Limit Switch Setting
Rotate the actuator hand wheel manually to closed position
Using hex wrench, loosen the set screw on the CLOSE limit switch cam
Rotate the CLOSE cam towards CW limit switch lever until the switch “clicks” Tighten the set screw with
hex wrench
Rotate the actuator hand wheel manually to open position
Using hex wrench, loosen the set screw in the “open” limit switch cam
Rotate to “open” cam towards CCW limit switch lever until the switch “clicks” (fig 2)
Tighten set screw with hex wrench