socomec COUNTIS E05 Скачать руководство пользователя страница 4

4

EN

COUNTIS E05/E06 - 545867A - SOCOMEC

2. HAZARDS AND WARNINGS

The term "device" used in the paragraphs below refers to the COUNTIS E05 / E 06.
The  assembly,  use,  servicing  and  maintenance  of  this  equipment  must  only  be  carried  out  by  trained,  qualified 

professionals.

SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual.

2.1. Risk of electrocution, burns or explosion

• 

 Only duly authorised and qualified personnel may work or install/uninstall the device.

• 

 The instructions are valid together with the specific instructions for the device.

• 

 The devices are designed only for their intended purpose as set out in the instructions.

• 

 Only accessories authorised or recommended by SOCOMEC may be used in association with the devices.

• 

 Before proceeding with installation, maintenance, cleaning, disassembly, connection, or maintenance work, 

the device and system must be cut off from the mains to avoid electrocution and damaging the system and 

device.

• 

 These devices are not designed to be repaired by the user.

• 

 For any questions related to the disposal of the device, please contact SOCOMEC.

Failure to comply with the instructions of the device and this safety information can cause bodily injury, 
electric shock, burns, death or damage to property.

2.2. Risk of damaging the unit

To ensure that the unit operates correctly, make sure that:

• 

 The unit is correctly installed.

• 

 There is a maximum voltage at the voltage input terminals of 276 VAC phase-neutral

• 

 The network frequency indicated on the device is observed: 50 or 60 Hz.

• 

There is a maximum current of 40 A at the current input terminals (I1).

Failure to respect these precautions could cause damage to the unit.

2.3. Responsibility

• 

 Assembly, connection and use must be carried out in accordance with the installation standards currently in 

force.

• 

 The unit must be installed in accordance with the rules given in this manual.

• 

 Failure to observe the rules for installing this unit may compromise the device's intrinsic protection.

• 

 The unit must be positioned within an installation which complies with the standards currently in force.

• 

 Any cable which needs to be replaced may only be replaced with a cable having the correct rating.

Содержание COUNTIS E05

Страница 1: ...COUNTIS E05 COUNTIS E06 MID www socomec com en countis e0x Single phase energy meter Direct 40 A M BUS COUNTIS E05 E06 INSTRUCTION MANUAL EN...

Страница 2: ...o the electrical network and to the loads 10 7 MID COMPLIANCE 11 8 COMMUNICATION 12 8 1 General information 12 8 2 Recommendations 12 8 3 Communication structure 12 8 4 Communication tables 12 9 CONFI...

Страница 3: ...3 EN COUNTIS E05 E06 545867A SOCOMEC 1 DOCUMENTATION All documentation on the COUNTIS E05 E06 is available online at www socomec com en countis e0x...

Страница 4: ...igned to be repaired by the user For any questions related to the disposal of the device please contact SOCOMEC Failure to comply with the instructions of the device and this safety information can ca...

Страница 5: ...of these instructions thoroughly before commissioning Check the following points as soon as you receive the package containing the unit The packaging is in good condition The unit has not been damaged...

Страница 6: ...M BUS communication Bus 4 2 Functions Measures and displays total and partial energy Dual tariff management T1 T2 Electrical parameter measurements I U V f Power power factor M Bus communication MID v...

Страница 7: ...ain zone In the case of a Code XX corrupt metrological settings return to Manufacturer 5 Value of the partial meter Flashing meter stopped 6 Active communication 7 Inductive value 8 Imported or export...

Страница 8: ...A Power factor PF Apparent power S kVA Active power P kW Reactive power Q kvar Frequency f Hz Direction of current Logged data Total active reactive energy Ea Er kWh kvarh Total active and reactive e...

Страница 9: ...o the safety instructions section 2 Hazards and warnings page 4 Keep away from electromagnetic interference generator systems Avoid vibrations with accelerations greater than 1 g for frequencies lower...

Страница 10: ...PZ2 10 62 lb in 1 2 Nm max 6 2 Connection to the electrical network and to the loads The COUNTIS E05 E06 are intended for single phase networks with neutral M Bus 2 3 M Bus connection Pulse output 4 5...

Страница 11: ...6 2 Connection to the electrical network and to the loads page 10 Fitting terminal covers After connecting the device ensure that the terminal covers are fitted properly and secured by the plastic se...

Страница 12: ...ded JYSTY Nx2x0 8 mm twisted pair 0 5 mm If the distance of 1000 m is exceeded and or the number of devices is greater than 250 add a repeater to allow additional devices to be connected If there are...

Страница 13: ...nge your communication settings How to browse through the programming mode is described in the following stages Function Where Buttons Press Switch pages within a menu Every page within a menu Realtim...

Страница 14: ...UP menu press for 3 seconds to put the device into programming mode Press to go to the different screens 3s Primary M BUS address Secondary M BUS address Communication speed Reset partial energy to ze...

Страница 15: ...f menu SETUP 3s Primary M BUS address 000 001 249 250 Secondary M BUS address 0 1 99999998 99999999 the address is specific to each device Baudrate 300 2400 9600 Reset energy Ea partial Ea partial Er...

Страница 16: ...ple setting the communication address In SETUP mode see page 15 go to the Primary M BUS address screen Example changing the communication address to 243 3 3 x2 3 x4 3 x3 3 x1 Secondary M BUS address C...

Страница 17: ...mported reactive energy ______________ Tariff 2 Imported active energy ______________ Tariff 2 Imported reactive energy ______________ Total imported active energy ______________ Total exported active...

Страница 18: ...ve energy Tariff 2 Imported reactive energy Total imported active energy description in chapter 10 1 1 Total exported active energy description in chapter 10 1 1 Total imported reactive energy descrip...

Страница 19: ...EC 10 1 1 Detailed view of the partial energy meter Total imported active energy Total imported reactive energy 10 1 2 Starting up the partial energy meter 3 sec 3 sec 3 sec 10 1 3 Stopping the partia...

Страница 20: ...20 EN COUNTIS E05 E06 545867A SOCOMEC 10 1 4 Resetting the partial energy meter to zero 3 sec x1 3 sec...

Страница 21: ...ars if there are connection or malfunction errors 11 1 Malfunction If you see this message Code xx the meter has malfunctioned and must be replaced 12 ASSISTANCE Causes Solutions Device not working Ch...

Страница 22: ...ut consumption 0 5VA max per phase Startup current Ist 20mA Minimum current Imin 0 25A Transition current Itr 0 5A Reference current Iref 5A Permanent overload lmax 40A Intermittent overload 30 Imax f...

Страница 23: ...arh Realtime active power 1 display 4 digit 00 00 99 99 kW Realtime reactive power 1 display 4 digit 00 00 99 99 kvar Realtime voltage 1 display 4 digit 000 0 999 9 V Realtime current 1 display 4 digi...

Страница 24: ...W x H x D mm Modular width of 2 modules DIN 43880 18 x 90 x 70 Installation On DIN rail EN 60715 Connection capacity tightening torque See chapter 6 Connection page 10 Protection index Front IP51 casi...

Страница 25: ...cksum of metrological firmware t 1 Tariff 1 t 2 Tariff 2 tot Total menu SEtuP Setup menu Prl Primary M BUS address SEC Secondary M BUS address bAu Communication speed in bauds bits per second rES ALL...

Страница 26: ...Non contractual document 2016 Socomec SAS All rights reserved 545867A CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com...

Отзывы: