3 UNPACKING AND INSTALLATION
3.1 ENVIRONMENTAL
REQUIREMENTS FOR INSTALLATION
Install the UPS after first checking the following:
UPS-ENTERPRISE has been designed for use in closed environments.
Place the UPS on a flat and stable surface, in a ventilated environment away from heat sources and
exposure to direct sunlight.
Keep ambient temperature between 0°C and 40°C and humidity less than 90% (non-condensing); the best
temperature to guarantee longest possible battery life is 15-20°C.
Ensure that the environment that the UPS will be installed in is not dusty, and leave a space of at least 20
cm around it to allow for adequate ventilation and access to the rear panel.
Make sure not to set the UPS or any other heavy object on the cables.
Check that the voltage and frequency preset for operation is right for your electrical power supply. The UPS
data can be read on the plate on the rear panel.
For the RS232 serial connection or with a LAN network, use only the manufacturer-supplied cables and
accessories.
In case of RK models for installation in 19” standardized cabinets, the lateral brackets supplied must be
mounted.
The pictures that follow illustrate the assembly depending on the configuration.
ENT-RK10
ENT-RK15 / RK20
L
WARNING
Extract the UPS or the battery module and remove all the parts from the pack. It is strongly recommended to
keep the packaging materials, which have been designed for safe shipping in cases where the unit has to be
shipped back for maintenance.