55
EN
MASTERYS GP4 60-160 kVA - Ref.: IOMMASGPXX07-EN 05
Configuration 1
STANDARD configuration (default)
IN/OUT
DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE
STATE
IN1
UPS POWER OFF
1
Command sent to UPS
(2)
Close to activate
Normally open
IN2
GEN SET ON
1
Activate S023 status
Open to activate
Normally closed
IN3
INSULATION FAULT
10
Activate A026
Open to activate
Normally closed
RELAY 1
GENERAL ALARM
10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2
OPERATING ON BATTERY
30
Relating to A019
Normally open
RELAY 3
END OF BACK-UP TIME
10
Relating to A017
Normally open
IMMINENT STOP
10
Relating to A000
Normally open
RELAY 4
LOAD SUPPLIED BY AUTO-
MATIC BYPASS
10
Relating to S002
Normally open
Configuration 2
OPTIONS SUPERVISOR configuration
IN/OUT
DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE
STATE
IN1
UPS POWER OFF
1
Command sent to UPS
(2)
Close to activate
Normally open
IN2
FAN FAILURE
10
Activate A054
Close to activate
Normally open
IN3
BATTERY DISCONNECTED
10
Activate A016
Open to activate
Normally closed
RELAY 1
GENERAL ALARM
10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2
OPERATING ON BATTERY
30
Relating to A019
Normally open
RELAY 3
REDUNDANCY LOST
10
Relating to A006
Normally open
RELAY 4
BATTERY DISCONNECTED
1
Relating to A016
Normally open
Configuration 3
SAFETY configuration
IN/OUT
DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE
STATE
IN1
UPS POWER OFF
1
Command sent to UPS
(2)
Close to activate
Normally open
IN2
INSULATION FAULT
1
Activate A026
Open to activate
Normally closed
IN3
CHARGER DISABLE/ENABLE
10
Command sent to UPS
(2)
Open to activate
Normally closed
RELAY 1
GENERAL ALARM
10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2
UPS POWER OFF
1
Relating to A059
Normally open
RELAY 3
END OF BACK-UP TIME
10
Relating to A017
Normally open
IMMINENT STOP
10
Relating to A000
Normally open
RELAY 4
INSULATION FAULT
1
Relating to A026
Normally open
Configuration 4
ENVIRONMENTAL configuration
IN/OUT
DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE
STATE
IN1
UPS POWER OFF
1
Command sent to UPS
(2)
Close to activate
Normally open
IN2
PROGRAMMABLE ALARM
10
Activate A064
Open to activate
Normally closed
IN3
BATTERY TEMPERATURE
ALARM
10
Activate A020
Open to activate
Normally closed
RELAY 1
GENERAL ALARM
10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2
BATTERY TEMPERATURE
ALARM
10
Relating to A020
Normally open
RELAY 3
REDUNDANCY LOST
10
Relating to A006 and A001
Normally open
RELAY 4
PROGRAMMABLE ALARM
10
Relating to A064
Normally open
Configuration 5
EXTERNAL MAINTENANCE BYPASS configuration
IN/OUT
DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE
STATE
IN1
UPS POWER OFF
1
Command sent to UPS
(2)
Close to activate
Normally open
IN2
GEN SET ON
1
Activate S023 status
Open to activate
Normally closed
IN3
EXTERNAL MAINTENANCE
BYPASS CLOSED
10
Activate S018 status
Open to activate
Normally closed
RELAY 1
GENERAL ALARM
10
(NC1 or NO1 position can be chosen)
Relating to A015
Normally open/closed
RELAY 2
OPERATING ON BATTERY
30
Relating to A019
Normally open
RELAY 3
END OF BACK-UP TIME
10
Relating to A017
Normally open
IMMINENT STOP
10
Relating to A000
Normally open
RELAY 4
LOAD SUPPLIED BY AUTO-
MATIC BYPASS
10
Relating to S002
Normally open
1. The acronyms mentioned are linked to MODBUS table (Snnn=Status/Annn=Alarm).
2. A self-locking emergency push button must be used for the UPS Power Off input.
Note: custom configuration is also available. For more information contact Socomec.