Smith 19A Series Скачать руководство пользователя страница 9

19A SERIES BOILER

INSTALLATION INSTRUCTIONS

19. OWNERS INSTRUCTIONS

A.

For best performance of the boiler, the following

suggestions should be performed by a qualified boiler room
technician, through a regular program of maintenance and
adjustment to obtain the following.

1. Oil burner combustion:  12 to 12 1/2 + % CO2, zero smoke,

smooth lightoff and operation.

Gas burner combustion:  10 to 10 1/2% CO2, 0.02% CO,
smooth lightoff and operation.

2. Keep boiler fireside surface clean. Flue gas temperature

reading above 450°F over boiler room temperature signals
the start of soot accumulation. Inspect at least twice each
year.

3. Steam boiler water condition should be observed. Unstable

water line, system steam hammer indicate dirty water.
Blow-down is recommended. However, the introduction of
excess raw water to a steam boiler can result in the deposit
of scale and inefficient operation of physical damage to
the boiler.

4. Float operated and probe type low water cutoff devices

should be maintained according to the instructions of the
manufacturer.

5. Limit control function should be checked on a regular basis.

6. Flame safeguard controls should be checked regularly.

B.

The products of combustion must be conducted to the

outdoors by means of a metal connector of at least the same
size as the boiler smokehood outlet and a chimney or stub-
stack. The boiler is constructed for pressurized operation
and the burners are selected for operation against a back
pressure of 0.10 ins. w.c. at the boiler outlet. If the actual
conditions cause a back pressure in excess of 0.10 ins. w.c.
at the boiler outlet, consult the Smith Co. for verification of
burner size. If the chimney has the ability to develop excess
draft, a barometric draft control should be installed in the
chimney. Check with the Smith representative for assistance.

18. CLEANING BOILER WATERWAYS

A.

STEAM BOILERS

NOTE

The boiler should be cleaned before connecting system
piping and installing steam trim.

1. Plug unused openings all around the boiler leaving a valved

overflow pipe connected to the safety valve tapping. Also
provide a valved blow-down connection to one of the
bottom tappings.

2. The fuel burning equipment should be installed and made

ready to operate in accordance with the burner instructions.

3. Fill the boiler with water to the middle of the upper port,

adding a boiler cleaning compound, as recommended in
A.S.M.E. Section VI.

4. Fire the boiler for at least one hour at a low rate to

circulated the cleaning compound through the boiler.

5. Blow off surface of boiler water through skimmer connection

or through safety valve opening by feeding clean water
into the boiler through a bottom fill connection.

6. When the water coming off the surface runs clear, shut off

the burner, close the top valve and open the bottom blow-
down valve. If there is a slight steam pressure in the
boiler, it will assist the blow-down.

7. When the sections have cooled after blow-down, flush the

interior of the boiler from the top by introducing water from
a hose through the top port. When the water runs clear,
complete the system piping, install the steam trim and
controls. Fill the boiler with clean water. Heat the boiler
water to at least 180°F to release corrosive gases.

B.

WATER BOILERS

NOTE

The system piping should be completed before cleaning
the boiler.

1. Add an approved boiler compound. Follow the compound

manufacturer's instructions for best results. Fill the system
and vent air wherever necessary.

2. Heat the water to at least 180°F and circulate through all

the piping system. After about one hour, drain the system
thoroughly. Wash the interior of the boiler with a hose
inserted through the top tapping. When blow-down water
runs clean, allow boiler to cool, then fill the system with
clean water.

3. Heat the water up to about 180°F and vent air as necessary

to purge the system. The boiler is now ready to operate.

PAGE 9

Содержание 19A Series

Страница 1: ...motive anti freeze in boiler waterways If necessary to use anti freeze be sure to employ a preparation designed for hydronic heating systems such as ethylene or propylene glycol Water treatment is not recommended This boiler uses gaskets to seal the ports of adjoining sections These gaskets are made of a fluorocarbon elastomer designation FKM marketed under the brand name Viton Consult a water tre...

Страница 2: ...ng Includes Mounting Plate w Observation Glass and Cover PAGE 2 19A SERIES BOILER INSTALLATION INSTRUCTIONS 13 78105 Burner Mounting Plate Rope 1 4 x 4 75 14 60434 Burner Mounting Plate Insulating Block 14 60430 Burner Mounting Plate Insulating Block Beckett Burner 3 6 Section 15 Upper Port Hydronic Seal 16 Lower Port Hydronic Seal 17 60025 Insulating Ceramic Rope 18 Tie Rod Hardware 19 Front Obse...

