converter mode on off off Enable Green function if enabled this function switch off the UPS at the fo...

Страница 22: ...and Mac OS X operating systems 10 4 EPO PORT The EPO emergency power off port allows the user to shut down the UPS in online mode or in battery mode when an emergency occurs Use a RJ11 cable not provi...

Страница 23: ...5 R6 Input Tx Rx GND C SW1 SW2 GND R R1 General alarm R2 No mains R3 Battery low R4 On by pass R5 Overload R6 Overtemperature 10 6 1 1 10 6 1 3 10 6 1 2 SW1 SW2 relay contact OFF OFF NO ON OFF NC GND...

Страница 24: ...9999 seconds maximum 3 Press 3 to configure NO or NC operation of each relay Shift SW2 to the ON position to activate the settings If SW2 is returned to the OFF position SW1 can be used to check the N...

Страница 25: ...UPS internal batteries not completely charged Recharge the batteries for a minimum of 8 hours UPS in overload Disconnect non essential loads Depleted batteries The batteries will degrade quickly if u...

Страница 26: ...r OFF button Check that all emergency condition has been solved and restart the UPS Sd1 RPO shutdown Nothing to do UPS is off due to software scheduled power off UPS restart automatically at the progr...

Страница 27: ...n Linear Load 1 6 Linear Load Converter mode derating 50 70 Batteries Type Maintenance free sealed lead life expectancy 3 5 years Voltage V 24 48 48 72 Typical backup 2 min 8 12 8 10 Recharge time Hou...

Страница 28: ...386 1 5807 860 Fax 386 1 561 11 73 info si socomec com SPAIN 836 3RZHU RQWURO QHUJ IILFLHQF Solar Tel 34 93 540 75 75 Fax 34 93 540 75 76 info es socomec com UNITED KINGDOM Power Control Energy Effici...

Отзывы: