8 | SmithsEP.co.uk | Issue 001 - April 2020
Technical manual Ostro air curtain v201709
www.sonniger.com
8
It is important to note that the minimum distance between the unit and the floor for installation with engine at the bottom is
not less than 100mm. This allows access to the electrical terminal strip and to the water exchanger vent.
Connection of heating medium
The connection of the heating medium to the heat curtain
using G 1/2" threaded connection
s
should be made on the basis of
a design by an authorized designer. If the air curtain is connected to a district heating network without a mixing unit, a water filter is
required.
In case of horizontal and vertical mounting with nozzles at the top, the exchanger is vented through the nozzles. If the device
is mounted vertically with nozzles at the
bottom
to vent the exchanger, use a vent which is located on the exchanger collector on
the engine side.
Connecting the power supply and control system of the curtain
To connect the power supply, control and/or bleed the
Heat
Exchange
r
move the right hand casing as per the diagram
, which is
fastened with the lock to the lower steel housing and the main housing EPP. The lid is disassembled in the direction shown by the
arrows in the figure below. The lid should be grasped in the places indicated in the drawing and should be gradually "released"
from the locks for several mil
l
imetres. Cable entries for power and control cables are located on the inlet grille.
ATTENTION !
The air curtain must be level
.
When it is mounted in a position other than vertical
or horizontal there is a risk of fan damage and unit malfunction
ATTENTION !
Ensure that no connection wire is clamped between the lid and the rest of the
curtains before assembling the lid.
www.sonniger.com
9
Technical manual Ostro air curtain v201709
6. CONTROL PANEL
The curtain control is done by using the COMFORT control panel, which allows to adjust the flow and air temperature. The
control panel should be located outside the curtain airflow zone. Up to 2
air
curtains can be connected to one COMFORT panel.
To install the control panel, unscrew the screw, remove the front cover and panel board, fix the panel to the wall, and replace the
panel and cover (installation instructions and fixing kit are included in the package).
7. DOOR SWITCH
The
(DC)
door switch is an additional element for switching the curtain on/off, depending on the opening of the door. It is designed
for indoor installation. It includes:
Relay cabinet - reed relay switchboard
Reed relay - Reinforcement for door-fitting,
hermetic magnetic switch, consisting of a movable and
fixed element
Scheme of the relay cabinet – reed relay interface
Dimensions of reed relay
Parameters of relay reed switchboard
When installing the door switch, remove the factory-made jumper:
NC-1
for
air
curtain W (curtain with a water heater) / C (curtain without a water heater)
NC-COM
for
air
curtain E (curtain with an electric heater)
Power supply 230V/50Hz
Inductive load relay contact 5(A)
NC magnetic sensor circiut NC
IP66
Description of the COMFORT control panel switches
ON/OFF
-
switching on/off of the machine
I-II-III
-
fan gear switches, COMFORT terminal strip clamps
clamp 8 - high speed III
clamp 7 - middle speed II
clamp 6 - low speed I
HEAT
-
when the room temperature is lower than the set value, the thermostat switches on the fan (W, E, C),
the electric heater (E) and the valve actuator (W); When the set temperature is reached, the fan is switched off,
the valve closes the water flow or the electric heater switches off
FAN
/
COOL
-
not supported function, in th
ese
settings the device does not work