Страница 3: ...arge cast iron cover plates A slide damper is provided in the flue gas outlet for back pressure adjustment The boilers are supplied completely knocked down for field assembly as factory assembled blocks of sections or completely assembled boiler burner units All items should be inspected for damage upon receipt and any damage reported to the wholesaler and trucker All components should be stored i...

Страница 4: ...must be provided to allow complete combustion of fuel and ventilation of the room to avoid excessively high ambient temperature Air inlet by natural ventilation directly from the outside shall have total free area of not less than one sq in per 14 000 BTU per hour of input of all fuel burning appliances in the boiler room Where combustion air must be obtained through ducts see ANSI NFPA 31 or ANSI...

Страница 5: ...R LEFT 5 FT LBS STEP 4 LOWER RIGHT 5 FT LBS STEP 5 UPPER RIGHT 25 FT LBS STEP 6 LOWER LEFT 25 FT LBS STEP 7 UPPER RIGHT 50 FT LBS STEP 8 LOWER LEFT 50 FT LBS STEP 9 UPPER LEFT 10 FT LBS STEP 10 LOWER RIGHT 10 FT LBS Prepare additional intermediate sections and install in the same manner described above Be sure each section is properly sealed against water leakage and flue gas exfiltration Be certa...

Страница 6: ...he 5 16 x 1 1 2 studs and hex nuts furnished in screw seats in the back section Apply self adhesive insulating tape Items 21 and 22 in Parts detail drawing on Page 2 to smoke hood flange and damper angle Item 23 Fasten the slide damper in the open position for starting the burner adjustment process See FIGURE 6 for recommended L coil piping and FIGURE 7 for SM9 18 single and or dual piping arrange...

Страница 7: ...NION GATE VALVE TEMPERING VALVE FLOW LIMITING VALVE TEMPERATURE GAUGE OPERATING CONTROL TANKLESS HEATER TEMPERED WATER SUPPLY COLD WATER INLET The sealing rope should be placed in the groove on the boiler side of the plate using adhesive to hold it in place The insulation block has a burner opening and a cutout for the observation opening Locate the block with the high temperature facing on the fi...

Страница 8: ...OUT COVERS Be sure the rope seals are in place around the groove in the cleanout cover plate Install the plates on the boiler sections carefully to insure proper sealing all around using the 5 16 x 2 special anchor bolt and 5 16 hex head nuts After periodic flue cleaning replace nuts at 10 lbs torque Use Hi Temp silicone caulk to seal covers air tight 14 REAR OBSERVATION PORTS 7 12 SECTIONS INSTRU...

Страница 9: ...WAYS A STEAM BOILERS NOTE The boiler should be cleaned before connecting system piping and installing steam trim 1 Plug unused openings all around the boiler leaving a valved overflow pipe connected to the safety valve tapping Also provide a valved blow down connection to one of the bottom tappings 2 The fuel burning equipment should be installed and made ready to operate in accordance with the bu...

Страница 10: ...T CONN FRONT VIEW SIDE VIEW TOP VIEW 12 ADAPTER COLLAR 11 12 SECTION ONLY SERIES 19A BOILER STEAM TAPPING AND CONTROL LOCATIONS 3 SUPPLY TAPS 3 4 41 1 4 A 1 TAP AIR REMOVAL CONN OPT LWCO B 1 1 4 TAP SAFETY VALVE C 1 TAP OPTIONAL LWCO D 3 4 TAP OPER TEMP CONN A B VENT CONNECTION 3 4 TAP STD MAN RESET HIGH LIMIT 3 A 4 SUPPLY CLEANOUTS 3 RETURN TAP OPTIONAL INSPECTION TAPPINGS 3 4 TAP OPT OPT INSP TA...

Страница 11: ... monoxide Hot gases from appliance venting system pipes or chimney escaping into the living space Flames coming out around the appliance Yellow colored flames in the appliance Stale or smelly air The presence of soot or carbon in or around the appliance Very high unexplained humidity inside the building If any of the symptoms of CO poisoning occur or if any of the signs of carbon monoxide are pres...

Страница 12: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799 ...

Отзывы: