CONFIGURATION AND START UP
Q
SECTION 1
10
4 CONFIGURATION AND START-UP
4.1 CONFIGURATION OF THE OUTPUT VOLTAGE/BATTERY EXPANSIONS
L
WARNING
The factory configuration is for operation with output voltage of 230V, without additional battery
expansions.
For normal uses with standard back-up, no configuration work is required.
To enter configuration mode, put the “UPS in bypass” by pressing the OFF button (if switched off, simply insert
the mains power plus):
1. Press both buttons together for 3 seconds until a beep is heard.
2. In configuration mode, the battery LED bar will be flashing.
3. If no action is taken within 10 seconds, the UPS exits from configuration mode.
4. Proceed with configuration by pressing the “OFF” button until the desired configuration is obtained, displayed
as in the table that follows:
The battery LED bar stops flashing and the LEDs indicate the
number of battery expansions included
:
Display
Selection
Total battery capacity
Physical appearance
0 expansions (default)
1 string
UPS only
1 expansion
3 strings
UPS + 1 battery cabinet
2 expansions
5 strings
UPS + 2 battery cabinets
After configuration of the battery expansion, wait for 10 seconds to automatically exit from the setting procedure.
If you want to configure the 230V output voltage (default) or 220V or 240V, then press the buttons again
simultaneously for 3 seconds, before exiting from setting mode (within 10 seconds).
In output voltage setting mode, as well as the battery LED bar, the no-break output LED also flashes.
For configuration of the
voltage,
use the same arrangements as for the battery expansions with the “OFF”
button for selection of the desired value, as shown in the table that follows.
Display Selection
220V
230V (default)
240V
After completing the configuration procedures, it is recommended to switch the UPS off; the new parameters will
have effect the next time it is switched on.
4.2 Power Share Configuration (1500 / 2000VA version only)
Functionality of the Power Share sockets can be configured through the software (Net-Vision/Uni Vision).
The purpose of this group of extra sockets is, generally speaking, to feed part of the users (those with low
priority) to be able to exclude them in critical situations and leave full availability of power supply to the privileged
users connected to the main sockets.
Possible configurations: the Power Share outlet is disconnected in case of:
•
(Default) Overload on the output with mains line up or load greater than 95% in battery operation.
•
Residual battery capacity < XX % (user-selectable through the software)
•
Residual battery back-up time < di XX min (user-selectable through the software)
•
Emergency Lighting operation (user-selectable through the software)
Emergency Lighting means activating the Power Share sockets only when the mains line is down; this is
a contrary logic function, but one which is useful for activating an emergency lights line when the mains
line is down without the need for additional circuitry.