Operation
Controller
ATyS
OPERATION
ATyS C20/C30
56
SOCOMEC - Réf. : 532 214 C
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
PRESENTATION
Enter operation mode:
•
Step 1:
press and hold
the “TEST” push button for 5 s
•
Step 2:
enter the operation code (CE) using
navigation push buttons (code 4000)
•
Step 3:
press “validation”
push button
Exit operation mode:
Press and hold the “TEST” push button for 5 s
or automatic exit without action during around
2 min
Navigate in operation mode:
• Press “TEST” push button to access
different features
• Press “validation” push button to activate
required function
OPERATION MODE ARCHITECTURE
No, press
“TEST”
No, press
“TEST”
1
2
1
2
Led “test on load”
is blinking
Led “test off load”
is blinking
Enter: press 5 seconds
Yes, press
“validation”
Yes, press
“validation”
Exit: press 5 seconds
TEST OFF LOAD
Genset start
sequence
TEST ON LOAD
Loss of priority
source sequence
Led “TEST ON LOAD”
is fixed
Led “TEST OFF LOAD”
is fixed
ATYS 432 A GB
This mode allows in manual mode (not padlocked) to start
a test off load. In automatic mode, it allows to start a test,
on or off load.