Issue/Rev. 0.7 (11/17)

Page 2

 • 

MN01045

3.  Mount the UPT Transmitter onto the meter dome  

adaptor. A weatherproof gasket and three 3/8" - 16 x  

 

1-1/4" mounting bolts are provided. Care must be taken 

to properly engage the transmitter coupling or gear to the 
meter drive coupling or gear.

  For adaptation to old style (single case) PD meter (old 

style PD meters include Models AB, AS, B, or S-12, 13, 
24, 28, 30, 35, 42, 45, 50, 60, 65, 75, and 100), also 
mount the 5/8" spacer between the UPT Transmitter and 

meter dome adaptor. An additional weatherproof gasket 
and longer mounting bolts are provided.

4.  If a live calibrator is required to be installed below the 

UPT Transmitter then a UPT calibrator adapter kit is 

required P/N 529288011. If a live calibrator is required on 

top of the UPT Transmitter then a remote calibrator kit is 

required P/N 529288001.

5.  If additional stack accessories are not required, install a 

blind cover plate (10078-1) on the top of the UPT Trans

-

mitter. The manual calibrator and other parts removed in 
previous steps can be discarded (see note below). 

6.  If additional stack accessories are required, reinstall   

the previously removed calibrator and stem assembly 
into the new calibrator adaptor housing located on top  
of the transmitter by reversing the removal procedure 

described in Step 2 above (see note below).

7.  Install oiler in calibrator housing (parts provided in the 

adaptation kit):

  a.  Attach tube to oiler.
  b.  Insert tube through calibrator housing.

  c.  Drive oiler (force fit) into housing.

  d.  Attach oiler tube to top of calibrator, just below drive  

 coupling.

8.  Reassemble the accessories (counter, mechanical tem

-

perature compensator, etc.) onto the calibrator housing. 

9.  Check the calibrator setting and adjust (if necessary) to 

the setting recorded in Step 2b. Recalibration of the me

-

ter may be required due to breaking of seals on original 
calibrator adjustment and is recommended to maintain 
optimum meter accuracy.

  For adaptation to old style PD meters, the meter must be 

recalibrated because the new factory-installed calibrator 
is not adjusted. 

10.If desired, a seal wire can be installed (like a belt) around 

the middle of the UPT Transmitter cover and housing to 
prevent unauthorized tampering with internals.

Note:

 With the calibrator removed from the meter, the oiler

fitting on the PD meter is no longer needed and should be
sealed off.

ATEX/IECEx Installation

Standards Used:

 

IEC 60079-0 6th Edition, EN 60079-0: 2012 +A11:2013, 

 

UL 60079-0 6th Edition, CAN/CSA C22.2 No. 60079-0:11
IEC 60079-1 7th Edition, EN 60079-1: 2014. UL 60079-1 
7th Edition, CAN/CSA C22.2 No. 60079-1:11
Cable entries must be in accordance to EN/IEC 60079-1 

section 13.
For wiring systems utilizing cable glands the gland and or 

thread adaptor must be Ex certified.

The cable end must be securely installed and depending  
on the cable type be properly protected from mechanical 
damage.

For wiring systems utilizing conduit, an Ex certified sealing 

device must be used immediately at the entrance of the 
enclosure. Any unused entry must be suitably blocked  

with an Ex db IIB IP65 certified plug for ATEX and IECEx 

applications.

Equipment bonding shall be provided at the external 
grounding facility terminal, external connection is not 

 

required when using metallic conduit or armored cable. 

External grounding facility terminal wire range: 

 

10-12 AWG (5.26 sq mm to 3.31 sq mm) wire.

CAUTION: 

To prevent ignition of hazardous atmospheres, 

disconnect from supply circuit before opening. Keep tightly 

closed when circuits are in operation.

WARNING: 

To prevent ignition of hazardous atmospheres, 

do not open enclosure unless area is known to be non-

 

hazardous. To reduce the risk of ignition of hazardous 

 

atmospheres, conduit runs must have a sealing fitting 

 

connected within 18 inches of the enclosure.

Special Conditions For Safe Use:

- Special Fasteners: Cover Bolts - DIN 912 grade 12.9 (alloy 
steel) M8 x 1.25, thread tolerance 6g, only replace with this 

type.

- Select wiring and cable glands suitable for 80°C operation.
- Contact manufacturer at address listed for information on 
the dimensions of the flameproof joints.

FMC Technologies Measurement Solutions Inc.

 

1602 Wagner Avenue

 

Erie, Pennsylvania 16510  
USA

 

 

 

 

 

 

Marking

Equipment 

Covered

Certificate

Ex db IIB T6

Tamb = -40°C to 70°C IP65

Model: UPT

DEMKO 03 ATEX 0308254X

IEC Ex UL 04.0009X

Содержание UPT

Страница 1: ...nnsylvania 16514 Prior to installation the unit should be stored in its original packing case and protected from adverse weather condi tions and abuse Mechanical Installation When ordered with a Smith...

Страница 2: ...ed 10 If desired a seal wire can be installed like a belt around the middle of the UPT Transmitter cover and housing to prevent unauthorized tampering with internals Note With the calibrator removed f...

Страница 3: ...nnections Rotation of Transmitter Shaft Reference Dimensions Drawing Below Electronics Ground white 1 Input Power 12 24 Vdc brown 2 Counter Clockwise Clockwise Channel B Output grey 3 Leading Lagging...

Страница 4: ...acket from enclosure b Remove screws holding T Bar in place 1 2 3 4 5 6 7 8 9 9 8 7 6 5 4 3 2 1 Step 4a Step 4b Step 3 Remove the coupling and pull the shaft out Step 2 a Remove hairspring cotter pin...

Страница 5: ...minal block Step 7 Inspect terminal block and encoder for damage corrosion or wear and replace if needed Step 6 Step 8 a Re insert o ring tighten cover over o ring and then tighten aluminum piece with...

Страница 6: ...m is approximately 1 8 above the T bar base Note Ensure that the washer is between the cotter pin and the housing Apply a light coat of Loctite 222 included to the set screw threads prior to tightenin...

Страница 7: ...l corrosion protection to the flame path TechnipFMC synthetic grease P N 644886401 is recommended Apply a nickel based anti size lubricant to all cover fasteners TechnipFMC P N 646002401 is recommende...

Страница 8: ...moisture can enter into the UPT housing TechnipFMC com TechnipFMC 2017 MN01045 Issue Rev 0 7 11 17 TechnipFMC FMC Technologies Measurement Solutions Inc 500 North Sam Houston Parkway West Suite 100 Ho...

Отзывы: