66
EN
MASTERYS GP4 60-160 kVA - Ref.: IOMMASGPXX07-EN 05
A035
RECTIFIER INPUT SUPPLY NOT OK
The input mains supply is out of tolerance. Verify that the input
voltage and frequency are within the UPS ratings.
A037
CHARGER CRITICAL ALARM
There is a problem with the battery charger. Please contact the
Service Dept.
A038
CHARGER PREVENTIVE ALARM
Battery charger was blocked by a critical alarm, or Battery
Voltage is too low after 16 hours of charging.
A040
INVERTER CRITICAL ALARM
There is a problem with the inverter. Please contact the Service
Dept.
A041
INVERTER PREVENTIVE ALARM
There is a non-critical problem with the inverter. Check the fans
are working properly. Please contact the Service Dept.
A043
INVERTER IMMINENT STOP
Imminent redundancy was lost due to overload, unit imminent
stop, etc.
A046
PARALLEL BOARD CRITICAL
ALARM
There is a problem with the Parallel Board. Check the PowerLink
connections, otherwise, please contact the Service Dept.
A047
PARALLEL BOARD PREVENTIVE
ALARM
There is a non-critical problem with the Parallel Board. Check the
Power Link connections, otherwise, please contact the Service
Dept.
A048
BYPASS CRITICAL ALARM
There is a problem with the bypass. Please contact the Service
Dept.
A049
BYPASS PREVENTIVE ALARM
There is a non-critical problem with the bypass. Please contact
the Service Dept.
A050
BYPASS INPUT SUPPLY NOT OK
The auxiliary supply is out of tolerance. Verify that the input volt-
age and frequency are within the UPS ratings.
A051
PHASE ROTATION FAULT
The auxiliary mains is not connected properly. Please check
phase connection order is correct.
A052
BYPASS BACK-FEED DETECTION
There is a backfeed problem with the bypass. Please contact the
Service Dept.
A054
FAN FAILURE
Fan Failure can generate overheating. Please contact the Service
Dept.
A055
ACS ALARM
Communication between ACS and Inverter is lost.
A056
MAINTENANCE BYPASS ALARM
Output and Maintenance ByPass switches are closed at the
same time.
A057
INTERNAL BACKFEED DETECTION
There is a backfeed problem with the rectifier. Please contact the
Service Dept.
A059
UPS POWER OFF
The UPO emergency input on ADC+SL has been activated.
A060
WRONG CONFIGURATION
UPS is not configured properly. Please check the configurations
or contact the Service Dept.
A061
INTERNAL / COMMUNICATION
FAILURE
The internal communication between UPS sub-system is lost.
Please contact the Service Dept.
A062
OPTION BOARD ALARM
There is a communication problem with the option board. Please
contact the Service Dept.
A063
SPARE PARTS NOT COMPATIBLE
Spare parts are not registered on the UPS or are not compatible.
12.2 System status
S002
LOAD SUPPLIED BY AUTOMATIC
BYPASS
Load on bypass, supplied by auxiliary mains. Load not protected.
S018
EXTERNAL MAINTENANCE BYPASS
CLOSED
External maintenance bypass input is closed.
S023
GEN SET ON
Genset input.
S064
CARD IN SLOT 1 PRESENT
S065
CARD IN SLOT 2 PRESENT
S066
CARD IN SLOT 3 PRESENT
Содержание MASTERYS GP4 Series
Страница 1: ...MASTERYS GP4 60 160 kVA EN INSTALLATION AND OPERATING MANUAL www socomec com...
Страница 71: ......