CONFIGURATION AND START UP

 

 

Q

   

SECTION 1   

 

10 

 

4   CONFIGURATION AND START-UP 

4.1  CONFIGURATION OF THE OUTPUT VOLTAGE/BATTERY EXPANSIONS 

L

 

WARNING

 

The factory configuration is for operation with output voltage of 230V, without additional battery 
expansions. 

For normal uses with standard back-up, no configuration work is required.

 

 

To enter configuration mode, put the “UPS in bypass” by pressing the OFF button (if switched off, simply insert 
the mains power plus): 
1.  Press both buttons together for 3 seconds until a beep is heard. 
2.  In configuration mode, the battery LED bar will be flashing. 
3.  If no action is taken within 10 seconds, the UPS exits from configuration mode. 
4.  Proceed with configuration by pressing the “OFF” button until the desired configuration is obtained, displayed 

as in the table that follows: 

 

The battery LED bar stops flashing and the LEDs indicate the 

number of battery expansions included

 

Display 

Selection 

Total battery capacity 

Physical appearance 

 

0 expansions (default) 

1 string 

UPS only 

 

1 expansion  

3 strings 

UPS + 1 battery cabinet 

 

2 expansions  

5 strings 

UPS + 2 battery cabinets 

 
After configuration of the battery expansion, wait for 10 seconds to automatically exit from the setting procedure. 
 
If you want to configure the 230V output voltage (default) or 220V or 240V, then press the buttons again 
simultaneously for 3 seconds, before exiting from setting mode (within 10 seconds). 
In output voltage setting mode, as well as the battery LED bar, the no-break output LED also flashes. 
For configuration of the 

voltage, 

use the same arrangements as for the battery expansions with the “OFF” 

button for selection of the desired value, as shown in the table that follows. 
 

Display Selection 

 

220V  

 

230V (default) 

 

240V 

 
After completing the configuration procedures, it is recommended to switch the UPS off; the new parameters will 
have effect the next time it is switched on. 

4.2  Power Share Configuration (1500 / 2000VA version only) 

Functionality of the Power Share sockets can be configured through the software (Net-Vision/Uni Vision). 
The purpose of this group of extra sockets is, generally speaking, to feed part of the users (those with low 
priority) to be able to exclude them in critical situations and leave full availability of power supply to the privileged 
users connected to the main sockets. 
 
Possible configurations: the Power Share outlet is disconnected in case of: 

 

(Default) Overload on the output with mains line up or load greater than 95% in battery operation. 

 

Residual battery capacity < XX % (user-selectable through the software) 

 

Residual battery back-up time < di XX min (user-selectable through the software) 

 

Emergency Lighting operation (user-selectable through the software)  
Emergency Lighting means activating the Power Share sockets only when the mains line is down; this is 
a contrary logic function, but one which is useful for activating an emergency lights line when the mains 
line is down without the need for additional circuitry. 

Содержание ENT-RK10

Страница 1: ...UPS ENTERPRISE 800 2000 VA PRODUCT MANUAL...

Страница 2: ......

Страница 3: ...3 2 3 Putting an external battery expansion into operation 9 4 CONFIGURATION AND START UP 10 4 1 CONFIGURATION OF THE OUTPUT VOLTAGE BATTERY EXPANSIONS 10 4 2 Power Share Configuration 2000VA version...

Страница 4: ...notification of the malfunction if it is not possible to provide proof of purchase the serial number and date of production will be used to calculate expiry of the warranty which may lead to a reduct...

Страница 5: ...ppropriate procedure When assembling and replacing the battery the UPS should always be switched off and disconnected from the mains power supply The UPS contains an internal power source which is the...

Страница 6: ...ed via a first AC DC conversion followed by a DC AC conversion in order to provide the consumer a stable waveform that is exempt of noise or distortions and therefore completely independent of the inp...

Страница 7: ...e buzzer reset alarms OFF Off button inverter OFF LED 1 Battery capacity LED bar LED 2 GREEN Mains up and regular LED 3 YELLOW Auxiliary mains present and regular bypass line LED 4 RED General alarm s...

Страница 8: ...ow for adequate ventilation and access to the rear panel Make sure not to set the UPS or any other heavy object on the cables Check that the voltage and frequency preset for operation is right for you...

Страница 9: ...e standards in force A distribution panel must be set up if there is not one already which can be used to isolate the mains upstream of the UPS This panel must have an automatic switch of sufficient c...

Страница 10: ...ure that the safety switch on the battery expansion is in the OFF position during the connection steps Set the battery expansion unit beside the UPS on the side that does not have the air vents Connec...

Страница 11: ...mode within 10 seconds In output voltage setting mode as well as the battery LED bar the no break output LED also flashes For configuration of the voltage use the same arrangements as for the battery...

Страница 12: ...lication is powered by the UPS and continuous power is guaranteed If the UPS is switched on with mains absent follow the same procedure as described above and after the self test the UPS will go into...

Страница 13: ...no longer be muted It is recommended to close down applications manually if the automatic shutdown procedure has not been activated via the specific software installed on the computer WARNING your ap...

Страница 14: ...ation of performance 5 1 4 Switching the UPS off Partial switching off with mains present Pressing the OFF key for 2 sec in normal operation with mains present activates the partial switching off of t...

Страница 15: ...ions on the leading operating systems based on JSC Java Shutdown Client Net Vision Web SNMP manager for control via LAN with TCP IP protocol and remote shutdown management the relay card with 3 zero p...

Страница 16: ...ica Gestione Rel R1 R2 R3 Rel Uscite Rel I1 Ottici Ingresso 9 PIN The maximum voltage that can be applied to the contacts is 60Vdc and the maximum current is 500mA Pin DB 9 Signals NC NO JUMPERS 4 Gen...

Страница 17: ...atic by pass Voltage selected 15 Overload with mains present 130 for 10 seconds AC AC efficiency 88 Crest factor 3 1 Reference normatives Standard European UPS standard EN50091 and CE marking Safety E...

Страница 18: ...ted Insert the main switch Mains voltage is missing Have an electrician check the mains The MAINS LED does not come on the acoustic alarm sounds at intervals Fuse on the input faulty Replace the fuse...

Страница 19: ...Q VIEW SECTION 4 800 VA 1000 VA tower front view rear view Battery extension tower 1000 VA rack 19 Battery extension rack 19 Rear view Front Rear view 4 2 1 7 5 6 8 5 6 5 7 1 4 2 5 8 5...

Страница 20: ...VIEW SECTION Q 5 1500 2000 VA tower Battery extension tower rear view rear view 1500 2000 VA rack 19 Rear view Battery extension rack 19 Rear view 2 7 1 6 4 5 3 5 3 4 1 5 5 5 5 6 8 2 7 5...

Страница 21: ...3 Presa di uscita power share 4 Connettore seriale RS232 USB DB9 5 Connettore batteria per espansione esterna 6 Presa di uscita per utenze 7 Presa ingresso rete e fusibile 8 Interruttore batterie 1 L...

Отзывы: