Whilst in manual mode, check the wiring
and if ok power up the product.
LED “Power” Green: ON
/('0DQXHO'HIDXW5HG3URGXFWbQRW
Available): ON
Whi
and
STEP 5
Check
Ensure that the emergency handle is
not inserted in the product and turn
the mode selector to the AUT position.
LED “Power” Green: ON
LED Manuel/Default: OFF
___________________________________________________________
Ensure that the emergenc
STEP 6A
Motorised Operation
To enable control, close contact 312 with 317.
To force the product to 0 position/OFF bridge
the contact 313 with 317.
For contactor logic bridge contact 316 with 317.
To operate: close the contact corresponding to
the desired position.
,PSūPV
maintened
order I
position I
order 0
position 0
order II
position II
Contactor logic
Impulse logic
STEP 6C
Padlocking Mode
(in position O)
3x
Ø 4-8
mm
Ø 0.1
5-0.3
1 in
CONTROL / COMMAND Terminals -
Ensure that the product is in Manual Mode.
CON
STEP 3B
STEP 4
Power Supply Terminal -
Remove the Top cover to access and connect the terminal - Replace the cover before putting in service.
1
2
3
Connect the product with a cable of section of 24 to 16 AWG.
Screw M3 - Tightening torque: min.: 5 lb-in - max. 7 lb-in.
1
2
30
1
30
22
312 313 314 315 316 317
63A 64A 24 14 04 13
CONTROL
OUTPUTS
1
2
Class CC
4A fuse
Spares: Motorisation module
AUT
AUT
AUT
AUT
90
°
90
°
I
II
0
0
STEP 6B
Emergency Manual Operation
AUT
AUT
AUT
AUT
II
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
AUT
Ref. Spare part motorisation
USED FOR ATyS REFERENCE
97095010
100A
2, 3, 4 P
B4
97232010 / 97233010 / 97234010
97095020
200A
2, 3, 4 P
97232020 / 97233020 / 97234020
97095026
260A
2, 3, 4 P
B5
97232026 / 97233026 / 97234026
97095040
400A
2, 3, 4 P
97232040 / 97233040 / 97234040
NOTE: Nominal Aux. Supply Voltage : 208 – 277Vac