SOCOMEC - Réf. : 875 503D
13
PROGRAMMING
Off load
In order to operate this product correctly,
it must be configured. The micro-
switches are arranged beneath a grey
cover which is removed using a screw-
driver. The assignment of the micro-
switches is shown below.
1
CT
Pul. Network
2 3 4 5 6 7 8
ON
OFF
COUNTIS AT
16 15
17
18
19
20
21
12 13
14
8
5
2
11
9
7
6
4
3
1
1 2 3 4 5 6 7 8
CT RATIO
10
OFF
OFF
OFF
OFF
OFF
40
OFF
ON
OFF
OFF
OFF
CT/5 ratio
1
2
3
4
5
20
ON
OFF
OFF
OFF
OFF
50
ON
ON
OFF
OFF
OFF
60
OFF
OFF
ON
OFF
OFF
75
ON
OFF
ON
OFF
OFF
100
OFF
ON
ON
OFF
OFF
125
ON
ON
ON
OFF
OFF
200
ON
OFF
OFF
ON
OFF
300
ON
ON
OFF
ON
OFF
500
ON
OFF
ON
ON
OFF
750
ON
ON
ON
ON
OFF
1000
ON
OFF
OFF
OFF
ON
1250
ON
ON
OFF
OFF
ON
1750
ON
OFF
ON
OFF
ON
2500
ON
ON
ON
OFF
ON
4000
ON
OFF
OFF
ON
ON
150
OFF
OFF
OFF
ON
OFF
250
OFF
ON
OFF
ON
OFF
400
OFF
OFF
ON
ON
OFF
600
OFF
ON
ON
ON
OFF
800
OFF
OFF
OFF
OFF
ON
1200
OFF
ON
OFF
OFF
ON
1500
OFF
OFF
ON
OFF
ON
2000
OFF
ON
ON
OFF
ON
3000
OFF
OFF
OFF
ON
ON
Note :
Parameter are taken into account when
the instrument is powered
Note:
Factory configuration:
1-2-3-4-5-8 = OFF
6-7 = ON
Pulse values:
100 Wh
OFF
OFF
1 kWh
ON
OFF
Value
6
7
10 kWh
OFF
ON
100 kWh
ON
ON
Network types
Unbalanced 3 or 4 wires
OFF
Balanced 3 or 4 wires
ON
Types
8