10
EN
COUNTIS E03/E04 - 545865A - SOCOMEC
6. CONNECTION
6.1.
Connecting the COUNTIS E03/04
L
L
N
N
4 5
2
1
3
Fixed / flexible
0.14 mm
2
->
2.5 mm
2
0.27"
/ 6.9 mm
PZ2
4.5 lb.in
/
0.5 Nm max.
Rigid / supple
1.5 mm² ->
6 mm²
0.47"
/ 12 mm
PZ2
10.62 lb.in
/
1.2 Nm max.
6.2. Connection to the electrical network and to the loads
The COUNTIS E03/E04 are intended for single-phase networks with neutral.
Modbus
1: +
2: -
3: NC (not connected). May be used for shielding continuity.
Pulse output
4: -
5: +
Optocoupler pulse outputs
Terminals 4-5 must be supplied with voltage between 5 and 27
VDC (27 mA max)
Network
L: : Phase input
L': : Phase output
N: Neutral connection
L
L
N
N
4 5
L
L’
40A
N
230 VAC 50/60 Hz
2
1
3
NC
-+
COM RS485
MODBUS
-+
2 3