33
CPSS Emergency MASTERYS EM
10 to 80 kVA - Ref.: IOMMASELXX03-GB 00
10.3-1
COMMUTATION confi guration
DIP1: ON - DIP2: ON
IN/OUT
Description
Filter level
OUT 1
General Alarm
2
OUT 2
Battery discarging
3
OUT 3
Battery low & shutdown in progress
2
OUT 4
UPS on bypass
2
IN 1
(1)
ESD
1
IN 2
Powered by generator
1
IN 3
(2)
External alarm A40
1
POWER SAFE confi guration
DIP1: ON - DIP2: OFF
IN/OUT
Description
Filter level
OUT 1
Internal failure
2
OUT 2
Battery discharging
2
OUT 3
Battery charger fault
2
OUT 4
External alarm A40
2
IN 1
(1)
ESD
1
IN 2
External alarm A38
2
IN 3
(2)
External alarm A40
2
EMERGENCY LIGHT confi guration (default)
DIP1: OFF - DIP2: OFF
IN/OUT
Description
Filter level
OUT 1
ON MODE
1
OUT 2
Battery discharging
2
OUT 3
Interference and faults from the system
2
OUT 4
Battery charger fault
2
IN 1
(1)
ESD
1
IN 2
External alarm A38
2
IN 3
(2)
Isolation controller
2
(1) If the external ESD button is not used always insert a jumper to short circuit input IN 1.
(2) On ADC with temperature sensor is used as input dedicated to the external battery temperature probe
The fi lter level indicates the activation delay: 1 immediate activation (1 second minimum communication time), 2 10 s delay, 3 30 s delay.
SECURITY confi guration
DIP1: OFF - DIP2: ON
IN/OUT
Description
Filter level
OUT 1
General Alarm
2
OUT 2
ESD active
1
OUT 3
Battery low & shutdown in progress
2
OUT 4
ESD active
1
IN 1
(1)
ESD
1
IN 2
External alarm A39
2
IN 3
(2)
External alarm A40
2
OUT2
IN3
OUT3
OUT1
IN1
IN2
OUT4
10.3. ADC CARD
To be installed in one of the two slots available, these cards can be used to manage up to four normally closed or normally open
outputs, and up to three digital inputs in confi gurable mode. If more than one ADC card is used simultaneously, the dip switch
confi gurations must be diff erent. Secure the card with the appropriate screws.
This card can be confi gured to control up to four outputs that can be set as normally closed or normally open and up to three digital in-
puts. The card is inserted in one of two slots provided. Up to four operating modes can be selected using the two DIP switches 1 or 2.
• Electrical data
- Permitted Nominal current and voltage of NO or NC contacts: 2 A 250 Vac depending on the terminal used.
- Inputs are activated on loop closing.
• Connection of the generator
If your system uses a generator connect the ‘generator set ready’ no-potential contact to connector IN 2 on the optional ADC
card confi gured in standard or power safe mode. This automatically extends the voltage and frequency value range when power
is supplied by the generator set.
• External ESD connection
A remote emergency shutdown system (ESD) can be installed by means of the optional ADC card. Connect a normally closed
zero-potential contact to terminals IN1+ and IN1- of the ADC card.
10. STANDARD FEATURES AND OPTIONS
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK