MCM-Inst-1.10
Page 11 of 27
○
MeterConfig
= 10 for the CT around L1
○
MeterConfig
= 20 for the CT around L2
○
MeterConfig
= 30 for the CT around L3
●
Single-phase, two-wire, line-to-line, without neutral:
See
●
Single-phase, three-wire, line-to-line, with neutral:
See
3.2.3 Single-Phase, Three-Wire
below for details.
For loads with more than one CT, we recommend keeping all CTs on the same SMB.
3.2.2 Three-Phase, Three-Wire Delta
This service is common in commercial and industrial settings. It does not include a neutral conductor.
Load #1 is three-phase, three-wire, delta, measured with three CTs. Load #2 is three-phase, three-
wire, delta, measured with two CTs. Load #3 is single-phase, line-to-line, and measured with one CT.
V
B
V
C
V
N
V
A
CT2
ADDR+1
ADDR+0
CT1
CT3
CT2 CT1
CT3
Additional Loads
L3 L2 L1
Meter Power
Load #1,
3Ø
Load #2,
3Ø, 2 CTs
Load #3,
1Ø, 1 CT
Earth
Figure 4: Three-Phase Three-Wire Delta
This service supports the following types of loads:
●
Three-phase, three-wire, delta (no neutral):
You may meter this with either three or two CTs.
○
With three CTs wired as shown for load #1 above, use the default
MeterConfig
values:
■
MeterConfig1
= 10
■
MeterConfig2
= 20
■
MeterConfig3
= 30
○
With two CTs wired as shown for load #2 above, use the following
MeterConfig
values:
■
MeterConfig1
= 90
■
MeterConfig2
= 50
●
Single-phase, line-to-line:
You may meter this with one or two CTs.
○
With two CTs, use:
■
MeterConfig
= 10 for any CT around L1