15
NETYS PR RACK 1U
- Ref.: IOMNETPRXX01-GB 02
ENGLISH
10. TROUBLESHOOTING
This section examines some of most likely problems that can compromise correct operation of the UPS, attempting to solve them
and identifying the possible causes and remedies.
WARNING!
The UPS internally generates hazardous electrical voltages.
All maintenance must be performed solely and exclusively by authorized personnel.
If you have difficulty in getting the UPS to work, the reason may be among those listed below. For any other problem, you are advised
to get in touch with your dealer or service organisation directly.
For quick and effective action, when you call it is important to give precise details of the defect, the model number and the manufac-
turing serial number that can be found on the conformance and inspection certificate or on the data plate on the bottom of the UPS.
NOTE: the UPS has an audible alarm feature to alert you of potential power problems. Use Table 8 to determine and resolve the
UPS alarms and conditions.
10.1. SILENCING AN AUDIBLE ALARM
Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition (see Table 8). To
silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing.
10.2. TROUBLESHOOTING
Legend:
= Unlit
= Lit
= Flashing
Alarm or Condition
Possible Cause
Action
The
indicator is not on; the
UPS does not start.
The power cord is not
connected correctly.
Check the power cord connections.
The UPS is in Standby mode.
Press and hold the button until you hear the UPS
beep (approximately two seconds) to supply power to the
connected equipment.
The wall outlet is faulty.
Replace the input fuse with another of the same type or
reset the automatic switch.
The UPS operates in Battery
mode only, even though normal
utility power is present.
The input circuit protector is
open (230V models only).
Save your work and turn off your equipment. Turn off the
UPS. Reduce the load, then press the input circuit protec-
tor on the UPS rear panel.
The UPS does not provide the
expected backup time.
The batteries need charging
or service.
Plug the UPS into a power outlet for 24 hours to charge
the battery. Press the
button; if the alarm beeps, see
"Replacing Batteries" on page 40 to replace the battery.
During extended power outages, turn off the UPS after
saving your work and shutting down your computer to
conserve battery power.
Normal operation.
None. The UPS is operating in Normal mode and automa-
tically provides consistent voltage with the Buck and Boost
feature. Power is available to the load segments as indica-
ted by Load 1 (Green) and Load 2 (Green).
1 beep every 4 seconds.
The UPS is on battery due to
a utility failure.
The UPS is powering your equipment with battery power.
Prepare your equipment for shutdown. If this is an exten-
ded power outage, save your work and turn off your
equipment to conserve battery power.
1 beep every 2 seconds.
The battery is running low.
Two minutes or less of battery power remains (depending
on load configuration and battery charge).
Save your work and turn off your equipment. The alarm
cannot be silenced.